Bekijk gratis de handleiding van IFM TA3171 (5 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 12 mensen en kreeg gemiddeld 4.0 sterren uit 6.5 reviews. Heb je een vraag over IFM TA3171 of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/5
Installation Instructions
Temperature transmitter
TA3171 
704729 / 02 11 / 2010
UK
2
1  Functions and features
The temperature transmitter detects the current system temperature and converts
it into an analogue output signal (4 ... 20mA).
Measuring range: -50 ... 150°C / -58 ... 302°F
Measuring element: Pt 1000 to DIN EN 60751, class A
Temperature resistance
        









Maximum operation time depending on the medium temperature
Contents
1 Functions and features ........................................................................................2
2 Installation............................................................................................................3
3 Electrical connection ............................................................................................3
4 Scale drawing ......................................................................................................4
5 Technical data ......................................................................................................5
3
UK
2  Installation
Mount the unit to G¼ process
connection.
3  Electrical connection
The unit must be connected by a suitably qualified electrician.
The national and international regulations for the installation of electrical
equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
Disconnect power.
Connect the unit as follows:



 


Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black).