Rack Air Containment System (ACCS1000–
ACCS1007)—Overview
Introduction
The Rack Air Containment System (RACS) is a mechanical ducting system that attaches to the front
or rear of an enclosure to provide increased cooling capacity. The RACS is a modular system that
works with APC® NetShelter® SX enclosures and InRow® cooling units to provide maximum
cooling predictability, capacity, and efficiency. By attaching the RACS to the rear of the NetShelter
SX, air expelled from IT equipment is forced to pass through the cooling unit, where it is
conditioned. This ensures that warm exhaust air does not enter the air inlets of installed servers.
Redundant configurations allow maximum availability. Optional front containment configurations
reduce noise and provide additional control of air flow. The RACS components can be attached to a
single enclosure or a group of enclosures. The RACS consists of eight components that can be
installed separately or together, depending on your configuration.
ACCS1000—Rear containment for InRow RC or SC cooling units
ACCS1001—Rear containment for NetShelter SX and InRow RP cooling units
ACCS1002—End caps for any rear- or front-containment configuration
ACCS1003—Front containment for InRow RC or SC cooling units
ACCS1004—Front containment for InRow RP cooling units
ACCS1005—Front containment for NetShelter SX enclosures
ACCS1006—Rear containment for NetShelter SX 750-mm enclosures
ACCS1007—Front containment for NetShelter SX 750-mm enclosures
Features of the RACS
Rear containment—Ensures server exhaust air is returned to the InRow cooling unit for
maximum cooling predictability. Prevents recirculation of hot exhaust air.
Front containment—Ensures cold supply air is not captured by neighboring equipment.
Modular design—Compatible with standard NetShelter SX enclosures, providing maximum
system flexibility and scalability.
Redundant configurations—Provide N + 1 or uding additional InRow 2N redundancy by incl
cooling units.
Clear polycarbonate door inserts—Provide required air containment while allowing visibility
to installed IT equipment and a consistent appearance across enclosures.
Lockable doors—Provide enclosure security.
Noise reduction—Containment of both the front and rear of the enclosure reduces the level of
noise generated by the installed equipment.
• ACCS1000—Rear containment for InRow 300mm cooling units
• ACCS1001—Rear containment for NetShelter SX and InRow RP cooling units
• ACCS1002—End caps for any rear- or front-containment configuration
• ACCS1003—Front containment for InRow 300mm (100 series) cooling units
• ACCS1004—Front containment for InRow 600mm cooling units
• ACCS1005—Front containment for NetShelter SX enclosures
• ACCS1006—Rear containment for NetShelter SX 750-mm enclosures
• ACCS1007—Front containment for NetShelter SX 750-mm enclosures
• ACCS1009—Front containment for InRow 300mm (300 series) ACRC301S/H
Rack Air Containment System (ACCS1000–
ACCS1009)—Overview
Rack Air Containment System Overview—ACCS1000-ACCS10072
Compatibility
The RACS can be coupled with one or more NetShelter SX enclosures in the following configurations:
A ducted return and flooded supply configuration
A ducted return and ducted supply (recommended configuration for uncontrolled environments)
The configurations listed in the following table and shown in the following figure provide hot air
retrieval and provide coupling for either redundancy or capacity.
Number of NetShelter
SX Enclosures
Number of InRow RC or
SC cooling units
Number of InRow RP
cooling units
1 1 or 2 1
2 2, 3, or 4 1 or 2
na2207a
InRow RC or SCInRow RP
SX RackSX Rack
SX Rack
SX Rack SX Rack
SX Rack SX Rack
RCRC
RC
RC
RC
RC
RC
RC RC
SX Rack
RP
SX Rack SX Rack
SX Rack
SX Rack
SX Rack
RP RP
RP RP
SX Rack
RC RC
SX Rack
RC RC
2 + 2
2 + 3
2 + 4
2 + 1
2 + 2
3Rack Air Containment System Overview—ACCS1000-ACCS1007
Cross-reference symbols
If you need to remove and reinstall other equipment in order to install the RACS, see the documentation
provided with that equipment for instructions.
Tools required
Safety and handling
Note: The RACS is only intended for use with APC NetShelter SX enclosures.
Upon installation of this RACS, firmware reconfiguration of the cooling system is required.
For configuration information, see the Operation manual for your cooling unit.
Caution: The air conditioners included in the system must have a capacity exceeding the
load in the racks. Temperatures will exceed safe limits if the load exceeds the cooling
capacity.
Caution: Do not install the RACS in ambient environments where the dew point (the
temperature at which condensation begins) is expected to be greater than 18.3°C (65°F).
When you see this symbol in the RACS installation instructions, see the installation
manual of the unit for detailed instructions.
When you see this symbol in the RACS installation instructions, read the RACS System
Overview ACCS1000–ACCS1007 sheet before continuing with the installation of the
equipment. This brief document is packaged with the Rack Air Containment End Caps
(ACCS1002) and is available at the APC Web site, www.apc.com.
#2 Phillips screwdriver T30 Torx® screwdriver 10-mm wrench


Product specificaties

Merk: Apc
Categorie: Niet gecategoriseerd
Model: ACCS1009
Kleur van het product: Zwart, zilver
Gewicht: 13640 g
Breedte: 300 mm
Diepte: 196 mm
Hoogte: 1911 mm
Gewicht verpakking: 22550 g
Breedte verpakking: 508 mm
Diepte verpakking: 2032 mm
Hoogte verpakking: 152 mm
Soort: Voorpaneel
Met slot: Ja
Certificering: REACH
Duurzaamheidscertificaten: RoHS
Code geharmoniseerd systeem (HS): 85389099

Heb je hulp nodig?

Als je hulp nodig hebt met Apc ACCS1009 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Apc

Apc

Apc SP3OPT008 Handleiding

26 Februari 2024
Apc

Apc P4V Handleiding

27 November 2023
Apc

Apc ACRC100 Handleiding

31 Augustus 2023
Apc

Apc UTS10BI Handleiding

3 Augustus 2023
Apc

Apc AP7768 Handleiding

3 Augustus 2023
Apc

Apc UTS6H Handleiding

3 Augustus 2023
Apc

Apc PDPM144F Handleiding

3 Augustus 2023

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd