Kidde HD135 Handleiding


Lees hieronder de đź“– handleiding in het Nederlandse voor Kidde HD135 (16 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 106 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/16
AC Wire-in Single and/or Multiple Station (up to 24 Devices) Heat Alarm
with 9 Volt Battery Back Up, 135ÂşF fixed temperature.
Thank you for purchasing this heat alarm. It is an important part of your family’s
home safety plan. You can trust this product to provide the highest quality safe-
ty protection. We know you expect nothing less when the lives of your family
are at stake. Kidde alarms and accessories CAN ONLY BE interconnected with
other Kidde alarms and accessories as well as specified brands and models of
interconnect compatible alarms. Connection of Kidde products to a non-speci-
fied manufacturer’s interconnect system, or connection with non-specified
equipment from another manufacturer into an existing Kidde system could result
in nuisance alarming, failure to alarm, or damage to one or all of the devices in
the interconnect system. Refer to the User’s Guide supplied with each Kidde
product for interconnect compatible models, brands, and devices. Refer to the
wiring instructions in section 3 for NFPA initiating device limits
For model: HD135F
820-0917-EN Rev. D
1000-7211-01
HD135F
For your convenience, write down the following information. If you call
our Consumer Hotline, these are the first questions you will be asked.
Heat Alarm Model Number
(located on back of alarm):
Date Code (located on back of alarm): The
National Fire Protection Association (NFPA)
and the manufacturer recommend replacing
this alarm ten years from the date code.
Date of Purchase:
Where Purchased:
Heat Alarm User’s Guide
WARNING! BATTERY DOOR WILL NOT CLOSE UNLESS A BATTERY IS PRES-
ENT. REMOVAL OF THE HEAT ALARM BATTERY AND DISCONNECTING OR
LOSS OF AC POWER WILL RENDER THE HEAT ALARM INOPERATIVE.
ELECTRICAL RATING: 120 VAC, 60HZ, 80mA maximum per alarm (maximum
80mA for originating unit with 24 devices interconnected).
IMPORTANT! READ ALL INSTRUCTIONS BEFORE INSTALLATION AND KEEP
THIS MANUAL NEAR THE ALARM FOR FUTURE REFERENCE.
WARNING! THIS HEAT ALARM IS NOT DESIGNED TO PROTECT LIFE SAFE-
TY AGAINST FIRE AND SMOKE.
SEE LIMITATIONS OF ALARMS IN SECTION 8 FOR DETAILS.
CONTENTS OF THIS MANUAL
1 SPECIFICATIONS
2 RECOMMENDED LOCATIONS OF ALARMS
3 LOCATIONS TO AVOID
4 INSTALLATION INSTRUCTIONS
5 OPERATION AND TESTING
6 FALSE ALARMS
7 MAINTENANCE
8 LIMITATIONS OF HEAT ALARMS
9 GOOD SAFETY HABITS
10 NFPA PROTECTION STANDARD 72
11 SERVICE AND WARRANTY
Do not try to repair this heat alarm yourself. Refer to the instructions in
Section 11 for service.
1. SPECIFICATIONS
Model Number . . . . . . . . . . . . . . . . . . . . . . . . . .HD135ËšF
AC 120 VAC, 60HZ, 80 mA max, 9 V battery backup, Multiple station (up to
24), compatible with Kidde/Lifesaver smoke alarms (see section 3 for a complete
list of compatible devices).
U.L. Temperature rating . . . . . . . . . . . . . . . . . . .135ÂşF Fixed temperature only
U.L. Maximum ambient temperature at ceiling . .100ÂşF
U.L. Recommended coverage . . . . . . . . . . . . . . .2500 Square Feet (Note "A")
U.L. recommended spacing . . . . . . . . . . . . . . . . .50 Feet
Maximum distance from wall . . . . . . . . . . . . . . .25 Feet (Note"B")
Note A: Maximum coverage established by U.L. is based on providing equal
response time as sprinkler devices spaced at 10-Ft intervals (100 Sq/Ft) on a
smooth ceiling approximately 15 feet high. Higher ceilings may adversely affect
response time and earlier response time may be obtained by reducing the spac-
ing between alarms.
Note B: Maximum distance is from any wall or ceiling projection extending
down more than 12 inches.
2. RECOMMENDED LOCATION OF ALARMS
• The most favorable mounting location
for a heat alarm is on the ceiling in the
center of the room. At this location the
alarm is closest to all areas of the room
(see figure 3).
EXCEPTION: When the mounting surface
might become considerably warmer or
cooler than the room, such as a poorly
insulated ceiling, below an unfinished attic,
or an exterior wall. In these cases the alarm
should be mounted on an inside wall.
• If the alarm cannot be located in the
center of the room, an off-center location
can be used on the ceiling. When off cen-
ter mounting an alarm on the ceiling,
locate it at a minimum of 4" (10 cm) from
the side wall (see figure 3).
• If a ceiling mounting location is not fea-
sible the next logical location for mounting
heat alarms is on the side wall. When
mounting the alarm on the wall, use an
inside wall with the top edge of the alarm
at a minimum of 4" (10 cm) and a maxi-
mum of 12" (30.5 cm) below the ceiling
(see figure 1).
• Install Heat Alarms on sloped, peaked or cathedral ceilings at or within 3 ft
(0.9m) of the highest point (measured horizontally). NFPA 72 states: “Smoke
alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (.3m in 2.4m) hori-
zontally shall be located on the high side of the room.” NFPA 72 states: “A row
FIGURE 1
FIGURE 2


Product specificaties

Merk: Kidde
Categorie: Niet gecategoriseerd
Model: HD135

Heb je hulp nodig?

Als je hulp nodig hebt met Kidde HD135 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Kidde

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd