Bekijk gratis de handleiding van IFM NF5029 (5 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 181 mensen en kreeg gemiddeld 4.6 sterren uit 91 reviews. Heb je een vraag over IFM NF5029 of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/5
Operating instructions
(Safety-related part ATEX)
Inductive NAMUR sensors
NE****/ NF****/ NG****/ NI****/ NN****/ NT****/ NS****
UK
706250 / 00 02 / 2012
2
Remarks for safe use in hazardous areas
Functions and features
Use in hazardous areas according to the classification
II 1G / 2G
(Group II, category 1G / 2G, apparatus for gas atmosphere).
The requirements of the standards EN 60079-0:2009, EN 60079-11:2012,
EN 60079-26:2007+Corr 2009 are met.
EC type test certificate
PTB 01 ATEX 2191
Use in hazardous areas according to the classification
II 1D
(Group II, category 1D, apparatus for dust atmosphere).
The requirements of the standards EN60079-0:2009 and EN60079-11:2012 are met.
EC type test certificate
BVS 04 ATEX E153
Use in hazardous areas according to the classification /
table 1a:
Type Group Category Type of
protection
Explosion
group
Tempera-
ture class Ta in °C
NT****
NE****
NF****
II 1G Ex ia IIC / IIB T6 -20...70
NT****
NE****
NF****
II 1G Ex ia IIC / IIB T5 -20...80
NG****
NI****
NN****
NS****
II 1G Ex ia IIB T6 -20...70
NG****
NI****
NN****
NS****
II 1G Ex ia IIB T5 -20...80
NG****
NI****
NN****
NS****
II 2G Ex ia IIC T6 -20...70
3
UK
Type Group Category
Type of
protection
Explosion
group
Tempera-
ture class Ta in °C
NG****
NI****
NN****
NS****
II 2G Ex ia IIC T5 -20...80
table 1b:
Type Group Category Type of
protection
Tempera-
ture class Ta in °C Ta in °C
NE****
NF****
NG****
NI****
NN****
NS****
NT****
II 1D Ex ia IIIC 90°C -20...70
NE****
NF****
NG****
NI****
NN****
NS****
NT****
II 1D Ex ia IIIC 100°C -20...80
Marking
II 1G Ex ia IIC T6 Ga
II 1D Ex ia IIIC T 90°C Da Ta -20...70 °C
Type
NT****, NE****, NF****
II 1G Ex ia IIC T5 Ga
II 1D Ex ia IIIC T 100°C Da Ta -20...80 °C
Type
NT****, NE****, NF****
II 1G Ex ia IIB T6 Ga
II 2G Ex ia IIC T6 Gb
II 1D Ex ia IIIC T 90°C Da Ta -20...70 °C
Type
NG****, NI****, NN****,NS****


Product specificaties