Bekijk gratis de handleiding van Siemens RDG260KN (3 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 2 mensen en kreeg gemiddeld 5.0 sterren uit 2 reviews. Heb je een vraag over Siemens RDG260KN of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/3
Operating Instructions
en
RDG200KN, RDG204KN
RDG260KN, RDG264KN
RDG2..KN – Room thermostat with KNX communications allowing users to set ideal
temperature, relative humidity and CO level (RDG204KN&RDG264KN). The thermostat offers2
the operating modes Comfort, Economy and Protection.
In addition, it can operate in Auto mode as per a schedule via KNX bus or local.
The fan operates either in Auto mode or at the selected speed in Manual mode.
Main display Operating mode
Operating mode selection*Holiday mode
SchedulerProtection mode
Fan speed selectionEconomy mode
Escape
Comfort mode
Delete schedule
Cooling mode
Confirm parameters
Electric heater active
Number of schedules or slave alarms
Heating mode
Scheduler mode
Outside temperature
Manual changeover
Parameter
Auto mode
Digits for setpoint display
Temporary timer
Time bar for schedule
Fault
Additional user information, such as outside temperature, time of
day from KNX bus, relative humidity, or indoor air quality
Fresh air indication
Condensation in room
(dewpoint sensor active) or
humidity control active
Morning: 12-hour format; Afternoon: 12-hour format
Relative humidity
Degrees Celsius or Fahrenheit
Indoor air quality
CO2 values
Button lock
Value with thermometer: Digits for room temperature display
Automatic fan
Operating mode button * Fan mode button
Rotary knob
Fan speed I
Green leaf Protection hospitality mode or scheduler buttonFan Speed II
IAQ level indicator(Valid only for RDG2..4KN: Available from product
index G or higher versions)
Fan Speed III
* When P002 = 3, the icon is displayed as and the button can be used to switch unit between °C and °F. (scan the above QR
code for the latest version info).
Changing the room temperature
Turn the rotary knob clockwise to increase, or counterclockwise to decrease the current room
temperature setpoint.
Note: The setting range is 5...40 °C; it can be limited by parameters P013 and P016.
(for parameter settings, see Control parameters on page 2).
Adjusting the fan speed
Speed I
Press the right button repeatedly until the desired fan mode is reached.
In Auto mode , the fan speed is automatically selected by the thermostat
depending on setpoint and current room temperature.
In Manual mode, the fan operates independently and runs at the speed set by the
user: speed I / speed II / speed III.
Speed II
Speed III
Changing the operating mode
Comfort mode
Economy mode
Protection modeAuto mode
1. Comfort mode
In Comfort mode, the thermostat maintains the room temperature at the setpoint which can be adjusted
with the rotary knob.
2. Economy mode
In Economy mode, the thermostat maintains the room temperature at a lower or higher setpoint, thus saving
energy and money.
The thermostat can be set to Economy mode either by pressing the operating mode button if enabled
(P002 = 2), or via an external signal (switch or KNX bus command) such as keycard or presence detector.
The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling. They can be adjusted via
parameters P019 and P020 (for parameter settings, see Control parameters on page 2).
3. Protection mode
In Protection mode, the thermostat stops operating. However, if the room temperature drops below 8 °C,
heating is switched on to protect the room against frost.
The thermostat switches to Protection mode when the window contact (local or on KNX) is activated.
The setpoints for Protection mode can be changed by your HVAC installer if desired:
Changes made by installer: Frost protection: _________ C Heating protection: __________C˚˚
4. Auto mode
In Auto mode, the thermostat automatically switches over between Comfort and Economy mode as per the
KNX bus or local schedule (enabled via P005).
If no schedule is available, Comfort replaces Auto.
Important: If setpoints are set to Off, there is no protective heating or cooling function.Risk of frost!
Green leaf indication
The green leaf indication is an energy-efficient setting and indicates the end user settings.
Green leaf: Settings are within the
preset energy-efficient range.
Red leaf: Settings exceed the preset energy-
efficient range.
End users can press the red leaf and return to
the
energy-efficient range.
IAQ level indication
Disable IAQ color indication by selecting P009 = 7 or 9.
(Good air quality)
(Fair air quality)
(Bad air quality)
Reminder to clean filter, display of external faults
FIL **
AL1 **
AL2 **
AL3 **
This message reminds you to clean the filter on your HVAC equipment.
It appears after _______ "fan operating hours" and disappears when the thermostat is
manually set to Protection. These fault messages tell you an external fault has occurred **:
AL1 :AL2 : _______________________ __________________________
AL3 : _______________________
** Needs to be configured by HVAC installer
Scheduler
Set schedule
Press button once and then turn the rotary knob or press button continuously to select programming
mode PROG.
Press button once to enter scheduler mode .
Turn the rotary knob to select the weekday to be set, then press button once.
Turn the rotary knob to view existing schedules, then press button once to select the schedule that need
to be edited.
Comfort mode setting of selected schedule and icons and are displayed, then press button once.
The start time for Comfort flashes and can be changed by turning the rotary knob.
Press button once to confirm the adjusted value and enter the Economy mode setting for the schedule.
Icons and are displayed, then press button once. The start time for Economy flashes and can be
changed by turning the rotary knob.
Press button once to confirm the adjusted value. Then users can view other schedules by turning the
rotary knob and enter other schedule settings (same as edited schedule).
Note: User can press button to delete any schedule or (Esc) to cancel the change. The maximum number of set schedule is