Vemer EV2M-4DIN Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Vemer EV2M-4DIN (2 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 25 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
Mod. EV2M-2DIN
EV2M-4DIN
EV2M-R
V3IS00443–010
EV2M-2DIN
EV2M-4DIN
EV2M-R
EV2M-2DIN
EV2M-4DIN
EV2M-R
EV2M-2DIN
EV2M-4DIN
EV2M-R
Power supply connection terminals
Voltage reading window
Current reading window
Parameter setting key
Metering connection terminals
36 60
45
65
88
72 60
45
65
87
5
72 75
72
66
L
N
1
3
5
6
8
COM I V
LOAD
L
N
COM I V
1
3
10
11
13
LOAD
5 4 3 12
L
N
LOAD
P1P2
P1P2
P1P2
EV2M-2DIN
TRUE RMS
kA
V
A
Prg
Input 5(6)A 600 V~
PRG
A
V
Input 5(6)A~ 600 V~
TRUE RMS
kA
EV2M-4DIN
V
A
kA
EV2M-R
TRUE RMS
Input 5(6)A 600 V~
Prg
User Manual
DIGITAL VOLMETER-AMMETER
Read all the instructions carefully
The EV2M meters are digital multimeters to measure TRMS values (true
root mean square values) for alternate voltage and current. It reads these two
quantities simultaneously on two 3-digit LED displays.
SAFETY WARNINGS
During the installation and operation of the instrument, proceed in accordance
with the instructions below:
1) The instrument should be installed by a competent operator following the
installation diagrams carefully
2) Before touching the connector terminals make sure that the wires to be connected
or already connected to the instrument are not live
3) The instrument should be installed in a panel from which no access can be gained
to the terminals after installation
4) Do not power or connect the instrument if any part of it is damaged
5) The electrical system of the building in which the instrument is to be installed
should have a switch and a protective device against over-currents
6) The instrument is designed for installations with over-voltage category III and
pollution level 2, in accordance with the EN 61010-1 standard.
Code Model Description
VE149100 EV2M–2DIN Voltage-current reading meter 2 DIN
VE196200 EV2M–4DIN Voltage-current reading meter 4 DIN
VE195400 EV2M–R Voltage-current reading meter 72 x 72
TECHNICAL SPECIFICATIONS
Power supply: 230 V AC (-15%/+10%), 50/60 Hz
– maximum consumption: 4 VA
Measurement of true root mean square (TRMS) values for voltage and current
Voltmeter connection:
– connection type: direct
– maximum voltage: VMAX = 600 V
– maximum consumption: 2,5 VA
Ammeter connection:
– connection type: by AT x/5 A
– available scales: from 5/5 A to 1000/5 A
– maximum and nominal current rating: In = 5 A; IMAX = 6 A
– maximum consumption: 2,5 VA
Reading filter (update speed)
Maximum section of wires:
– 6 mm2 for model EV2M-2DIN and EV2M-4DIN
– 2,5 mm2 for model EV2M-R
Operating conditions:
– operating temperature: –10 ÷ +45 °C
– relative humidity: 10% ÷ 90% non-condensing
Storage temperature: –20 ÷ +60 °C
Display: 7-segment LED digit display
Enclosure:
– 2 module DIN, RAL 7035 gray for EV2M-2DIN
– 4 module DIN, RAL 7035 gray for EV2M-4DIN
– standardized dimensions 72 x 72 mm according to DIN 43700 for EV2M-R
Protection rating: IP51 on the front
RESOLUTION AND ACCURACY
Voltage (full scale V MAX
= 600 V):
– Maximum reading: 615 V
– Minimum reading: 10V
– Resolution: 1V
– Accuracy: ± 0,5% full scale ± 1 digit (from 3% to 100% of full scale value)
Current (full scale In = 5 A):
– Maximum reading: 6 A
– Minimum reading: 0,02 A
– Resolution: 0,01 A
– Accuracy: ± 0,5% full scale ± 1 digit (from 3% to 100% of full scale value)
Note: current data refer to the values provided by the amperometric transformer;
maximum and minimum readings directly depend on the AT ratio used, whereas
resolution is dependent on the scale used, as described below.
OPERATION
During normal operation the device reads the Voltage value (Volts) in the top window and the
current value (Amperes) in the bottom window.
The current value is automatically read in the most appropriate scale:
0,01 A resolution in the 0,02 A ÷ 10 A range (e.g.: )6.47
0,1 A resolution in the 10 A ÷ 100 A range (e.g.: )39.1
1 A resolution in the 100 A ÷ 1000 A range (e.g.: )528
10A resolution for values above 1000 A (e.g.: : )1.03
In the latter case the value is expressed in kA with the decimal point lit after the first digit and
the LED point lit to the right of the last digit above the kA symbol
SETTINGS
After switching the device on it is possible to check and/or change some of the factory settings
by pressing or holding down the key according to the procedure described below.Prg
Press the Prg key
The voltage and current reading displays will read a value
referring to the transformer primary (factory setting: 5).
To change this value, hold down the key for at least 2 Prg
seconds until the digits fl ash. Then press and hold the key
pressed until the desired value is reached (the reading will
increase by 5-unit steps; 1000 is read as ).001.
After a few seconds from the moment the key is released, a value
will indicate the reading fi lter (factory value: 10). The lower this
value, the faster the readings will be updated, the higher the
value, the more stable the reading will be.
To change this value, hold down the key for at least 2 Prg
seconds until the digits fl ash. Then press the key repeatedly
until the desired value is set (the reading will increase by 1-unit
steps; the value range is from 1 to 20).
After one of these parameters is set the device will go off and
then on again using the new parameters. The device is reset
automatically with no need to disconnect it from the power supply.
ERROR MESSAGES
Memory error: EEE
The device has undergone damage that jeopardizes operation
Overload error: KKK
The quantity measured (voltage and/or current) has exceeded the
maximum admissible value: V > 1,02 x VMAX; I > 1,2 x In.
Reset is automatic.
REFERENCE STANDARS
Conformity to the EU directives:
2006/95/CE (Low Voltage)
89/336/CEE mod. modified by 92/31/EEC and 93/68/EEC (EMC)
is declared with reference to the following harmonised standards:
EN 61010-1, EN 61000-6-2 and EN 61000-6-4
Dimensions
Dimensions
Dimensions
Connection
Connection
Connection
Description
Description
Description


Product specificaties

Merk: Vemer
Categorie: Niet gecategoriseerd
Model: EV2M-4DIN

Heb je hulp nodig?

Als je hulp nodig hebt met Vemer EV2M-4DIN stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Vemer

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd