Bekijk gratis de handleiding van Kidde SLED177i (13 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 161 mensen en kreeg gemiddeld 4.9 sterren uit 81 reviews. Heb je een vraag over Kidde SLED177i of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/13

ATTENTION! The model SLED177i strobe light is designed to notify hearing impaired
individuals of impending danger. The strobe light has no detection means and MUST be
used in conjunction with operating and interconnected Smoke, Heat, or Carbon
Monoxide Alarms.
The model SLED177i AC wire-in Strobe light can be directly interconnected with Kidde
Safety 3-wire Smoke, Heat and CO alarms. It will produce an intermittent strobe flash
pattern (approximately 4 flashes, followed by approximately 5 seconds off) when trig-
gered by a Carbon Monoxide alarm and a flash every second when triggered by a
smoke or heat alarm.
Thank you for purchasing this strobe light. It is an important part of your family’s home
safety plan. You can trust KIDDE Safety to provide the highest quality safety products.
We know you expect nothing less when the lives of your family are at stake.
For model: SLED177i
1102-7201-00
Strobe
Light
For your convenience, write down the following information. If you call
our Consumer Hotline, these are the first questions you will be asked.
Strobe Light Model Number
(located on back of alarm):
Date Code (located on back of device):
Date of Purchase:
Where Purchased:
SLED177i
Strobe Light User Guide

IMPORTANT! READ ALL INSTRUCTIONS BEFORE INSTALLATION AND SAVE
THIS USER GUIDE FOR FUTURE REFERENCE
WARNING! THIS VISUAL SIGNALING DEVICE HAS NO DETECTION
MEANS. IT MUST BE USED IN CONJUNCTION WITH OPERATING AND
INTERCONNECTED ALARMS.
WARNING! DO NOT TRY TO REPAIR THIS STROBE LIGHT YOURSELF
REFER TO THE INSTRUCTIONS IN SECTION 11 FOR SERVICE.
WARNING! DISCONNECTING OR LOSS OF AC POWER WILL RENDER
THIS SIGNALING DEVICE INOPERATIVE.
WARNING! THIS STROBE LIGHT IS EXTREMELY BRIGHT. DO NOT LOOK
DIRECTLY AT THE LIGHT WHEN THE LIGHT IS FLASHING..
CONTENTS OF THIS USER GUIDE
1 -- SPECIFICATIONS
2 -- APPLICATIONS
3 -- RECOMMENDED APPLICATIONS OF STROBE LIGHTS
4 -- LOCATIONS TO AVOID
5 -- INSTALLATION INSTRUCTIONS
6 -- OPERATION AND TESTING
7 -- MAINTENANCE
8 -- LIMITATIONS OF SIGNALING DEVICES FOR THE HEARING IMPAIRED
9 -- GOOD SAFETY HABITS
10 -- NFPA PROTECTION STANDARD 72
11 -- SERVICE AND WARRANTY
!
!
!
!

The following diagram shows that the light intensity gradually decreases as the
viewing angle is increased. Use this information to determine the best location
for the strobe light.
2. APPLICATIONS
PRIMARY DIRECT AND INDIRECT VISIBLE SIGNAL
Locate the strobe light on the ceiling in the center of the room or on
the wall a minimum of 80"(2 m) above the floor.
For rooms larger than 250 sq. ft. (14 ft. by 16 ft. - 4.27m by 4.88 m) the
notification device should be located within 16 feet of the pillow when located in a
sleeping area.
SUPPLEMENTARY VISIBLE SIGNAL
The strobe must be located more than 30 inches above the floor.
3. RECOMMENDED LOCATIONS OF VISUAL SIGNALING DEVICES
• Locate the first strobe light in the bedroom in which the hearing impaired
individual sleeps. If the bedroom door is kept closed at night, an
interconnecting smoke detector must also be installed in that bedroom.
• Locate additional strobe lights in any lived-in room where a hearing impaired
individual would need to be notified of an alarm condition.
4. LOCATIONS TO AVOID
• In direct sunlight or high ambient light areas; the bright light may reduce one’s
ability to notice the strobe light.
•
In areas where the temperature may fall below 0°C (32°F) or rise above 49°C (120°F).
• In areas with high humidity.
• Do not use outdoors (This device is not listed for outdoor use).
WALL
CEILING
25 90
25 85
30 80
30 75
35 70
35 65
40 60
45 55
55 50
75 30-45
90 5-25
100 0
(LIGHT INTENSITY) (IN DEGREES)
PERCENT ANGLE
90°
90°
90° 90°
0°
0°
45°
45°
45° 45°
SOURCE
LIGHT
SOURCE
LIGHT
WALL
CEILING
25 90
25 85
30 80
30 75
35 70
35 65
40 60
45 55
55 50
75 30-45
90 5-25
100 0
(LIGHT INTENSITY) (IN DEGREES)
PERCENT ANGLE
90°
90°
90° 90°
0°
0°
45°
45°
45° 45°
SOURCE
LIGHT
SOURCE
LIGHT
Product specificaties
Merk: | Kidde |
Categorie: | Niet gecategoriseerd |
Model: | SLED177i |
Heb je hulp nodig?
Als je hulp nodig hebt met Kidde SLED177i stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Kidde
2 December 2024
2 December 2024
24 September 2024
18 September 2024
18 September 2024
17 Juni 2023
11 Juni 2023
10 Juni 2023
10 Juni 2023
27 Mei 2023
Handleiding Niet gecategoriseerd
- Swann
- AudioThing
- Mitsai
- Steinberg
- Point Source Audio
- Muse
- Pit Boss
- Flavel
- Hario
- Louis Tellier
- Weihrauch Sport
- Primus
- OpenVox
- Zylight
- Avocent
Nieuwste handleidingen voor Niet gecategoriseerd
18 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025