Vimar 01975 Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Vimar 01975 (1 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 26 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/1
Viale Vicenza, 14
36063 Marostica VI - Italy
www.vimar.com
49400437A0 05 2105
01975
SMART AUTOMATION BY-ME PLUS
Actuator with output 1-10 V d.c. 30 mA for driver LED control,
relay output 120-230 V 2,5 A, power supply 120-230 V~ ~
50-60 Hz, installation on DIN rail (60715 TH35), occupies 3
modules of 17.5 mm. Version for MARINE applications.
Actuator for driver LED with 1-10 V control. The device is controlled by a rocker
push-buttons. The device’s maximum output current is 30 mA.
CHARACTERISTICS.
• Rated supply voltage: BUS 29 V
• Input: 10 mA
• Auxiliary supply: 120-230 V~ ± 10%
• Consumption: 25 mA
• Dissipated power: 1,6 W
• Distance between actuator and LED driver: 10 m max with twisted cable
• Terminals:
- TP BUS
- 120-230 V~ 50-60 Hz
- relay contacts (C, NC, NO)
- control 1-10 V
• Changeover relay outputs
• Controllable loads at 120-230 V~
- resistive loads: 2,5 A (20.000 cycles)
- LED spot lights: 2,5 A (20.000 cycles)
• Operating temperature: -5 °C - +45 °C (for indoor use)
• 3 modules of 17.5 mm.
CONNECTIONS.
The wire diagram (bottom right) shows an example of a connection with an LED
driver. Depending on the type of LED driver used, the connection of terminal to L
the LED driver through the relay contacts integrated in device 01975 may not be
necessary; in this case, connect terminal directly to the electric phase.L
The feeding circuit of the relay output must be protected against overloads by a
device, fuse or automatic circuit breaker, with rated current not higher than 10 A.
CONFIGURATION.
FOR THE DETAILS OF INSTALLATION AND CONFIGURATION, SEE THE
By-me SYSTEM INSTRUCTIONS MANUAL.
• Functional blocks: 1; the block can belong to at most 4 groups.
• Selecting the functional block (configuration), when the control unit, during group
creation, requires pressing the device button:
- press the configuration button, the red LED will light up;
- with the red LED on, the control unit will configure the functional block; at the end
of this operation the red LED will go out.
PARAMETERS.
• adjustment speed: low, medium or high;
• LED always off or on only with dimmer on.
• Parameter offset: minimum output voltage adjustable from 1 to 2 V (default value
1,2 V).
• Default parameters: dimmer actuator with medium adjustment speed, LED
always off and offset of minimum output voltage.
SCENARIOS.
The actuator can belong to up to 4 different scenarios and, for each scenario, save
the status to retrieve when activating the scenario.
INSTALLATION RULES.
Installation should be carried out by qualified personnel in compliance with the
current regulations regarding the installation of electrical equipment in the country
where the products are installed.
For further instructions, please refer to the manual enclosed with the control panel.
CONFORMITY TO STANDARDS.
LV directive. EMC directive.
Standards EN 50428, EN 50491.
For MARINE use, this device has been submitted to the following tests:
IEC 60068-2-52 - Test Kb: Salt mist, cyclic (sodium, chloride solution),
IEC 60068-2-6 - Test Fc: Vibration (sinusoidal)
This device complies with part 15 of the Rules (with the limits for a Class B FCC
digital device). Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause undesiderable
operation.
REACH (EU) Regulation no. 1907/2006 – Art.33. The product may contain traces
of lead.
ACTUATOR 1-10V
2,5A 120-230V
01975
120-230V 2,5A 120-230V
N L NC
NO
C
1-10V BUS 30mA
By-me CONF.
FRONT VIEW AND CONNECTIONS.
Configuration Led.
Configuration button.
BUS lineConnection to
the LED driver
C
NO
120-230 V~
ACT UA R 1-10VTO
2,5A 120-230V
01975
120-230V 2,5A 120-230V
N L NC
NO
C
1-10V BUS 30mA
By-me CONF.
L N
LED Driver
LED
Lamp
FUSE
L
N
+
-
1-10 V
bus line
120-230 V
+ -
EXAMPLE OF CONNECTION.
NC
WEEE - Information for users
If the crossed-out bin symbol appears on the equipment or packaging, this means the product must not be
included with other general waste at the end of its working life. The user must take the worn product to a
sorted waste center, or return it to the retailer when purchasing a new one. Products for disposal can be con-
signed free of charge (without any new purchase obligation) to retailers with a sales area of at least 400 m 2,
if they measure less than 25 cm. An efcient sorted waste collection for the environmentally friendly disposal
of the used device, or its subsequent recycling, helps avoid the potential negative effects on the environment
and people’s health, and encourages the re-use and/or recycling of the construction materials.


Product specificaties

Merk: Vimar
Categorie: Niet gecategoriseerd
Model: 01975

Heb je hulp nodig?

Als je hulp nodig hebt met Vimar 01975 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Vimar

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd