Bekijk gratis de handleiding van Mitsubishi MXZ-3HA50VF (72 pagina’s), behorend tot de categorie Airco. Deze gids werd als nuttig beoordeeld door 100 mensen en kreeg gemiddeld 4.4 sterren uit 2 reviews. Heb je een vraag over Mitsubishi MXZ-3HA50VF of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/72

Models
MXZ-2HA40VF-E1 , ET1
MXZ-2HA50VF-E1 , ET1
MXZ-3HA50VF-E1 , ET1
HFC
utilized
R32
SERVICE MANUAL
No. OBH828
OUTDOOR UNIT
PARTS CATALOG (OBB828)
Indoor unit service manual
MSZ-HR•VF Series (OBH822)
CONTENTS
1. TECHNICAL CHANGES ···································3
2. SAFETY PRECAUTION ····································3
3. PART NAMES AND FUNCTIONS ···················13
4. SPECIFICATION ··············································14
5. NOISE CRITERIA CURVES ····························17
6. OUTLINES AND DIMENSIONS ······················ 18
7. WIRING DIAGRAM ··········································20
8. REFRIGERANT SYSTEM DIAGRAM ·············24
9. PERFORMANCE CURVES ·····························27
10. ACTUATOR CONTROL ···································36
11. SERVICE FUNCTIONS ····································37
12. TROUBLESHOOTING ·····································41
13. DISASSEMBLY INSTRUCTIONS ····················66
MXZ-2HA40VF
MXZ-2HA50VF
Product specificaties
| Merk: | Mitsubishi |
| Categorie: | Airco |
| Model: | MXZ-3HA50VF |
Foutcodes Mitsubishi MXZ-3HA50VF
Foutcodes uit de officiële handleiding, met betekenis en oplossing.
| Code | Betekenis | Oplossing |
|---|---|---|
| 10-time blink | Low discharge temperature protection - The frequency of the compressor is kept 80 Hz or more and the discharge temperature is kept under 39°C for more than 20 minutes. | Check refrigerant circuit and refrigerant amount. Refer to 12-6 'Check of LEV'. |
| 11-time blink | Communication error between P.C. boards, Current sensor, Zero cross detecting circuit, Converter, or Bus-bar voltage - Communication error occurs between the outdoor control P.C. board and outdoor power P.C. board for more than 10 seconds. | Check the connecting wire between outdoor control P.C. board and outdoor power P.C. board. Check the voltage of power supply. Replace the outdoor power P.C. board if necessary. |
| 14-time blink | Stop valve - The current of compressor is power module is out of order. | Check the stop valve. Check the refrigerant circuit and the refrigerant amount. |
| 17-time blink | Outdoor refrigerant system abnormality - A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor. | Check for a gas leak in a connecting piping etc. Check the stop valve. Refer to 12-6 'Check of outdoor refrigerant circuit'. |
| 2-time blink | Outdoor power system - Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started, or converter protection cut-out or bus-bar voltage protection cut-out operates 3 consecutive times within 3 minutes after startup. | Check the connection of the compressor connecting wire. Refer to 12-6 'How to check inverter/compressor'. Check the stop valve. |
| 3-time blink | Discharge temperature thermistor, Defrost thermistor, Ambient temperature thermistor, Fin temperature thermistor, or P.C. board temperature thermistor - A thermistor shorts or opens during compressor running. | Refer to 12-6 'Check of outdoor thermistors'. Replace the outdoor control P.C. board if P.C. board temperature thermistor is faulty. |
| 4-time blink | Overcurrent - 21 A current flows into power module. | Reconnect compressor connector. Refer to 12-6 'How to check inverter/compressor'. Check the stop valve. |
| 5-time blink | Discharge temperature - The discharge temperature exceeds 115°C during operation. | Check refrigerant circuit and refrigerant amount. Refer to 12-6 'Check of LEV'. |
| 6-time blink | High pressure - The outdoor heat exchanger temperature exceeds 70°C during cooling or the indoor gas pipe temperature exceeds 70°C during heating. | Check refrigerant circuit and refrigerant amount. Check the stop valve. |
| 7-time blink | Fin temperature or P.C. board temperature - The fin temperature exceeds 88°C during operation or the P.C. board temperature exceeds 67°C during operation. | Check around outdoor unit. Check outdoor unit air passage. Refer to 12-6 'Check of outdoor fan motor'. |
| 8-time blink | Outdoor fan motor - A failure occurs 3 consecutive times within 30 seconds after the fan gets started. | Refer to 12-6 'Check of outdoor fan motor'. |
| 9-time blink | Outdoor control system - Nonvolatile memory data cannot be read properly. | Replace the outdoor control P.C. board. |
Heb je hulp nodig?
Als je hulp nodig hebt met Mitsubishi MXZ-3HA50VF stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Airco Mitsubishi
29 Juli 2026
5 Juni 2026
2 Juni 2026
5 Mei 2026
28 April 2026
28 April 2026
13 Maart 2026
12 Maart 2026
12 Maart 2026
11 Maart 2026
Handleiding Airco
Nieuwste handleidingen voor Airco
26 Augustus 2026
26 Augustus 2026
25 Augustus 2026
25 Augustus 2026
25 Augustus 2026
24 Augustus 2026
24 Augustus 2026
24 Augustus 2026
24 Augustus 2026
21 Augustus 2026