Bekijk gratis de handleiding van IFM E70580 (4 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 33 mensen en kreeg gemiddeld 4.9 sterren uit 17 reviews. Heb je een vraag over IFM E70580 of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/4
Installation instructions
AS-i bus termination
E70580
7391014/00 06 / 2014
UK
2
1 Safety instructions
Please read the product description prior to set-up of the unit. Ensure that the
product is suitable for your application without any restrictions.
The unit conforms to the relevant regulations and EC directives.
Improper or non-intended use may lead to malfunctions of the unit or to
unwanted effects in your application.
That is why installation, electrical connection, set-up, operation and
maintenance of the unit must only be carried out by qualified personnel
authorised by the machine operator.
2 Functions and features
The passive AS-i bus termination includes two different terminating resistors
(Z1 and Z2) and is used to improve the signal quality for total cable lengths of
100 m.
Three-level voltage monitoring and display for AS-Interface and AUX.
Cable lengths of up to 200 m are possible when the AS-i bus termination is
installed at the point furthest away from the AS-i power supply.
Max. current consumption < 15 mA.
3 Display
Green LED lights: AS-i voltage > 26.5 V DC
Yellow LED lights: AS-i voltage > 18 V DC
4 Installation
Disconnect power.
3
UK
Loosen screw 1 (included) and open the bus
termination.
Choose a flat mounting surface and fix the bus
termination on it (mounting holes 1).
The mounting screws are not supplied.
Preferably place the AS-i cable in the upper
profile slot (2) (terminating resistor Z1).
Should the required signal quality not be sufficient
despite a cable length of up to 200 m, place the
AS-i cable in the lower profile slot (3) (terminating
restistor Z2).
Place the cable correctly in the profile slot.
3
2
The free profile slot can be used for monitoring
the external voltage supply (AUX, black flat
cable).
If the black flat cable is not used, seal the
profile slot with a flat cable blank (E70399).