IFM SF6200 Handleiding


Bekijk gratis de handleiding van IFM SF6200 (3 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 12 mensen en kreeg gemiddeld 4.5 sterren uit 6.5 reviews. Heb je een vraag over IFM SF6200 of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/3
Installation Instructions
Flow sensor
701816 / 01 03 / 2011
2
1 Function and features
In conjunction with the VS3000 control monitor the flow sensor monitors flows in
liquids and gases. The sensor / control monitor combination senses whether a
preset flow value has been reached (= medium flowing) or not (= medium not flow-
ing) and provides a switched signal.
2 Installation
The unit is adaptable for various process fittings (clamp adapters to be ordered
separately as accessories, order no. E4016, E40174).
In the case of horizontal pipes mount the unit from the side, if possible (fig. 1).
- When the unit is to be mounted at the bottom of the pipe, it should be free
from deposits.
- When the unit is to be mounted at the top of the pipe, it should be completely
filled with the medium to be monitored.
In the case of vertical pipes mount the unit in a place where the medium flows
upwards (fig. 2).
1 2
To avoid malfunction a minimum
distance between the flow sensor and
bends, valves, changes in cross-sec-
tion or such like must be observed:
Min. 5 x pipe diameter upstream
(A),
min. 3 x pipe diameter downstream
(B).
D
A
B
min.
5 x D
min.
3 x D
3
UK
124
3
Screw the clamp adapter (2) onto the process fitting (1).
Insert the flow sensor (4) into the adapter.
Set the requested installation length.
Tighten the nut (3) (follow the instructions included with the clamp adapter).
Recommended insertion depth of the sensor: 20 ... 30 mm in the pipe. Min.
12 mm, max. to mid pipe.
Note: The sensor tip must not touch the pipe wall.
3 Electrical connection
Connection to control monitor VS3000 or SR59xx; voltage supply to
EN50178, SELV, PELV.
The unit must only be connected by an electrician.
The national and international regulations for the installation of electrical
equipment must be observed.
For units with cULus approval and the scope of validity cULus:
The device shall be supplied from an isolating transformer having a sec-
ondary Listed fuse rated either
a) max 5 amps for voltages 0~20 Vrms (0~28.3 Vp) or
b) 100/Vp for voltages of 20~30 Vrms (28.3~42.4 Vp).
4 Scale drawing
7,7
45
15
M12x1
217
10
20
25 146


Product specificaties

Merk: IFM
Categorie: Niet gecategoriseerd
Model: SF6200

Heb je hulp nodig?

Als je hulp nodig hebt met IFM SF6200 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden