Silent Knight FFT-HSC Handleiding


Lees hieronder de đź“– handleiding in het Nederlandse voor Silent Knight FFT-HSC (1 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 42 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/1
P/N 54695 Rev A
ECN 11-0003
FFT-HSC Installation
Instructions
The FFT-HSC Fire Fighter Handset Cabinet is
used to store FFT-FHS handsets.
Compatibility
The FFT-HSC is compatible with the Silent
Knight FFT series Fire Fighters Telephone. For
more information refer to the IFP-FFT
installation manual 54708 or the SK-FFT
installation manual 54711.
Mounting
Mount the FFT-HSC cabinet so it is firmly
secured to the wall surface. When mounting on
concrete, especially when moisture is expected,
attach a piece of 3/4 inch plywood to the
concrete surface and then attach the cabinet to
the plywood.
The cabinet can be surface or flush mount. If you
will flush mount the cabinet, the hole for the
enclosure should be 14.75" W x 25" H x 4" D.
Do NOT flush mount in a wall designated as a
firebreak.
Key Shaped Holes
Bottom Mounting Holes


Product specificaties

Merk: Silent Knight
Categorie: Niet gecategoriseerd
Model: FFT-HSC

Heb je hulp nodig?

Als je hulp nodig hebt met Silent Knight FFT-HSC stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Silent Knight

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd