Basic Rack PDU
Important Safety Instructions 2
Important Warnings 2
Installation 3
Features 4
Warranty & Product Registration 4
Español 5
Français 9
Owner’s Manual
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2014 Tripp Lite. All rights reserved.
PDUH30HV19
(Series Number: AG-00E6)
PDUH32HV19
(Series Number: AG-00E5)
PDUH30HV
(Series Number: AG-00E6)
PDUH32HV
(Series Number: AG-00E5)
14-09-039-9333BC.indb 1 9/29/2014 12:33:52 PM
2
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed
during the installation, operation and storage of this product. Failure to
heed these instructions and warnings will void the product warranty.
Important Warnings
• The PDU provides the convenience of multiple outlets, but DOES NOT provide surge or line noise
protection for connected equipment.
• The PDU is designed for indoor use only, in a controlled environment, away from excess
moisture, temperature extremes, conductive contaminants, dust or direct sunlight.
• Keep indoor ambient temperature between 32°F and 104°F (0°C and 40°C).
• The PDU must be installed by a qualified technician only.
• Do not attempt to mount the PDU to an insecure or unstable surface.
• Install in accordance with National Electrical Code standards. Be sure to use the proper
overcurrent protection for the installation, in accordance with the plug/equipment rating.
• Connect the PDU to an outlet that is in accordance with your local building codes and that is
adequately protected against excess currents, short circuits and earth faults.
• The electrical outlets supplying power to the equipment should be installed near the equipment
and easily accessible.
• Do not connect the PDU to an ungrounded outlet or to extension cords or adapters that
eliminate the connection to ground.
• Be sure to provide a local disconnect device on any models that are permanently installed
without a plug that is easily accessible.
• Never attempt to install electrical equipment during a thunderstorm.
• Individual equipment connected to the PDU should not draw more current than the individual
PDU’s outlet’s rating.
• The total load connected to the PDU must not exceed the maximum load rating for the PDU.
• Do not attempt to modify the PDU, input plugs or power cables.
• Do not drill into or attempt to open any part of the PDU housing. There are no user-serviceable
parts inside.
• Do not attempt to use the PDU if any part of it becomes damaged.
• Use of this equipment in life support applications where failure of this equipment can reasonably
be expected to cause the failure of the life support equipment or to significantly affect its safety
or effectiveness is not recommended. Do not use this equipment in the presence of a
flammable anesthetic mixture with air, oxygen or nitrous oxide.
14-09-039-9333BC.indb 2 9/29/2014 12:33:52 PM
3
Installation
Note: The illustrations may differ somewhat from
your PDU model.
1 The Determine Installation Configuration.
PDU supports four primary installation
configurations: 1U Rack, 0U Rack, Wall and
Under-Counter. Choose a configuration and
follow the installation instructions in the
appropriate section of Step 1 before
proceeding to Step 2.
Note: Regardless of installation configuration,
the user must determine the fitness of
hardware and procedures before mounting.
The PDU and included hardware are designed
for common rack and rack enclosure types
and may not be appropriate for all
applications. Exact mounting configurations
may vary.
1-1 1U Rack Installation. Attach the PDU to the
rack by inserting four user-supplied screws (A)
through the PDU mounting brackets ( ) and B
into the mounting holes of the rack rail as
shown.
1-2 Remove the 0U Rack Installation. Part 1:
screws ( ) attaching the mounting brackets to C
the PDU, change the orientation of the
brackets as shown and reattach the brackets.
Use only the screws supplied by the
manufacturer or their exact equivalent
(#6-32, 1/4” flat head). Attach the Part 2:
PDU vertically by inserting two or more user-
supplied screws ( ) through the PDU mounting A
brackets ( ) and into mounting points in the B
rack or rack enclosure.
1-3 After repeating Part 1 Wall Installation.
above, attach the PDU to a stable mounting
surface by inserting two or more user-supplied
screws ( ) through the PDU mounting brackets A
(B) and into secure mounting points on the
mounting surface.
1-4 After repeating Under-Counter Installation.
Part 1 above, attach the PDU to a stable
mounting surface by inserting four user-
supplied screws ( ) through the PDU mounting A
brackets ( ) and into secure mounting points B
on the mounting surface.
2 Attach the input plug of the PDU to a grounded outlet. Insert the plug directly into a
grounded outlet that does not share a circuit with a heavy electrical load (such as an air
conditioner or refrigerator).
3 Attach equipment to the PDU. Do not exceed the load rating of the PDU. The total electrical
current used by the PDU will be displayed on the digital meter in amperes.
2
1-1
1-2
1-3
1-4
3
A
A
A
C
C
B
B
B
A
A
B
C
Step 1
Step 1
Step 1
14-09-039-9333BC.indb 3 9/29/2014 12:33:54 PM


Product specificaties

Merk: Tripp Lite
Categorie: Stekkerdoos
Model: Basic PDUH30HV
Kleur van het product: Zwart
Gewicht: 3510 g
Breedte: 439.4 mm
Diepte: 95.2 mm
Hoogte: 43.2 mm
Snoerlengte: 3.66 m
Gewicht verpakking: 3850 g
Breedte verpakking: 514.4 mm
Diepte verpakking: 285.8 mm
Hoogte verpakking: 76.2 mm
Soort: Eenfasig
Gebruikershandleiding: Ja
Materiaal behuizing: Metaal
Land van herkomst: China
Afmetingen verpakking (BxDxH): 514.4 x 285.8 x 76.2 mm
Duurzaamheidscertificaten: RoHS
Temperatuur bij opslag: -15 - 50 °C
Spanning: 200 - 240 V
Bedrijfstemperatuur, bereik: 5 - 122 °F
Hoogte, in bedrijf: 0 - 3000 m
Afmetingen (B x D x H): 439 x 95.3 x 43 mm
Montage: Horizontaal/Verticaal
Stekker: NEMA L6-30P
(Buitenste) hoofdverpakking hoogte: 304.8 mm
(Buitenste) hoofdverpakking breedte: 508 mm
(Buitenste) hoofdverpakking brutogewicht: 17990 g
(Buitenste) hoofdverpakking lengte: 533.4 mm
Hoeveelheid per (buitenste) hoofdverpakking: 5 stuk(s)
Rackcapaciteit: 0U/1U
AC-ingangsfrequentie: 50 - 60 Hz
Relatieve vochtigheid in bedrijf (V-V): 5 - 95 procent
GTIN (EAN/UPC)-nummer (buitenste) hoofdverpakking: 10037332183214
Aantal AC uitgangen: 10 AC-uitgang(en)
Nominale input voltage: 200 - 240 V
Stopcontacttypes: C13 stekker
Stroom (max.): 30 A
PDU types: Basis
Spanningsbeveiliging: Ja