Bekijk gratis de handleiding van IFM DI6005 (7 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 19 mensen en kreeg gemiddeld 4.7 sterren uit 10 reviews. Heb je een vraag over IFM DI6005 of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/7

Operating instructions
Compact speed monitor M18
DI6005
11473498 / 0007 / 2022
GB

DI6005 Compact speed monitor M18
6
4 Function
The unit has two independently configurable switching channels.
About the measuring function:
The sensor measures the time between 2 successive transitions from “undamped” to “damped”. The
pulse/pause ratio undamped/damped is not relevant, but both the damped and undamped states
should be reliably detected.
If the frequency determined from this time [1/min] is below the last measured value, the output speed
decreases with 1/t. At less than 0.5 pulses/min, 0.0 pulses/min is measured. There is no underload.
An overload is present at over 32,000.0 pulses/min (533 Hz).
4.1 Single-point mode
SP1
H
SSC
0 PDV
OFF ON
Fig.1: Normally open = low active (factory setting)
SP1: Switch-off point
SP1+H: Switch-on point
If a set rotational speed is not reached, the transistor output will signal this as non-conducting.
H
SSC
0 PDV
SP1
ON OFF
Fig.2: Normally closed = high active
SP1: Switch-on point
SP1+H: Switch-off point
If a set rotational speed is not reached, the transistor output will signal this as conducting.
Imp./min.
3000
2500
2000
1500
1000
500
0
1
0
1
0
OUT
2
3
4
1
OUT
SP1 + H
SP1
t
1: Power-on delay time
2: Start-up delay
3: Normally open = low active
4: Normally closed = high active

DI6005 Compact speed monitor M18
8
4.3 Two-point mode
SP2 SP1
H
SSC
0 PDV
OFF ON
Fig.5: Normally open = low active
SP2: Switch-off point
SP1: Switch-on point
If a set rotational speed is not reached, the transistor output will signal this as non-conducting.
H
SSC
0 PDV
SP2 SP1
ON OFF
Fig.6: Normally closed = high active
SP2: Switch-on point
SP1: Switch-off point
If a set rotational speed is not reached, the transistor output will signal this as conducting.
Imp./min.
3000
2500
2000
1500
1000
500
0
1
0
1
0
OUT
2
3
4
1
OUT
SP1
SP2
t
1: Power-on delay time
2: Start-up delay
3: Normally open = low active
4: Normally closed = high active
It is also possible to configure SP1 as the lower switch point and SP2 as the upper switch point.
The lower switch point must be at least 10% lower than the higher switch point.
4.4 IO-Link mode
IO-Link allows the configuration of internal parameters such as switching threshold, start-up delay and
switching behaviour (normally closed/normally open) as well as reading the current measured values.
Furthermore IO-Link protects against signal faults and measured value losses as well as tampering
with the sensor. IO-Link facilitates the identification of connected devices in the system and provides
diagnostic functions.
Product specificaties
Merk: | IFM |
Categorie: | Niet gecategoriseerd |
Model: | DI6005 |
Heb je hulp nodig?
Als je hulp nodig hebt met IFM DI6005 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd IFM
1 Juli 2025
30 Juni 2025
16 Juni 2025
16 Juni 2025
16 Juni 2025
16 Juni 2025
23 Mei 2025
2 Mei 2025
2 Mei 2025
2 Mei 2025
Handleiding Niet gecategoriseerd
- Hombli
- Leaptel
- Vitek
- Lenmar
- ORCA
- Sightmark
- Rocstor
- Nobo
- Sensei
- PTZ Optics
- Powerfix
- Ikan
- Mitsai
- Cocraft
- Oertli
Nieuwste handleidingen voor Niet gecategoriseerd
1 Juli 2025
1 Juli 2025
1 Juli 2025
1 Juli 2025
1 Juli 2025
1 Juli 2025
1 Juli 2025
1 Juli 2025
1 Juli 2025
1 Juli 2025