Panasonic KT7 Handleiding


Lees hieronder de đź“– handleiding in het Nederlandse voor Panasonic KT7 (20 pagina's) in de categorie Temperatuurregelaar. Deze handleiding was nuttig voor 25 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/20
1
Instruction manual Temperature Controller KT7
No.KT71E3 2006.08
To prevent accidents arising from the misuse of this controller, please ensure the operator receives
this manual.
SAFETY PRECAUTIONS
Be sure to read these precautions before using our products.
The safety precautions are classified into categories: “Warning” and “Caution”.
Warning : Procedures which may lead to dangerous conditions and cause death or serious injury, if not
carried out properly.
Caution : Procedures which may lead to dangerous conditions and cause superficial to medium injury
or physical damage or may degrade or damage the product, if not carried out properly.
Warning
• When using this controller on occasions which serious injury would be expected to occur or when damage
is likely to expand or proliferate, make sure to take safety measures such as installing double safety
structures.
• Do not use this controller in s, or it may cause explosion.an environment with flammable gase
Caution
• Fasten the electric wire with the terminal screws securely. Imperfect connection may cause abnormal
heating or fumes.
• Use this controller according to the rating and environmental conditions. Otherwise abnormal heating or
fumes may occur.
• Do not touch the terminals while the power is supplied to the controller, as this may cause electric shock.
• Do not disassemble or modify the controller, as this may cause electric shock or fumes.
Caution
• This instrument should be used according to the specifications described in this manual.
If it is not used according to the specifications, it may malfunction or cause fire.
• Be sure to follow the warnings, cautions and notice. If not, it could cause serious injury or accidents.
• The contents of this instruction manual are subject to change without notice.
• This instrument is designed to be installed in a control panel. If not, measures must be taken to ensure
that the operator cannot touch power terminals or other high voltage sections.
• Be sure to turn the power supplied to the instrument OFF before cleaning this instrument.
• Use a soft, dry cloth when cleaning the instrument.
(Alcohol based substances may tarnish or deface the unit.)
• As the display section is vulnerable, do not strike or scratch it with a hard object.
• Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
• Matsushita Electric Works, Ltd. is not liable for any damage or secondary damage(s) incurred as a result
of using this product, including any indirect damage.
1. Model number
1.1 Explanation of model number
A K T 7
1 1 0
(1) (2) (3) (4) (5) (6)
(1) Supply voltage ------------ 1: 100 to 240V AC, 2: 24V AC/DC
(2) Input type ------------------- 1: Multi-input (Thermocouple, RTD, DC current and DC voltage
can be selected by keypad operation)
(3) Control output (OUT) ---- 1: Relay contact, 2: Non-contact voltage, 3: DC current
(4) Alarm output --------------- 1: Alarm output (1 point)
(The alarm type and Energized /Deenergized can be selected
by keypad operation)
(5) Heater burnout alarm ---- 0: Not available, 1: Available (5A), 2: Available (10A), 3: Available
(20A), 4: Available (50A)
(Heater burnout alarm is not available for the DC current output)
(6) Serial communication --- 1: Applied (The number is indicated only when Serial communication
is added.)
2
1.2 How to read the rated label
The rated label is attached to the case.
When Heater burnout alarm is added, CT rated current is written in the bracket ( ).
2. Name and functions of the sections
(1) EVT indicator
The red LED lights when Event output [Alarm, Loop break alarm
or Heater burnout alarm (Option)] is ON.
(2) OUT indicator
When OUT (control output) is ON, the green LED lights.
For DC current output type, this flashes corresponding to the output
manipulated variable.
(3) T/R indicator
The yellow LED flashes during serial communication.
(4) AT indicator
The yellow LED flashes while PID auto-tuning is being performed.
(5) PV display
Indicates the PV (input value) with a Red LED.
(6) SV display
Indicates the SV (main set value) with a Green LED.
(7) Increase key
Increases the numeric value.
(8) Decrease key
Decreases the numeric value.
(9) Mode key
Selects the setting mode or registers the set value.
(By pressing the Mode key, the set value can be registered)
(10) Sub mode key
Enters Auxiliary function setting mode 2 in combination with the Mode key. (Fig. 2-1)
Notice
When setting the specifications and functions of this controller, connect terminals 1 and 2 for power
source rst, then set them referring to “5. Setup” and “6. Operation flowchart” before performing
“3. Mounting to the control panel” and“4. Wiring”.
3. Mounting to the control panel
3.1 Site selection
This instrument is intended to be used under the following environmental conditions
(IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• Few mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 )
that does not change rapidly
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current is flowing
• No water, oil or chemicals or where the vapors of these substances can come into direct
contact with the controller
(1)
(2)
(5)
(3)
(6)
(7)
(8)
(9)
(10)
(4)
AKT71111001
No.
Relay contact output
Alarm output (1 point)
Heater burnout alarm is not added
(1)
(2)
(e.g.)
Supply voltage: 100 to 240V AC
Multi-input
(1) Model number, supply voltage, input type, output type, etc. are entered.
(2) Lot number is entered.
3
(
A
)
(
B
)
3.2 External dimensions (Unit: mm)
(Fig. 3.2-1)
3.3 CT (Current transformer) external dimensions (Unit: mm)
AKT4815 (for 20A) AKT4816 (for 50A)
(Fig. 3.3-1)
3.4 Mounting to DIN rail
Caution
Mount the DIN rail horizontally.
When DIN rail is mounted vertically, be sure to use commercially available fastening plates at both ends of
KT7 series. Mount the KT7 series to the DIN rail so that the KT7 series cannot move.
However, if the DIN rail is mounted horizontally in a position susceptible to vibration or shock, the
fastening plates must be used as well.
Recommended fastening plate
Matsushita Electric Works, Ltd. Fastening plate ATA4806
(1) Hook (A) of KT7 series on the upper side of
the DIN rail. (Fig. 3.4-1)
(2) Making (B) part of the KT7 series as a support,
fit the lower part of the KT7 series to the DIN rail.
KT7 series will be completely fixed to DIN rail with
a “Click” sound. (Fig. 3.4-1)
(Fig. 3.4-1)
4. Wiring
Warning
Turn the power supplied to the instrument OFF before wiring or checking it.
Working or touching the terminal with the power switched ON may result in severe injury or
death due to Electric Shock.
4100
97
22.5
75


Product specificaties

Merk: Panasonic
Categorie: Temperatuurregelaar
Model: KT7

Heb je hulp nodig?

Als je hulp nodig hebt met Panasonic KT7 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden