IFM TA3430 Handleiding


Bekijk gratis de handleiding van IFM TA3430 (3 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 189 mensen en kreeg gemiddeld 4.3 sterren uit 95 reviews. Heb je een vraag over IFM TA3430 of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/3
Installation Instructions
Temperature transmitter
TA3430
706040 / 01 12 / 2012
UK
2
1 Functions and features
The temperature transmitter detects the current system temperature and converts
it into an analogue output signal (4 ... 20 mA).
Measuring range: 0 ... 140°C / 32 ... 284°F
Measuring element: Pt 1000 to DIN EN 60751, class A
Temperature resistance
110 115 120 125 130 135 140 145 150
[°C]
40
80
120
160
200
240
[min]
0
¥
155
Maximum operation time depending on the medium temperature
2 Installation
There are a number of possibilities:
1. Installation to G½ process connection.
2. Installation with E30016 (G ½) or E30024 (½“ NPT) progressive ring fitting.
3. Installation with welding adapter E30055 (ball adapter) or E30056 (collar
adapter).
4. Installation with E34110 clamp adapter for hygienic systems (A) and process
adapter (B).
Slightly grease the contact areas between the sensor and adapter using a lubricat-
ing paste which is suitable and approved for the application.
For information on the installation with adapters / progressive ring fittings please
refer to the instructions enclosed with the respective articles.
3
UK
standard applications hygienic systems
21 3 4
A
B
tightening torque: 30...50 Nmj
3 Electrical connection
The unit must be connected by a suitably qualified electrician.
The national and international regulations for the installation of electrical
equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
Referring to UL: For use on a low voltage circuit with overcurrent protec-
tion in accordance with UL873 Tab. 28.1 or Imax = 100/Ub (Ub = voltage
of the circuit).
Disconnect power.
Connect the unit as follows:
L+
3
4
2
1
BU
BK
BN
WH L-
n.c.
n.c.
3
1
4
2
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black); n.c. = not connected.


Product specificaties

Merk: IFM
Categorie: Niet gecategoriseerd
Model: TA3430

Heb je hulp nodig?

Als je hulp nodig hebt met IFM TA3430 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden