Bekijk gratis de handleiding van Jung ES2212 (4 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 2 mensen en kreeg gemiddeld 4.4 sterren uit 1.5 reviews. Heb je een vraag over Jung ES2212 of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/4

Light Management Touch sensor AC/DC 24 V
Ref.-no.: ..2212..,
..2224.., ..2248..
Operating instructions
Touch sensor AC/DC 24 V
1. Safety warnings
Attention! Electrical equipment must be installed and fitted by
qualified electricians only. Failure to observe any of the installation
instructions may cause damage to the device and result in fire or
other hazards.
The sensor is a safety class III device. Connect only SELV circuits of
24 V to the device (no mains potential!).
2. Function
Touch sensors intended for connection to the 8-channel relay station (art.
no. RS8 REG) or other control systems with max. 24 V. One red LED for
each sensor indicates the corresponding status. Connection to the device
is made at the back by means of a terminal block.
Fig. A
Stand: Jan-09 24098200

Light Management Touch sensor AC/DC 24 V
Ref.-no.: ..2212..,
..2224.., ..2248..
Fig B
3. Connection
Sensor outputs and LED inputs for
• design range A 500: see fig. B
• design ranges CD 500, LS 990, Aluminium, Stainless Steel,
Anthracite: see fig. C
Assigned to following
rocker
Sensor
terminal
1-ch. 2-ch. 4-ch.
LED-
terminal
1 1 1
2
1
2 2
3 3 3
4
1
2
4 4
5 5 5
6
3
6 6
7 7 7
8
2
4
8 8
4. Installation
• Fit the supporting ring in the correct position on a ush-mounting
box (observe the TOP marking).
• Place the decorative frame on the supporting ring.
• Connect the touch sensor to the 8-channel relay station (see table
above).
• Place the touch sensor on the supporting ring.
• Protection against removal is possible.
2

Light Management Touch sensor AC/DC 24 V
Ref.-no.: ..2212..,
..2224.., ..2248..
Fig. C
5. Technical data
Rated voltage sensor: max. AC/DC 24 V SELV
Rated voltage LED: DC 24 V SELV
Current load of sensor: max. 20 mA per sensor
LED current: approx. 1 mA per LED
Connection: 2 x terminal block 9-pole
0.25...0.8 mm2 single wire
Power consumption: max. 0.2 W
(all LEDs on)
Safety class: III
Ambient temperature: -5 °C ... +45 °C
Storage / transport temperature: -25 °C ... +70 °C
Technical specifications subject to change.
3
Product specificaties
Merk: | Jung |
Categorie: | Niet gecategoriseerd |
Model: | ES2212 |
Heb je hulp nodig?
Als je hulp nodig hebt met Jung ES2212 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Jung
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
Handleiding Niet gecategoriseerd
- EAT
- Glorious
- Diamond Audio
- Autodesk
- Sanus
- Dometic
- Glemm
- Palson
- Skan Holz
- Crem
- Reloop
- Valcom
- Comtek
- Oromed
- Lapp
Nieuwste handleidingen voor Niet gecategoriseerd
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025
15 Juli 2025