Samsung AM050KXMDEH Handleiding

Samsung Airco AM050KXMDEH

Lees hieronder de ๐Ÿ“– handleiding in het Nederlandse voor Samsung AM050KXMDEH (14 pagina's) in de categorie Airco. Deze handleiding was nuttig voor 30 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/14
5
ENGLISH
CAUTION SIGNS
Do not install the drain pipe directly to the bottom part of the outdoor unit and built a proper drainage so that water drains
out smoothly. If not, pipe may freeze or bursts during winter time and cause damage to the product or water leakage.
๎˜ƒ๎™˜ When the draining work is not done properly, water leak may occur and cause property damage.
Install the power cable and communication cable of the indoor and outdoor unit at least 1.5m away from the electric
appliances and install it at least 2m away from the lightning conductor.
๎˜ƒ๎™˜ Noise may be generated from the electronic devices, depending on the status of the electric wave.
Install the outdoor unit within the angle stated in the table, according to the height of the building.
๎˜ƒ๎™˜ Do not leave the refrigerant container under the hot sunlight. (There is risk of explosion.)
๎˜ƒ๎™˜ You must use the appropriate pipes according to the standard since the pressure of the refrigerant is very high.
๎˜ƒ๎™˜ Make sure that the pipes does not get any weaker by welding it too much.
๎˜ƒ๎™˜ Make sure to install the product away from childrenโ€™sโ€™ reach. (Sharp parts of the heat exchanger is may cause personal
injury and when parts of the product gets damage, it may decrease productโ€™s performance.)
Building
Lightning rod
Protective angle: 25~55ยฐHeight of the building Protection control
20m or less 55หš
40m or less 35หš
60m or less 25หš
Install the indoor unit away from lighting apparatus that uses ballast stabilizer.
๎˜ƒ๎™˜ If you use the wireless remote control, it may not operate normally due to ballast stabilizer.
Do not install the product in following places.
๎˜ƒ๎™˜ Place where outdoor unitโ€™s noise and warm air may disturb neighbors. (It may cause property loss.)
๎˜ƒ๎™˜ Do not leave any obstacles around the inlet and outlet of the product. (It may cause damage or accidents.)
๎˜ƒ๎™˜ The place where there is mineral oil or arsenic acid.
-Those parts may get damaged due to burned resin and cause water leakage or product may fall.
-The e๎˜›ciency of the heat exchanger may reduce or product may break.
๎˜ƒ๎™˜ The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
-The copper pipe or connection pipe may corrode and refrigerant may leak.
๎˜ƒ๎™˜ The place where there is a machine that generates electromagnetic waves.
-The air conditioner may not operate normally due to problems in control system.
๎˜ƒ๎™˜ The place where there is a danger of combustible gas leakage or place where thinner or gasoline is handled.
-(There is risk of ๎˜Ÿre or explosion.)
๎˜ƒ๎™˜ The place with carbon ๎˜Ÿber or ๎˜žammable dust.
๎˜ƒ๎™˜ The place near seashore or hot spring where there is risk of outdoor unit corrosion.
Wear protective equipment (such as safety gloves, goggles, and headgear) during installation and maintenance works.
Installation/repair technicians may be injured if protective equipment is not properly equipped.
8
Selecting installation location
Installation Guide at the seashore
Make sure to follow below guides when installing at the seashore.
Xf Do not install the product in a place where it is directly exposed to sea water and sea breeze.
- Make sure to install the product behind a structure (such as building) that can block see breeze.
- Even when it is inevitable to install the product in seashore, make sure that product is not directly exposed to sea
breeze by installing a protection wall.
Xf Consider that the salinity particles clinging to the external panels should be su๎˜›ciently washed out.
Xf Because the residual water at the bottom of the outdoor unit signi๎˜Ÿcantly promotes corrosion, make sure that
the slope does not disturb drainage.
- Keep the floor level so that rain does not accumulate.
- Be careful not to block the drain hole due to foreign substance.
Xf When product is installed in seashore, periodically clean it with water to remove attached salinity.
Xf Make sure to install the product in a place that provides smooth water drainage. Especially, ensure that the base
part has good drainage.
Xf If the product is damaged during the installation or maintenance, make sure to repair it.
Xf Check the condition of the product periodically.
- Check the installation site every 3 months and perform anti-corrosion treatment such as R-Pro supplied by
SAMSUNG (Code : MOK-220SA) or commercial water repellent grease and wax, etc., based on the product
condition.
- When the product is to be shut down for a long period of time, such as off-peak hours, take appropriate measures
like covering the product.
Xf If the product installed within 500m of seashore, special anti-corrosion treatment is required.
* Please contact your local SAMSUNG representative for further details.
Sea
Sea breeze
Outdoor
unit
Outdoor
unit
Sea
Sea breeze
Outdoor
unit
Sea
Sea breeze
Outdoor
unit
Protection wall
Protection wall should be constructed with a solid material that can
block the sea breeze and the height and width of the wall should be
1.5 times larger than the size of the outdoor unit.(You must secure
more than 700 mm of space between the protection wall and the
outdoor unit for air circulation.)


Product specificaties

Merk: Samsung
Categorie: Airco
Model: AM050KXMDEH

Heb je hulp nodig?

Als je hulp nodig hebt met Samsung AM050KXMDEH stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Airco Samsung

Handleiding Airco

Nieuwste handleidingen voor Airco