IFM E1003A Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor IFM E1003A (3 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 119 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/3
704613/00 11/2010
UK
Operating instructions
Sockets for the connection of intrinsically safe circuits
E10**A
2
Operating instructions (safety-related part ATEX)
Remarks for safe use in hazardous areas
Functions and features
• Use in hazardous areas according to the classification
II 1G
(group II, category 1G, apparatus for gas atmosphere).
The requirements of the standards EN 60079-0, EN 60079-11, EN 60079-26 are met.
• Use in hazardous areas according to the classification
II 1D
(group II, category 1D, apparatus for dust atmosphere).
The requirements of the standards EN 60079-0 and EN 61241-11 are met.
EC type test certificate
BVS 05 ATEX E106
• Marking
II 1G Ex ia IIC T6 Ga Ta: -20°C ... +80°C
II 1D Ex ia IIIB T85°C Da Ta: -20°C ... +80°C
alternatively
II 1D Ex ia IIIC T85°C Da
Ta according to table "Total power of the current ciruits"
Installation / Set-up
The sockets must only be installed, connected and set up by qualified staff. The qualified
staff must have knowledge of protection classes, regulations and provisions for apparatus in
hazardous areas.
Check whether the classification (see "Marking" above and marking on the socket) is
suitable for the application.
• Connection only to intrinsically safe certified circuits.
Several intrinsically safe circuits may be connected to the sockets. The sum of the voltages
of one or more intrinsically safe circuits must not exceed the following value:
Utotal max = 60 V (peak value)
For material group IIIC
Total power of the current circuits:
Max. ambient temperature [°C] 40 70 80
Admissible power [mW] 750 650 550
3
UK
Installation remarks / Installation
• Adhere to the relevant national regulations and provisions.
• Avoid electrostatic charging on plastic units and cables.
• Protect the sockets efficiently against damage.
• The connected cables must be firmly laid and protected efficiently against damage
(reduced strain relief according to EN 60079-0 A2.3.2)
• The sockets are not suitable for installation in walls which separate zone 0 from zone 1.
• The relevant installation regulations (e.g. EN 60079-14) must be adhered to.
• The following cable diameters may be connected to the respective sockets:
Order no. Permissible external cable diameter
E1001A 10 ... 12 mm
E1002A 6 ... 8 mm
E1003A 6 ... 8 mm
E1004A 6 ... 8 mm
Special conditions for safe operation
• The sockets are only suited for the connection of intrinsically safe circuits.
Maintenance / Repair
The unit must not be modified nor can it be repaired. In case of a fault please contact the
manufacturer.
If needed, you can obtain data sheets or EC type test certificates from the manufacturer (see
cover sheet / back).


Product specificaties

Merk: IFM
Categorie: Niet gecategoriseerd
Model: E1003A

Heb je hulp nodig?

Als je hulp nodig hebt met IFM E1003A stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd IFM

IFM

IFM DP4302 Handleiding

12 April 2024
IFM

IFM EVCB02 Handleiding

11 Maart 2024
IFM

IFM EVCB03 Handleiding

11 Maart 2024
IFM

IFM EVF666 Handleiding

11 Maart 2024
IFM

IFM TM4599 Handleiding

8 Januari 2024
IFM

IFM ZB0074 Handleiding

8 Januari 2024
IFM

IFM EVF661 Handleiding

8 Januari 2024
IFM

IFM IIP201 Handleiding

7 Januari 2024
IFM

IFM DP4200 Handleiding

7 Januari 2024
IFM

IFM IIP200 Handleiding

7 Januari 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd