Andrews ET15 Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Andrews ET15 (2 pagina's) in de categorie Airconditioner. Deze handleiding was nuttig voor 30 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
Click www.andrews-sykes.com
or Call Us Free 0800 211 611
ET15
Portable Air Conditioning
Operating Instructions
& Safety Guide
General Safety
Keep children and animals away from air conditioning units.
Never leave them alone in a room where the units in use.
This equipment should only be used by a competent person who has read
and understood these instructions.
Never operate this equipment if you are ill, feeling tired or under the influence
of alcohol or drugs.
Keep the Air Conditioning vents clear of all obstructions.
Never put anything on top of the unit or block the air outlets.
Make sure equipment is switched off and unplugged after use
Never leave switched on or unattended.
Do not use the unit where sunlight is shining directly onto it.
Check condition of equipment before use. If unit is showing signs of damage
contact your supplier immediately.
Electrical Safety
This unit requires a 230 volt electrical supply. It plugs into a standard BS1363
domestic socket.
Always inspect plugs and leads for damage before plugging into the supply -
DO NOT USE IF ANY DAMAGE IS FOUND
Ensure cables are run as not to cause a hazard.
If an extension lead is used, ensure it is of the correct standard , and fully
uncoiled when being used.
Do not lay electrical cables in wet / damp areas.
Do not move equipment whilst operating.
Do not pull equipment by its cable.
It is recommended that electrical equipment is used via a suitable RCD.
WARNING!
This unit MUST be transported and operated in the upright position at all times
Electrical Supply
As standard this unit requires a 13 amp fused electrical supply rated at 230v 1ph 50hz.
The unit will operate from a standard 13A wall socket. The size of any extension
cable that may be 2-5mm2 minimum up to a maximum length of 10 metres. For
longer lengths 4mm2 cable must be used. If the cable is on a ‘cable drum’ then
ensure that it is completely unwound; serious complications will occur otherwise.
NOTE: most domestic proprietory extension cables are 1.5mm². This is not sufficient.
Air Cooled Units
The system comprises, a room unit fitted with either a fixed orexible ducting system
as specified by the customer. Condensate is collected, either in the units internal tank
and emptied by the user or pumped using an optional condensate disposal unit (fig. 1).
Air Flow
The angled air outlets at the top of the room unit are fitted with air grilles that allow the
angle of air outlet to be adjusted vertically and horizontally and, in conjunction with the
fan speed control switch, the air velocity and direction can be carefully set up to obtain
maximum coverage of the area being cooled without causing drafts. Care should be
taken to avoid outlet air being obstructed as this will cause the air to ‘eddy’ around the
unit resulting in recirculation and short/inaccurate cycling of the machine. Ideally, cold
air should be directed to create ablanketall across the ceiling area allowing natural
convection to drop the air over the whole area at very low velocity. An alternative top
panel with twin 7” ducts is available.
Siting of ET 15
Ideally, the room unit should be positioned equidistant along he shortest wall in the
room blowing down the length of the room. Of there is more than one unit in the
same area, then they would normally be positioned side by side, and equidistant
along the long wall, all pointing in the same direction. Sometimes it may be
necessary to position units around the perimeter of an area but, in this case, great
care should be taken t avoid one unit blowing cold air straight into another which
will adversely affect the machine operation. Good and correct air flow is, perhaps,
the single most important aspect of satisfactory applying portable air conditioners.
If in doubt seek the advice of your supplier.
Exhaust Tubes Air Cooled Unit
The exhaust tube(s) must carry the air to an area external to that being cooled,
preferably in the outside atmosphere (fig. 1).
Fitting the hot air exhaust
Keep the exhaust pipes as straight as
possible. Do not allow to sag.
Operating Instructions - ET15
Click www.andrews-sykes.com or Call Us Free 0800 211 611
Operation Instructions
The control panel on the room unit is illustrated above
Revolve thermostat knob fully CLOCKWISE to the number ‘8’ position
Plug in the room unit mains cable, and switch on the electricity, red mains
light will illuminate.
Select ‘Fan Only’ with the mode switch. The fan will start.
Select ‘Fan Speed’ with the fan speed switch, high or low depending on air
velocity required.
Select ‘Cooling’ with the mode switch, and revolve the thermostat knob fully
ANTI-CLOCKWISE to he number ‘1’ position. After a delay of 10 mins the
green ‘Cooling’ light will illuminate and the machine will proceed to cool the air.
Monitor the room temperature and when it has reduced to the desired level, very
slowly revolve the thermostat knob back, clockwise until the green ‘Cooling’
light goes out. The room unit will now control the room temperature cooling
automatically at this setting.
Routine Maintenance
The airlter must be kept clean, never allow to become choked with dust or dirt. If
allowed to do so, the performance of the unit will become impaired, resulting in loss of
air flow, freezing up the evaporator coil and possible component damage.
Accessing the Filter
On machines fitted with a hinged lower panel, open panel. The filter is located on
front of the evaporator. A second filter is fitted to the rear panel on all air cooled
machines (fig. 5 & 6).
The filter can be washed in warm, soapy water, rinsed and shaken dry before
replacement. Frequency of cleaning depends upon application and can only be
determined by the user. However, you should never allow more than two months
to elapse between cleaning. The probable life of thelter will be about one year
and spares are available from the supplier of the unit itself. Failure to havelter fitted
during operation will cause serious damage.
Problem Likely Cause Solution
No cooling Amber ‘ATTENTION’ light
illuminated. High level
condensate trip.
Condensate pump not reducing water level.
Kink in condensate tube between room unit
and external heat exchanger?
Leak inside room unit. Pumplter inside
room unit blocked. Condensate tube frozen.
No cooling Amber ‘ATTENTION’ light
illuminated. Bottle fitted
switch trip.
ensure bottle fitted correctly.
No cooling Amber ‘CONTAINER FULL
light illuminated. High level
condensate trip.
On machines without a removable
bottle, as above. On machines with a
bottle, remove container and replace
correctly.
To empty the condensate bottle:
Unscrew the 2 x thumb screws on the
front panel (fig. 2).
The front cover will hinge forward, giving
access to the container (fig. 3).
Empty the container, and carefully
replace (fig 4).
Ensure the drain pipe is fitted into the
container.
Fig. 5 - The filter is located on the rear of the unit, ensure it is kept clean.
Fig. 6 - And in the top of the hinged section, in front of the evaporator.
Fig.2
Fig.1
Fig.3 Fig.4
Fig.6
Fig.5
Fitting the hot air exhaust


Product specificaties

Merk: Andrews
Categorie: Airconditioner
Model: ET15

Heb je hulp nodig?

Als je hulp nodig hebt met Andrews ET15 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Airconditioner Andrews

Handleiding Airconditioner

Nieuwste handleidingen voor Airconditioner