Kidde P4010ACLEDS-2 Handleiding

Kidde Rookmelder P4010ACLEDS-2

Lees hieronder de 📖 handleiding in het Nederlandse voor Kidde P4010ACLEDS-2 (8 pagina's) in de categorie Rookmelder. Deze handleiding was nuttig voor 22 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/8
INTELLIGENT SMOKE
Smoke Alarm User Guide
Hardwire Interconnect Photoelectric Smoke
with LED Strobe and Voice
Model P4010ACLEDS-2
120V HARDWIRE
INTERCONNEC T
10YEAR BATTERY BACKUP
VOICE ALARM
LED STROBE
AMBIENT LIGHT SENSOR
SMOKE ALARM
AMBIENT LIGHT SENSOR
Alarm samples the ambient light conditions of its location
and, if possible, determines a Night / Day cycle to delay chirps
during the night until the next Day cycle begins.
P/N: 1319-7201-00 Rev A
8
5. Introduction, Product Features and Specifications
Introduction
This alarm detects products of combustion using photoelectric technology .
Ten (10) years after the unit was installed, this unit will automatically alert you that it is time to replace the unit. This is
called “End of Unit Life” mode. See Troubleshooting Guide. To help identify the date to replace the unit, a label has been
affixed to the side of the alarm. Write the “Install date” in the space provided, and then write in the “Replace by” date
(10 years from initial power up) in permanent marker on the label prior to installing the unit. NOTE: AC power must be
connected to obtain the full 10 year battery and unit life.
Product Features and Specifications:
Temperature: Operating Range: 40°F (4.4°C) to 100°F (37.8°C)
Humidity: Operating range: up to 95% RH non-condensing
Audible Alarm: 85+ dB at 10’ 3.0 to 3.5 KHz pulsing alarm, with voice message “Fire!
NOTE: This is not a CO alarm, but it will receive and transmit a CO alarm signal (with voice message
Warning! Carbon Monoxide”) from an interconnected CO or combination smoke/CO alarm.
Smoke Sensor: Photoelectric
Voice message system
Smoke Alarm SMART Hush® Control
Ambient Light Sensing
LED Strobe
Powered by 120VAC (60 Hz, 687 mA max) wire-in connector with sealed lithium battery backup.
Hardwire interconnectable to other compatible alarms.
One large, user- friendly button. (Strobe dome is the button).
Applications: Primary Direct or Indirect and Supplementary
Light Output: 177 Candela minimum (on axis measurement)
9
Permanently Disable
Alarm / Discharge
Battery
AC Connector
Product Features and Specifications:
Test / Hush
Button (dome)
Red Alarm
Light
Green Operate
Light
Alarm Sounder
CEILING
90° 90°
45° 45°
SOU CER
LIGHT
CEILING
90° 90°
45° 45°
SOU CER
LIGHT
25 90
25 85
30 80
30 75
35 70
35 65
40 60
45 55
55 50
75 30-45
90 5-25
100 0
( I (LIGHT N STEN ITY) IN DEGREES)
PERCENT ANGLE
25 90
25 85
30 80
30 75
35 70
35 65
40 60
45 55
55 50
75 30-45
90 5-25
100 0
( I (LIGHT N STEN ITY) IN DEGREES)
PERCENT ANGLE
90° 60 55 50 45 40 35 30
0
ZERO AXIS
WALL
FLOOR
5
10
15
20
25
The following diagrams show that the light intensity gradually decreases as the viewing angle is increased. Use this
information to determine the best location for the strobe light.
Front Back


Product specificaties

Merk: Kidde
Categorie: Rookmelder
Model: P4010ACLEDS-2

Heb je hulp nodig?

Als je hulp nodig hebt met Kidde P4010ACLEDS-2 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Rookmelder Kidde

Handleiding Rookmelder

Nieuwste handleidingen voor Rookmelder