Revision: PGBL-RGBL-IOM (05-26) 145085-A
GAS-FIRED AIR HANDLER INSTALLATION, OPERATION,
AND MAINTENANCE
Supersedes: I-PGBL-CRGBL-RPBL (05-14) PN145085R7
DISCONTINUED MODELS PGBL AND RGBL
⚠DANGER ⚠
FIRE OR EXPLOSION HAZARD
•Failure to follow safety warnings exactly could result in serious injury, death, or property
damage.
•Improper installation, adjustment, alteration, service, or maintenance can cause serious
injury, death, or property damage.
•Installation and service must be performed by a qualied installer, service agency, or the
gas supplier.
•Be sure to read and understand the installation, operation, and service instructions in this
manual.
•Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or
any other appliance.
WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any phone in your building.
•Leave the building immediately.
•Immediately call your gas supplier from a phone remote from the building. Follow the gas
supplier’s instructions.
•If you cannot reach your gas supplier, call the re department.
DO NOT DESTROY. PLEASE READ CAREFULLY. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

2PGBL-RGBL-IOM (05-26) 145085-A
WARNING: Improper installation, adjustment, alteration, service,
or maintenance can cause property damage, injury or death.
Read the installation, operation, and maintenance instructions
thoroughly before installing or servicing this equipment.
WARNING: To ensure safety, follow lighting instructions located
on the outlet box cover. See Hazard Levels, above.
Denitions of HAZARD INTENSITY LEVELS used in this Manual
1.DANGER: Failure to comply will result in severe personal injury or
death and/or property damage.
2.WARNING: Failure to comply could result in severe personal injury
or death and/or property damage.
3.CAUTION: Failure to comply could result in minor personal injury
and/or property damage.
WARNING: Gas-red appliances are not designed for use
in hazardous atmospheres containing ammable vapors or
combustible dust, in atmospheres containing chlorinated or
halogenated hydrocarbons, or in applications with airborne
silicone substances. See Hazard Levels, above.
1.1 Hazard Labels and Notices
There are warning labels on the unit and throughout this manual. For your safety, read
the denitions below and comply with all boxes labeled CAUTION, WARNING, and
DANGER during installation, operation, maintenance, and service of this heater.
1.0 General
1.0 General ..............................................................2
1.1 Hazard Labels and Notices.............................2
1.2 General Installation Information ....................3
1.3 Warranty ...........................................................3
1.4 Installation Codes ...........................................3
2.0 Furnace Location .............................................3
2.1 General Requirements and
Recommendations .........................................3
2.2 Combustion Air Requirements ......................4
3.0 Uncrating and Preparation ..............................5
3.1 Uncrating and Inspecting ...............................5
3.2 Preparing for Installation
................................5
4.0 Dimensions and Clearances ...........................6
4.1 Dimensions ......................................................6
4.2 Clearances .....................................................11
5.0 Suspension and Mounting ............................11
5.1 Weights ...........................................................11
5.2 Suspension - Applies to Model PGBL ..........11
5.3 Mounting - Indoor Model PGBL ...................12
5.4 Mounting Outdoor Models RPBL, CRGBL,
RPDBL ...........................................................12
6.0 Mechanical ......................................................17
6.1 Gas Piping and Pressures ............................17
6.2. Venting .........................................................19
6.3 Unit Inlet Air ...................................................25
6.4 Duct Connections ..........................................37
6.5 Blowers, Belts, and Drives ...........................38
7.0 Electrical Supply and Controls .....................40
7.1 General ...........................................................40
7.2 Supply Voltage and Wiring ...........................40
7.3 Thermostat, Other Optional Controls, and
Control Wiring ...............................................42
8.0 Controls ..........................................................43
8.1 Control Locations ..........................................43
8.2 Fan Control ....................................................44
8.3 High Temperature Limits .............................44
8.4 Reverse Flow, Limit Control ........................44
8.5 Combustion Air Proving Switch
..................44
8.6 Optional High Ambient Limit Control
.........44
8.7 Gas Controls ..................................................45
8.8 Pilot and Ignition Systems ...........................50
8.9 Burners, Orices, and Carryover System ...51
8.10 Burner Air Adjustment
................................51
9.0 Check Installation and Start-Up ....................52
9.1 Check the installation prior to start-up: ......52
9.2 Start-Up .........................................................52
9.3 Check installation after Start-up: .................53
10.0 Maintenance and Service ............................54
10.1 Maintenance Schedule................................54
10.2 Maintenance Procedures ............................54
10.3 Troubleshooting ..........................................58
INDEX ....................................................................59
INSTALLATION RECORD .....................................60
Table of Contents

PGBL-RGBL-IOM (05-26) 145085-A 3
1.2 General
Installation
Information
Installation should be done by a qualied agency in accordance with the instructions
in this manual and in compliance with all codes and requirements of authorities having
jurisdiction. The instructions in this manual apply to Reznor
®
Models PGBL, CRGBL,
RPBL, and RPDBL.
WARRANTY: Warranty is void if......
a.Furnaces are used in atmospheres containing ammable vapors or
atmospheres containing chlorinated or halogenated hydrocarbons or any
contaminant (silicone, aluminium oxide, etc.) that adheres to the spark
ignition ame sensing probe.
b.Wiring is not in accordance with the diagram furnished with the heater.
c.Unit is installed without proper clearances to combustible materials.
d.Furnace air throughput is not adjusted within the range specied on the
rating plate.
1.4 Installation
Codes
1.3 Warranty
Refer to the limited warranty form in the "Literature Bag".
The duct furnaces in the Reznor
®
models covered in this manual are design-certied to
ANSI and CSA standards by the Canadian Standards Association.The duct furnaces in
Models PGBL, CRGBL, RPBL and RPDBL are approved for installation in the United
States. The duct furnaces in Models PGBL, RPBL and RPDBL are approved for instal-
lation in Canada. All furnaces are approved for use with either natural gas or propane.
The type of gas for which the furnace is equipped and the correct ring rate are shown
on the rating plate attached to the unit. Electrical characteristics are shown on the unit
rating plate.
These units must be installed in accordance with local building codes. In the absence
of local codes, in the United States, the unit must be installed in accordance with the
National Fuel Gas Code NFPA/ANSI Z223.1 (latest edition). A Canadian installation
must be in accordance with the CSA B149.1 Natural Gas and Propane Installation
Code. These codes are available from CSA Information Services, 1-800-463-6727.
Local authorities having jurisdiction should be consulted before installation is made to
verify local codes and installation procedure requirements.
Special Installations
(Aircraft Hangars/
Garages)
Installations in aircraft hangars should be in accordance with NFPA No. 409 (latest
edition), Standard for Aircraft Hangars; in public garages in accordance with NFPA
No. 88A (latest edition), Standard for Parking Structures; and for repair garages in
accordance with NFPA No. 88B (latest edition), Standard for Repair Garages. In Can-
ada, installations in aircraft hangars, repair garages, and parking garages should be in
accordance with the requirements of the enforcing authorities and in accordance with
CSA B149 codes.
2.0 Furnace
Location
2.1 General Requirements and Recommendations
Location must comply with the clearances listed in Paragraph 4.1.2. Clearances from
the heater and vent to combustible construction or material in storage must conform
with the National Fuel Gas Code ANSI Z223.1a (latest edition) pertaining to gas-burn-
ing devices, and such material must not attain a temperature over 160°F by continued
operation of the heater.
There are a variety of factors, such as system application, building structure, dimen-
sions, and weight, that contribute to selecting the location. If equipped with an outside
air hood, it is recommended that the inlet to the hood not be facing into the prevailing
wind.
Read the installation information in this manual and select a location that complies with
the requirements.
CAUTION: Do not locate an indoor Model PGBL unit where it may
be exposed to water spray, rain, or dripping water.