CyberPower BP240VL3U01 Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor CyberPower BP240VL3U01 (1 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 21 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/1
1
2
3
4
5
6
7
8
9
2U
3U
4U
1U






1. Switch EBM DC breaker to the ON position.
2. Switch the utility circuit breaker feeding the UPS
to the ON position.
3. Turn the UPS ON – push and hold the ON/OFF
power button for 3 seconds; you will hear
continuous beeps, the BATTERY ON yellow
LED will first turn on for a couple of seconds
followed by the ON-LINE green LED.
4. Customize UPS system configuration settings as
needed. See User’s Manual for complete details.
User Manual is available to download on
www.CyberPowerSystems.com.
5. Connect equipment load to the UPS system.
1. Install rack mount ears to the extended battery
module (EBM) using eight black M5X7L flat head
screws. Install hanging brackets using six silver
M5X6L pan head screws.
2. Locate the space where the extended battery
module will be installed in the rack.
3. Install the rackmount rails using eight black
M5X12L pan head screws with plastic washers
and adjust the rails to the necessary rack depth.
4. Place the extended battery module on to the
rackmount rails. Make sure both left and right
hanging brackets are securely on the rackmount
rails. Secure the extended battery module with
the rack mount ears to the rack using four black
M5X12L pan head screws.
BP240VL3U01/ BP240VL3U02
QUICK START GUIDE
K01-0000704-00
UNPACKING
RACKMOUNT INSTALLATION
TOWER INSTALLATION
CONNECTING UPS TO
EXTENDED BATTERY MODULE
CONNECTING UPS TO MULTIPLE
EXTENDED BATTERY MODULES
EXTERNAL BATTERY MODULE CONFIGURATION
POWER ON THE UPS SYSTEM
1. Turn o the DC breaker on the EBM.
2. Loosen the two screws to remove the battery
cable retention bracket of the power module.
3. Use the output cable of the EBM to connect it
to the power module.
4. Rotate the battery cable retention bracket
and tighten the two screws to secure the
battery connector.
5. Turn on the DC breaker on the EBM.
1. Connect the 1st EBM to the UPS power module
following the “Connecting UPS to Extended Bat-
tery Module” instructions.
2. Turn o the DC breaker of the 2nd EBM.
3. Loosen the two screws to remove the battery
cable retention bracket of the 1st EBM.
4. Use the output cable of the 2nd EBM to con-
nect it to the 1st EBM. Rotate the battery cable
retention bracket and tighten the two screws to
secure the battery connector.
5. Turn on the DC breaker on the 2nd EBM.
6. Proceed to the External Battery Module
Configuration instructions to set the EBM
Number to the quantity of additional units
installed with the UPS system. This operation
can also be done if there is an RMCARD
installed in the UPS, or via PowerPanel®
Business Edition Agent software. Please see
their respective User’s Manuals for instructions.
1. Adhere four circular rubber pads to the left hand
side of the extended battery module. This will
become the bottom side.
2. Stand the extended battery module on its
side with the rubber pads facing down. Install
dust covers on open screw holes. If installing
the extended battery module together with a
UPS or an additional EBM secure the tie plate
between the two using four black M5X7L flat
head screws. Optionally adhere four circular
rubber pads to each rack mount ear to use as
tower stands. Screw the tower stands on to the
EBM and UPS using four black M5X12L pan head
screws for added stability as shown below.
1
3 41 Rack mount ear
Rack mount rail
2
This document is believed to be accurate, but CyberPower reserves the right to change or correct the contents and does not
assume any responsibility for omissions or errors. Entire contents copyright ©2018 CyberPower Systems, Inc. All rights reserved.
Reproduction in whole or in part without permission is prohibited.
Need Additional Help? Feel free to contact our Tech Support department with installation, troubleshooting,
or general product questions.
CyberPower Technical Support | 1-877-297-6937 | tech@cpsww.com | www.CyberPowerSystems.com
Mailing Address: 4241 12th Avenue E, Suite 400, Shakopee, MN 55379, USA
Hours of Operation: MondayFriday, 7:00am–6:00pm (CST)
IEC320 C14 TO IEC320 C13
POWER CORD RT GUIDE x1
LEFT & RIGHT RACKMOUNT
RAILS x1 EACH
LEFT & RIGHT HANGING
BRACKETS x1 EACH
3U RACKMOUNT EARS
(TOWER STANDS) x2
TOWER INSTALLATION
TIE PLATE x1
M5X7L BLACK FLAT
HEAD SCREWS x8
M5X12L BLACK PAN
HEAD SCREWS x12
QUICK START GUIDE x1REGISTRATION CARD x2EXTENDED BATTERY
MODULE (EBM) x1
M5X6L SILVER PAN
HEAD SCREWS x6
PLASTIC WASHERS x8SCREW HOLE DUST
COVERS x14
RUBBER PADS x12
CAUTION! Installation environment should be in a temperature and humidity controlled indoor area free of conductive
contaminants. Do not install this EBM where excessive moisture or heat is present (Please see specifications for acceptable
temperature and humidity range).
CAUTION! Never install an EBM, or associated wiring or equipment, during a lightning storm.
CAUTION! Do not work alone under hazardous conditions.
CAUTION! Risk of electric shock, do not remove top cover.
CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected.
CAUTION! Only use replacement batteries which are certified by Cyber Power Systems. Use of incorrect battery type is an electrical
hazard that could lead to explosion, fire, electric shock, or short circuit.
CAUTION! Batteries contain an electrical charge that can cause severe burns. Before servicing batteries, please remove any
conductive materials such as jewelry, chains, wrist watches, and rings.
CAUTION! Do not open or mutilate the batteries. Electrolyteuid is harmful to the skin/eyes and may be toxic.
CAUTION! To avoid electric shock, turn o and unplug the EBM from the wall receptacle (if installed) before servicing the battery.
CAUTION! Only use tools with insulated handles. Do not lay tools or metal parts on top of the UPS or battery terminals.
CAUTION! To prevent the risk of fire or electric shock, only use the supplied hardware to attach the mounting brackets.
1
OFF
External Battery Modules can be configured by the
user to display correct estimated battery runtimes.
1. Press the “ ” button to activate the ENTER
MAIN MENU.
2. Press the “p” and “ ” buttons to scroll to the q
Configure” menu.
3. Press the “ENTER” button to select the
Configure” menu.
4. Press the “p” and “ ” buttons to scroll to the q
EBM Number” option.
5. Press the “ ” button to select the ENTER
EBM Number” option.
The first configuration number will be displayed
on the second column of LCD display.
6. Press the “p” and “ ” buttons to scroll through q
the number of attached Battery modules.
NOTE: The first EBM is recognized by the UPS
system as number zero “0”. Set the EBM Number
to the quantity of additional units installed with
the UPS system.
7. Press the “ ” button to select the number ENTER
of EBM installed.
You will be prompted to save the selection.
Press the “ENTER button to save.
8. Press the “ ” button to cancel or return ESC
to the previous LCD menu.
IMPORTANT SAFETY INSTRUCTIONS
This Quick Start Guide contains important instructions. Please read and follow all instructions carefully
during the installation and operation of the unit. Read this Quick Start Guide thoroughly before
attempting to unpack, install, or operate this unit.
PLUG INTO A
WALL
RECEPTACLE
RELA Y
OUT PUT
OUT
IN
USB
RS23 2
BACK -FEED PROT ECTI ON
CON NECT OR
BATT ERY INPU T : 240V
EPO
IN TERF ACE
FU SE
250V~
10A
AC INPU T
(Cha rge Only )
AC OUTP UT
240V
BATT ERY OUTPU T
BATT ERY INPU T
240V
1
OUT PUT BREAKE R
30A/250V~
OUT PUT BREAKE R
30A/250V~
NON CRI TICA L
LOAD
21
CR ITIC AL LOA D43
IN PUT BREAKER
63A / 250V~

















































2
CONFIGURE SUBMENU AVAILABLE SETTINGS DEFAULT SETTINGS
EBM Number
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
Sets the quantity of EBM (extended
battery modules) number to get the
correct estimated runtime.
0
42

  



3
ON
1 2
2
OFF
43


Product specificaties

Merk: CyberPower
Categorie: Niet gecategoriseerd
Model: BP240VL3U01
Kleur van het product: Zwart
Gewicht: 76000 g
Breedte: 433 mm
Diepte: 660 mm
Hoogte: 132 mm
Accu/Batterij voltage: 12 V
Certificering: UL 1778\nCSA C22.2 NO.107.3-05\nFCC Part 15 Class A
Duurzaamheidscertificaten: RoHS
Accu/Batterij oplaadtijd: 4 uur
Temperatuur bij opslag: -20 - 45 °C
Luchtvochtigheid bij opslag: 0 - 95 procent
Aantal inbegrepen batterijen: 20 stuk(s)
Hoogte, in bedrijf: 0 - 3000 m
Hoogte bij opslag: 0 - 15000 m
Compatibiliteit: OL6KRT, OL6KRTF, OL8KRT, OL8KRTF, OL10KRT, OL10KRTF, OL10KRTHW
Bedrijfstemperatuur (T-T): 0 - 40 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 90 procent
Batterijtechnologie: Sealed Lead Acid (VRLA)
Hot-swap batterij: Ja

Heb je hulp nodig?

Als je hulp nodig hebt met CyberPower BP240VL3U01 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd CyberPower

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd