Air Conditioners
SLZ-KF25, KF35, KF50, KF60VA3
INSTALLATION MANUAL
For safe and correct use, please read this manual and the outdoor unit installation manual thoroughly before install-
ing the air-conditioner unit.
English
FOR INSTALLER
2
Contents
1. Safety precautions 2 .........................................................................................
2. Selecting the installation location 2 ...................................................................
3. Installation diagram 3 ........................................................................................
4. Installing the indoor unit 3 .................................................................................
5. Refrigerant piping work 5 ..................................................................................
6. Drainage piping work 7 .....................................................................................
7. Electrical work 8 ................................................................................................
8. Test run 15 ........................................................................................................
9. System control 17 .............................................................................................
10. Installing the grille 17 ........................................................................................
11. Easy maintenance function 20 ..........................................................................
1. Safety precautions
• Besuretoread“Safetyprecautions”beforeinstallingtheairconditioner.
• Besuretoobservethecautionsspeciedhereastheyincludeimportant
itemsrelatedtosafety.
• Theindicationsandmeaningsareasfollows.
Warning:
Couldleadtodeath,seriousinjury,etc.
Caution:
Couldleadtoseriousinjuryinparticularenvironmentswhenoperatedincor-
rectly.
• Afterreadingthismanual,besuretokeepittogetherwiththeinstruction
manualinahandyplaceonthecustomerssite.
: Indicates a part which must be grounded.
Warning:
Carefullyreadthelabelsaffixedtothemainunit.
Installtheindoorunitatleast2.5mabovefloororgradelevel.
Forappliancesnotaccessibletothegeneralpublic.
Warning:
• Donotinstallitbyyourself(customer).
 Incompleteinstallationcouldcauseinjuryduetore,electricshock,theunit
fallingorleakageofwater.Consultthedealerfromwhomyoupurchasedthe
unitorspecialinstaller.
• Installtheunitsecurelyinaplacewhichcanbeartheweightoftheunit.
When installed in an insufcient strong place, the unit could fall causing
injured.
• Usethespeciedwirestoconnecttheindoorandoutdoorunitssecurelyand
attachthewiresrmlytotheterminalboardconnectingsectionssothestress
ofthewiresisnotappliedtothesections.
 Incompleteconnectingandxingcouldcausere.
• Donotuseintermediateconnectionofthepowercordortheextensioncord
anddonotconnectmanydevicestooneACoutlet.
 Itcouldcauseareoranelectricshockduetodefectivecontact,defective
insulation,exceedingthepermissiblecurrent,etc.
• Checkthattherefrigerantgasdoesnotleakafterinstallationhascompleted.
• Performtheinstallationsecurelyreferringtotheinstallationmanual.
Incomplete installation could cause a personal injury due to re, electric
shock,theunitfallingorleakageofwater.
• Performelectricalworkaccordingtotheinstallationmanualandbesureto
useanexclusivecircuit.
 Ifthecapacityofthepowercircuitisinsufcientorthereisincompleteelectri-
calwork,itcouldresultinareoranelectricshock.
• Theusershouldneverattempttorepairtheunitortransferittoanotherloca-
tion.
• Theapplianceshallbeinstalledinaccordancewithnationalwiringregula-
tions.
• Ifthesupplycordisdamaged,itmustbereplacedbythemanufacturer,its
serviceagentorsimilarlyqualiedpersonsinordertoavoidahazard.
• Attachtheelectricalpartcovertotheindoorunitandtheservicepaneltothe
outdoorunitsecurely.
 Iftheelectricalpartcoverintheindoorunitand/ortheservicepanelinthe
outdoorunitarenotattachedsecurely,itcouldresultinareoranelectric
shockduetodust,water,etc.
• Besuretousethepartprovidedorspeciedpartsfortheinstallationwork.
 Theuseofdefectivepartscouldcauseaninjuryorleakageofwaterduetoa
re,anelectricshock,theunitfalling,etc.
• Ventilatetheroomifrefrigerantleaksduringoperation.
If the refrigerant comes in contact with a ame, poisonous gases will be
released.
• Wheninstallingorrelocating,orservicingtheairconditioner,useonlythe
speciedrefrigerant(R410A)tochargetherefrigerantlines.Donotmixitwith
anyotherrefrigerantanddonotallowairtoremaininthelines.
 Ifairismixedwiththerefrigerant,thenitcanbethecauseofabnormalhigh
pressure in the refrigerant line,and may result in an explosion and other
hazards.
 Theuseofanyrefrigerantotherthanthatspeciedforthesystemwillcause
mechanical failure or system malfunction or unit breakdown. In the worst
case,thiscouldleadtoaseriousimpedimenttosecuringproductsafety.
Caution:
• Performgrounding.
 Donotconnectthegroundwiretoagaspipe,waterpipearresterortelephone
groundwire.Defectivegroundingcouldcauseanelectricshock.
• Donotinstalltheunitinaplacewhereaninammablegasleaks.
 Ifgasleaksandaccumulatesintheareasurroundingtheunit,itcouldcause
anexplosion.
• Installagroundleakagebreakerdependingontheinstallationplace(where
itishumid).
If a ground leakage breaker is not installed, it could cause an electric
shock.
• Perform the drainage/piping work securely according to the installation
manual.
 Ifthereisadefectinthedrainage/pipingwork,watercoulddropfromtheunit
andhouseholdgoodscouldbewetanddamaged.
• Fastenaarenutwithatorquewrenchasspeciedinthismanual.
 Whenfastenedtootight,aarenutmaybrokenafteralongperiodandcause
aleakageofrefrigerant.
• Iftheunitisrunforlonghourswhentheairabovetheceilingisathightem-
perature/highhumidity(dewpointabove26ºC),dewcondensationmaybe
producedintheindoorunitortheceilingmaterials.Whenoperatingtheunits
inthiscondition,addinsulationmaterial(10-20mm)totheentiresurfaceof
theunitandceilingmaterialstoavoiddewcondensation.
2. Selectingtheinstallationlocation
2.1. Indoorunit
• Whereairowisnotblocked.
• Wherecoolairspreadsovertheentireroom.
• Whereitisnotexposedtodirectsunshine.
• Atadistance1mormoreawayfromyourTVandradio(topreventpicturefrom
being distorted or noise from being generated).
• Inaplaceasfarawayaspossiblefromuorescentandincandescentlights(sothe
infrared remote control can operate the air conditioner normally).
• Wheretheairltercanberemovedandreplacedeasily.
Warning:
Mounttheindoorunitintoaceilingstrongenoughtowithstandtheweightof
theunit.
2.2.
Wirelessremotecontrollermounting(ForSLP-2FAL*)
• Placeofmounting
• Whereitiseasytooperateandeasilyvisible.
• Wherechildrencannottouch.
• Mounting
 Selectapositionabout1.2mabovetheoor,checkthatsignalsfromtheremote
controlleraresurelyreceivedbytheindoorunitfromthatposition(‘beep’or‘beep-
beep’receivingtonesounds).Afterthat,attachremotecontrollerholdertoapillar
or wall and set the wireless remote controller.
In rooms where inverter type uorescent lamps are used, the signal from the
wirelessremotecontrollermaynotbereceived.
Note:
Thephrase“Wiredremotecontroller”inthisinstallationmanualrefersonlytothePAR-33MAA.Ifyouneedanyinformationfortheotherremotecontroller,
pleaserefertoeithertheinstallationmanualorinitialsettingmanualwhichareincludedintheseboxes.
3
(576) C
(576) C
J
625 D
408
88 525 B
570 A
150
313
576 - 610 C
408
576 - 610 C
625 D
I
570 A
525 B
481
208
245
127
18952
50 - 92
10
*1
37 +5
0
K
FEG
3. Installationdiagram
3.1. Indoorunit(Fig.3-1)
A Ceiling
B Grille
C Obstacle
D Min.1000mm
E Min.500mm(Entireperiphery)
If setting the maintenance space for E,besuretoleaveisaminimumof700mm.
Warning:
Mounttheindoorunitonaceilingstrongenoughtowithstandtheweightof
theunit.
3.2. Outdoorunit
Refer to the outdoor unit installation manual.
(mm)
Fig.3-1
Fig.4-1
4. Installingtheindoorunit
4.2. Ceilingopeningsandsuspensionboltinstallation
locations(Fig.4-2)
Caution:
Installtheindoorunitatleast2.5maboveoororgradelevel.
Forappliancesnotaccessibletothegeneralpublic.
• Usingtheinstallationtemplateandthegauge(suppliedasanaccessorywiththe
grille),makeanopeningintheceilingsothatthemainunitcanbeinstalledasshown
inthediagram.(Themethodforusingthetemplateandthegaugeareshown.)
* Before using, check the dimensionsof template and gauge, because they
changeduetouctuationsoftemperatureandhumidity.
* The dimensions of ceiling opening can be regulated within the range shown in
followingdiagram;socenterthemainunitagainsttheopeningofceiling,en-
suringthattherespectiveoppositesidesonallsidesoftheclearancebetween
them becomes identical.
• UseM10(3/8")suspensionbolts.
*Suspensionboltsaretobeprocuredattheeld.
• Installsecurely, ensuringthatthereisno clearancebetween theceiling panel&
grille,andbetweenthemainunit&grille.
A Outer side of main unit
B Bolt pitch
C Ceiling opening
D Outer side of Grille
E Grille
F Ceiling
G Min.500mm(Entireperiphery)
If setting the maintenance space for G,be
suretoleaveisaminimumof700mm.
H Maintenancespace
I Fresh air intake
J Angle
K Electriccomponentbox
* Leavethemaintenancespaceattheelectriccomponentboxend.
*1When installing inan existingceiling unitlocation or applyingadditional heatinsulation,
ensure a minimum space of 25 mm.
Fig.4-2
(mm)
24510
625
625
C
D
E
A
B
1 2
34
5 6
4.1. Checktheindoorunitaccessories(Fig.4-1)
The indoor unit should be supplied with the following accessories.
Accessoryname Q’ty
1Installation template 1
2Washers(withinsulation)
Washers(withoutinsulation)
4
4
3
Pipecover(forrefrigerantpipingjoint)
smalldiameter(liquid)
largediameter(gas)
1
1
4
Band(large)
Band(middle)
Band(small)
6
2
2
5Drain socket 1
6Insulation 1
7.5-24.57.5-24.5
Min.450H
Floor
7.5-24.57.5-24.5
Min.5
Min.2500
Min.450H


Product specificaties

Merk: Mitsubishi
Categorie: Airco
Model: SLZ-KF25VAD

Heb je hulp nodig?

Als je hulp nodig hebt met Mitsubishi SLZ-KF25VAD stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Airco Mitsubishi