Bekijk gratis de handleiding van Tripp Lite PDUMV20 (12 pagina’s), behorend tot de categorie Stekkerdoos. Deze gids werd als nuttig beoordeeld door 48 mensen en kreeg gemiddeld 4.9 sterren uit 24.5 reviews. Heb je een vraag over Tripp Lite PDUMV20 of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/12

Owner’s Manual
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed
during the installation, operation and storage of this product. Failure to
heed these instructions and warnings may affect the product warranty.
1
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Important Safety Instructions
• ThePDUprovidesconvenientmultipleoutletsbutitDOESNOTprovidesurgeorlinenoise
protectionforconnectedequipment.
• ThePDUisdesignedforindooruseonlyinacontrolledenvironmentawayfromexcessmoisture,
temperatureextremes,conductivecontaminants,dustordirectsunlight.
• DonotconnectthePDUtoanungroundedoutletorextensioncordsoradaptersthateliminatethe
connectiontoground.
• Useofthisequipmentinlifesupportapplicationswherefailureofthisequipmentcanreasonablybe
expectedtocausethefailureofthelifesupportequipmentortosignificantlyaffectitssafetyor
effectivenessisnotrecommended.Donotusethisequipmentinthepresenceofaflammable
anestheticmixturewithair,oxygenornitrousoxide.
• ThepowerrequirementforeachpieceofequipmentconnectedtothePDUmustnotexceedthe
individualoutlet'sloadrating.
• ThetotalpowerrequirementforequipmentconnectedtothePDUmustnotexceedthemaximum
loadratingforthePDU.
• DonotdrillintoorattempttoopenanypartofthePDUhousing.Therearenouser-serviceableparts
inside.
• DonotattempttomodifythePDU,includingtheinputplugsandpowercables.
• DonotattempttousethePDUifanypartofitbecomesdamaged.
• DonotattempttomountthePDUtoaninsecureorunstablesurface.
• Neverattempttoinstallelectricalequipmentduringathunderstorm.
Rack PDU
Metered Models: PDUMV15 and PDUMV20
Basic Models: PDUV15 and PDUV20
Español – p. 5 • Français – p. 9
©2014TrippLite.Allrightsreserved.
14-02-334-933043.indd 1 3/26/2014 11:52:06 AM

2
1B
1A
3
4
5
PDUMV15 and
PDUV15
PDUV20 and PDUMV20
PDUV20 and PDUMV20
1C
3
2
Installation
1A
Zero U Rack Configuration.Attachthethreemountingclips
suppliedwiththePDUtotherackenclosureusingtheincluded
hardware.Themountingclipsshouldbeattachedalonga
verticalplaneatequidistantpointswhichroughlycorrespond
tothecenterandendsofthePDU.Theexactmounting
configurationmayvarydependingontherackandenclosure.If
possible,usepre-existingmountingpointswithinthe
enclosure.
1B
Wall or Under-Counter Configuration.Attachthethree
mountingclipssuppliedwiththePDUtoawallorsimilarflat,
securesurfaceusingtheincludedhardware.Themounting
clipsshouldbeattachedalongaverticalorhorizontalplaneat
equidistantpointswhichroughlycorrespondtothecenterand
endsofthePDU.Ifpossible,usepre-existingmountingpoints.
WARNING: Do not attempt to mount the PDU with the
outlets facing downward; the mounting clips are not
designed to support the weight of the PDU in that manner.
1C
Zero U Rack Configuration (Mounting Buttons). Attachthe
includedmountingbuttonstothePDU.PositionthePDUas
desiredintherackenclosure,alignthebuttonswiththerack
mountingslots,andslidethePDUintoposition.
Note: Regardless of configuration, the user must determine the
fitness of hardware and procedures before mounting. The PDU
and included hardware are designed for common rack and rack
enclosure types and may not be appropriate for all
applications.
2
Attach the PDU to the mounting clips.Usinganassistant,
placearearcornerofthePDUontheinsideedgeofthe
mountingclips,pivotthePDUtowardthealternateinsideedge
andsnapintoplace.
3
Attach the input plug of the PDU to a grounded outlet.
Inserttheplugdirectlyintoagroundedoutletthatdoesnot
shareacircuitwithaheavyelectricalload(suchasanair
conditionerorrefrigerator).
4
Attach equipment to the PDU.Donotexceedtheloadrating
ofthePDU.ThetotalelectricalcurrentusedbythePDUwill
bedisplayedonthedigitalmeterinamperes.
5
Optional Installation (Models PDUV20 & PDUMV20).The
PDUincludesanadapterthatconvertstheL5-20Pinputplug
toa5-20Pinputplug.Theadapterisoptional;thePDUwill
workproperlywithoutconnectingtheadapter.
14-02-334-933043.indd 2 3/26/2014 11:52:08 AM

1 2
7
5
8
4
6
3
3
Features
NEMA 5-15P Input Plug (Models PDUV15 & PDUMV15)
NEMA 5-15R Outlets (Models PDUV15 & PDUMV15)
NEMA L5-20P Input Plug (Models PDUV20 & PDUMV20)
NEMA 5-15/20R Outlets (Models PDUMV20 and PDUV20)
NEMA 5-20P Plug Adapter (Models PDUV20 & PDUMV20): Theadapterconvertstheinput
plugfromNEMAL5-20PtoNEMA5-20P.
Circuit Breaker: IfthecurrentdrawnbytheequipmentconnectedtothePDUexceeds
theMaximumLoadRating,thecircuitbreakerwilltriptopreventpossibledamage.Whenthe
circuitbreakertrips,itsplungerwillpopup.Disconnectexcessequipmentandallowthebreakerto
coolatleastoneminutebeforedepressingtheplungertoresetthebreaker.
Ammeter (Models PDUMV15 and PDUMV20 only): Thetotalelectricalcurrentusedbythe
PDUwillbedisplayedonthedigitalmeterinamperes.
Illuminated Power Switch with Cover (Models PDUMV15 and PDUMV20 only)
1
2
3
4
5
6
7
8
14-02-334-933043.indd 3 3/26/2014 11:52:09 AM
Product specificaties
Merk: | Tripp Lite |
Categorie: | Stekkerdoos |
Model: | PDUMV20 |
Kleur van het product: | Zwart |
Gewicht: | 2440 g |
Breedte: | 38.1 mm |
Diepte: | 41.7 mm |
Hoogte: | 1535.9 mm |
Snoerlengte: | 4.6 m |
Gewicht verpakking: | 3180 g |
Breedte verpakking: | 88.9 mm |
Diepte verpakking: | 1605.3 mm |
Hoogte verpakking: | 61 mm |
Materiaal behuizing: | Aluminium |
LED-indicatoren: | Ja |
Land van herkomst: | China |
Certificering: | UL60950-1 (USA) and CAN/CSA C22.2 No. 60950-1-03 (Canada) |
Duurzaamheidscertificaten: | RoHS |
Temperatuur bij opslag: | -15 - 50 °C |
Hoogte, in bedrijf: | 0 - 3000 m |
Afmetingen (B x D x H): | 44.5 x 31.8 x 1524 mm |
Montage: | Verticaal |
(Buitenste) hoofdverpakking hoogte: | 200.7 mm |
(Buitenste) hoofdverpakking breedte: | 210.8 mm |
(Buitenste) hoofdverpakking brutogewicht: | 19960 g |
(Buitenste) hoofdverpakking lengte: | 1625.6 mm |
Hoeveelheid per (buitenste) hoofdverpakking: | 6 stuk(s) |
Rackcapaciteit: | 0U |
AC-ingangsfrequentie: | 50 - 60 Hz |
GTIN (EAN/UPC)-nummer (buitenste) hoofdverpakking: | 10037332132540 |
Aantal AC uitgangen: | 28 AC-uitgang(en) |
Nominale input voltage: | 100-127 V |
Stopcontacttypes: | NEMA 5–15, NEMA 5–20R |
Stroom (max.): | 20 A |
Input-connectietype: | NEMA 5-20P, NEMA L5-20P |
PDU types: | Gemeten |
Netspanning, in bedrijf: | 100-127 V |
Heb je hulp nodig?
Als je hulp nodig hebt met Tripp Lite PDUMV20 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Stekkerdoos Tripp Lite
30 Mei 2023
29 Mei 2023
26 Mei 2023
25 Mei 2023
23 Mei 2023
21 Mei 2023
18 Mei 2023
4 Mei 2023
4 Mei 2023
3 Mei 2023
Handleiding Stekkerdoos
- Furman
- Geist
- Adam Hall
- Huslog
- Act
- Hama
- Kindermann
- Anton/Bauer
- Steren
- Icy Box
- Ubiquiti Networks
- Qian
- Kopp
- Altronix
- Tecnoware
Nieuwste handleidingen voor Stekkerdoos
10 Maart 2025
9 Maart 2025
9 Maart 2025
26 Februari 2025
20 Februari 2025
20 Februari 2025
20 Februari 2025
14 Januari 2025
29 December 2024
7 December 2024