Honeywell F118 Handleiding
Honeywell
Luchtreiniger
F118
Lees hieronder de 📖 handleiding in het Nederlandse voor Honeywell F118 (12 pagina's) in de categorie Luchtreiniger. Deze handleiding was nuttig voor 24 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/12
PRODUCT DATA
68-0209-3
The Honeywell Trademark is used under license from Honeywell
International Inc. by Air-Pure Systems.
Honeywell International Inc. makes no representations or warranties
with respect to this product.
F118 In-Ceiling
Media Air Cleaner
APPLICATION
The F118 In-Ceiling Media Air Cleaner uses a three-speed
direct-drive, forward-curve blower motor and a 95 percent
DOP particle filter to capture airborne particles such as dust,
soot, and cooking smoke from the air circulated through it.
When equipped with two CPZ™ modules, the air cleaner also
adsorbs gases and odors from the air passing through it. The
F118 is recommended for use in rooms with drop ceilings, and
for spaces with structural ceilings not higher than 16 feet (4.8
meters) where there is a minimum one-foot (0.3 meter)
clearance between the drop ceiling and the structural ceiling.
The air cleaner is designed to use the Coanda effect to
circulate air throughout the space. This effect is the tendency
of air to travel close to a wall contour when ejected from a jet.
The air cleaner draws contaminated air up from the center of
the room, forces it through the filters, and then blows the
filtered air out through the narrow ends of the air cleaner.
FEATURES
• The DOP particle filter is 95 percent efficient at 0.3
micron particles, and more efficient on particles
smaller and larger.
• CPZ™ modules can reduce space odors.
• Circulates up to 425 cubic feet per minute (723 cubic
meters per hour).
• Provides Coanda air distribution by drawing in dirty
air, cleaning it, and bi-directionally recirculating the
filtered air throughout the space.
• Designed to overcome the increase in air flow
resistance normally caused by filter loading.
• White color cover complements the ceiling.
• Accessible three-speed pushbutton switch.
• Optional wall-mounted remote switch.
• Filters are easily removed and replaced.
• READ AND SAVE THESE
INSTRUCTIONS
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Planning the Installation ................................................... 3
Installation ........................................................................ 4
Operation .......................................................................... 8
Service ............................................................................. 8
Parts list ............................................................................ 9
Limited Two-Year Warranty .............................................. 12
F118 IN-CEILING MEDIA AIR CLEANER
68-0209-3 Revised 9-08 2
ORDERING INFORMATION
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Commercial Air Products Distributor.
2. Air-Pure Systems
16873 Fish Point Rd. SE
Prior Lake, MN 55372-1714
Phone: (800) 998-1919
Fax: (800) 221-3248
SPECIFICATIONS
IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed specifica-
tions. Also, this product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.
Color: Galvanized steel cabinet and white cover.
Blower/Motor: Three-speed direct-drive forward curve. Motor
lubrication is not required.
Ambient Temperature Rating:
Shipping and Storage: -20°F to +150°F ( -29°C to +66°C).
Operating: Ambient temperatures usually below 77°F (25°C)
but occasionally as high as 104°F (40°C).
Humidity: Up to 95% relative humidity, non-condensing.
Air Volume:
Electrical Ratings:
Grille Type: Perforated metal.
Dimensions:
Fig. 1. Approximate dimensions of F118 in in. (mm).
Mounting:
Hangs freely from structural ceiling.
Can be recessed into a drop ceiling frame.
Weight:
Shipping (Cabinet and Contents): 119 lb (54 kg).
Installation: 92 lb (42 kg).
CPZ™ Adsorbent Module: 8 lb (3.6 kg) each.
Module Total Weight: 10 lb. (4.5 kg) each.
Sound Level at 3.3 ft (1m):
High Speed: 65 dBA.
Medium Speed: 54.5 dBA.
Low Speed: 48 dBA.
Operation at low and medium speeds is within white noise
range.
Approvals:
UL: Listed.
CSA: Certified.
CE: Pending.
Replacement Parts: See the Parts List section.
120V 230V
High 425 cfm, 723 m3/hr 400 cfm, 680 m3/hr
Medium 300 cfm, 510 m3/hr 320 cfm, 544 m3/hr
Low 200 cfm, 340 m3/hr 220 cfm, 374 m3/hr
Current Draw 120V 230V
High 2.8A 1.6A
Medium 2.0A 0.8A
Low 1.4A 0.5A
12-1/2
(317)
1 (25) CLEARANCE
OF DROP CEILING
47-3/4
(1213)
23-1/2
(597)
VIEW UNDERSIDE
(GRILLE REMOVED)
POWER CONNECTOR
(ELECTRICAL BOX)
M16213
SUPPORT RODS
PRE-FILTER (WRAPS) PARTICULATE FILTER
F118 IN-CEILING MEDIA AIR CLEANER
368-0209-3 Revised 9-08
PLANNING THE INSTALLATION
The sizing procedure determines the number of F118 needed.
The correct number required for a particular application
depends on:
— type of contamination.
— number of occupants.
— room volume.
— room use.
— outdoor air quality.
Assuming that the structural ceiling height is no higher than
16 ft (4.8m), one F118 set on high speed cleans 425 cfm,
25,500 cf/hr (723 m3/hr). The number of air changes per hour
determines the amount of air cleaning that occurs. Use the
following formula to determine the required number of F118
Air Cleaners:
Area of room in cubic feet/air cleaner cubic feet per hour x
desired number of air changes per hour.
For example, to compute the number of air cleaners that
would be required to clean an area of 30,000 cubic feet, at
the rate of four times per hour when operating on high
speed: (30,000/25,500 x 4 = 4.7).
Result: This area requires five F118.
For the most efficient operation, place the F118 as close as
possible to the contaminant source. For ambient air cleaning,
it is essential to establish a uniform airflow pattern throughout
the entire space. Physical limitations, such as the following,
may change the number of air cleaners required:
• If there is insufficient mounting space, fewer air cleaners
can be installed. If it is necessary to reduce the number of
air changes per hour, bring in more outdoor air to maintain
low contaminant levels.
• An irregularly shaped room does not allow even airflow,
and may require more air cleaners.
For questions about determining the number of air cleaners
needed, consult your local Honeywell Commercial Air Cleaner
Distributor.
Choose Location
The air cleaner is designed to hang from a structural ceiling. It
mounts horizontally, inside or outside of a drop ceiling system.
It also fits between joists set 24 in. (610 mm) on center. When
used with a drop ceiling system, allow at least 12 in. (305 mm)
clearance between the structural and drop ceiling to allow
space for the air cleaner. To ensure unobstructed airflow, the
grille, which is one inch (25 mm) deep, must protrude below
the drop ceiling surface.
The location and orientation of the air cleaner affects its
performance. Mount it in a location that allows airflow to reach
the extreme areas of the zone. See Fig. 2.
Fig. 2. F118 Air Circulation Schematic (Coanda Airflow).
The air cleaner is rectangular to align with the walls of any
rectangular space. When installing an air cleaner in a
rectangular space, place the length parallel with the room
length and the width parallel with the room width.
When a room requires only one air cleaner, hang it in the
center of the room.
Large rooms usually require more than one air cleaner. When
using several, divide the entire space into equal volumes and
distribute the air cleaners throughout the space so each air
cleaner circulates similar air quantities. To ensure optimum
performance of each air cleaner:
1. Use the formula above to determine the number of air
cleaners required for the large room.
2. Visually divide the entire room into several cubic vol-
umes. For example, if three air cleaners are to be
installed, visualize the room as approximately three
cubic volumes.
3. Consider each portion as a single room and install the
air cleaner at the center of each area. Align the air
cleaners to be parallel. See Fig. 3.
Fig. 3. Arranging air cleaners in a large area.
M16209A
AIR PATHAIR PATH
RECOMMENDED FOR ROOMS
LESS THAN 16 FEET HIGH
(FLOOR TO STRUCTURAL CEILING )
DISTANCE FROM STRUCTURAL
CEILING TO DROP
CEILING – MINIMUM 12 INCHES
ALIGN AIR CLEANER WITH
WALLS, IF POSSIBLE
CORRECT INCORRECT
M16207A
Product specificaties
Merk: | Honeywell |
Categorie: | Luchtreiniger |
Model: | F118 |
Heb je hulp nodig?
Als je hulp nodig hebt met Honeywell F118 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Luchtreiniger Honeywell
13 December 2023
13 December 2023
13 December 2023
13 December 2023
16 November 2023
8 November 2023
8 November 2023
8 November 2023
8 November 2023
8 November 2023
Handleiding Luchtreiniger
- Luchtreiniger Electrolux
- Luchtreiniger Bosch
- Luchtreiniger Philips
- Luchtreiniger Samsung
- Luchtreiniger Delonghi
- Luchtreiniger Xiaomi
- Luchtreiniger Panasonic
- Luchtreiniger LG
- Luchtreiniger AEG
- Luchtreiniger BEKO
- Luchtreiniger Fysic
- Luchtreiniger JVC
- Luchtreiniger Karcher
- Luchtreiniger Miele
- Luchtreiniger Medion
- Luchtreiniger Quigg
- Luchtreiniger Tefal
- Luchtreiniger Topcom
- Luchtreiniger Unold
- Luchtreiniger Whirlpool
- Luchtreiniger Hoover
- Luchtreiniger Acer
- Luchtreiniger Adler
- Luchtreiniger Aeris
- Luchtreiniger Air-O-Swiss
- Luchtreiniger Airbutler
- Luchtreiniger Airfree
- Luchtreiniger Alpina
- Luchtreiniger Aluratek
- Luchtreiniger Amprobe
- Luchtreiniger Andrews
- Luchtreiniger Argo
- Luchtreiniger Bartscher
- Luchtreiniger Be Cool
- Luchtreiniger Bestron
- Luchtreiniger Beurer
- Luchtreiniger Bionaire
- Luchtreiniger Bissell
- Luchtreiniger Blaupunkt
- Luchtreiniger Blue Air
- Luchtreiniger Bob Home
- Luchtreiniger Boneco
- Luchtreiniger Bort
- Luchtreiniger Breville
- Luchtreiniger Daikin
- Luchtreiniger Daitsu
- Luchtreiniger Dimplex
- Luchtreiniger Dirt Devil
- Luchtreiniger Domo
- Luchtreiniger Duracraft
- Luchtreiniger Duux
- Luchtreiniger Dyson
- Luchtreiniger Easy Home
- Luchtreiniger Efbe-schott
- Luchtreiniger Elro
- Luchtreiniger ETA
- Luchtreiniger Eurom
- Luchtreiniger Evolar
- Luchtreiniger Ezviz
- Luchtreiniger Fakir
- Luchtreiniger Falmec
- Luchtreiniger Fellowes
- Luchtreiniger Fuave
- Luchtreiniger Galanz
- Luchtreiniger Gastroback
- Luchtreiniger GE
- Luchtreiniger Gemini
- Luchtreiniger Gorenje
- Luchtreiniger Gutfels
- Luchtreiniger H.Koenig
- Luchtreiniger Haier
- Luchtreiniger Hansa
- Luchtreiniger Hanseatic
- Luchtreiniger Haus Luft
- Luchtreiniger Health-Mor
- Luchtreiniger Helios
- Luchtreiniger Hisense
- Luchtreiniger Hitachi
- Luchtreiniger Homedics
- Luchtreiniger Hunter
- Luchtreiniger Ideal
- Luchtreiniger Innoliving
- Luchtreiniger IonizAir
- Luchtreiniger IQAir
- Luchtreiniger Kalorik
- Luchtreiniger Klarbach
- Luchtreiniger Klarstein
- Luchtreiniger Kodak
- Luchtreiniger Kogan
- Luchtreiniger Lanaform
- Luchtreiniger Laserliner
- Luchtreiniger Leifheit
- Luchtreiniger Leitz
- Luchtreiniger Lentz
- Luchtreiniger Lifeair
- Luchtreiniger Livoo
- Luchtreiniger Maxxmee
- Luchtreiniger Medisana
- Luchtreiniger Mill
- Luchtreiniger Mitsubishi
- Luchtreiniger Moneual
- Luchtreiniger Nedis
- Luchtreiniger Periso
- Luchtreiniger Polti
- Luchtreiniger Prem-i-air
- Luchtreiniger Profile
- Luchtreiniger Qlima
- Luchtreiniger Qlima - Zibro
- Luchtreiniger Reer
- Luchtreiniger REMKO
- Luchtreiniger Rowenta
- Luchtreiniger Royal Sovereign
- Luchtreiniger Russell Hobbs
- Luchtreiniger Sanyo
- Luchtreiniger Sauber
- Luchtreiniger Sencor
- Luchtreiniger Shark
- Luchtreiniger Sharp
- Luchtreiniger Silvercrest
- Luchtreiniger Soehnle
- Luchtreiniger Solis
- Luchtreiniger Sonnenkonig
- Luchtreiniger SPT
- Luchtreiniger Stadler Form
- Luchtreiniger Steba
- Luchtreiniger Stirling
- Luchtreiniger Stylies
- Luchtreiniger Sunbeam
- Luchtreiniger Suntec
- Luchtreiniger Sygonix
- Luchtreiniger Taurus
- Luchtreiniger TCL
- Luchtreiniger Teco
- Luchtreiniger Tesla
- Luchtreiniger Tosot
- Luchtreiniger Tristar
- Luchtreiniger Trotec
- Luchtreiniger Turmix
- Luchtreiniger Uni-T
- Luchtreiniger VAX
- Luchtreiniger Venta
- Luchtreiniger Vicks
- Luchtreiniger Vornado
- Luchtreiniger WDH
- Luchtreiniger Whynter
- Luchtreiniger Winix
- Luchtreiniger Woods
- Luchtreiniger Zelmer
- Luchtreiniger Zepter
- Luchtreiniger Olimpia Splendid
- Luchtreiniger Oregon Scientific
- Luchtreiniger Valore
- Luchtreiniger Black And Decker
- Luchtreiniger Concept
- Luchtreiniger Cuisinart
- Luchtreiniger ECG
- Luchtreiniger Guzzanti
- Luchtreiniger Hamilton Beach
- Luchtreiniger Heinner
- Luchtreiniger OBH Nordica
- Luchtreiniger Orbegozo
- Luchtreiniger Scarlett
- Luchtreiniger Trisa
- Luchtreiniger Wilfa
- Luchtreiniger Steren
- Luchtreiniger Soler And Palau
- Luchtreiniger Instant
- Luchtreiniger Hilti
- Luchtreiniger Danby
- Luchtreiniger Infiniton
- Luchtreiniger Cotech
- Luchtreiniger Ardes
- Luchtreiniger GOTIE
- Luchtreiniger Teesa
- Luchtreiniger Alen
- Luchtreiniger ElectriQ
- Luchtreiniger Heaven Fresh
- Luchtreiniger Heylo
- Luchtreiniger Holmes
- Luchtreiniger Inventor
- Luchtreiniger Oreck
- Luchtreiniger Prime3
- Luchtreiniger Proficare
- Luchtreiniger TruSense
- Luchtreiniger Brondell
- Luchtreiniger Brentwood
- Luchtreiniger Oricom
- Luchtreiniger Bimar
- Luchtreiniger Crane
- Luchtreiniger Lasko
- Luchtreiniger SPC
- Luchtreiniger Cecotec
- Luchtreiniger Thermex
- Luchtreiniger Carrier
- Luchtreiniger SHE
- Luchtreiniger LTC
- Luchtreiniger Hombli
- Luchtreiniger Levoit
- Luchtreiniger Aerial
- Luchtreiniger Blueair
- Luchtreiniger Argoclima
- Luchtreiniger Clean Air Optima
- Luchtreiniger AENO
- Luchtreiniger Cado
- Luchtreiniger Łucznik
- Luchtreiniger Queenaire
- Luchtreiniger GermGuardian
- Luchtreiniger LightAir
- Luchtreiniger Coway
- Luchtreiniger XPower
- Luchtreiniger Sensede
- Luchtreiniger Airthereal
- Luchtreiniger PURIFY
- Luchtreiniger Therapure
- Luchtreiniger AirExchange
- Luchtreiniger Djive
- Luchtreiniger TruSens
- Luchtreiniger Newaire
- Luchtreiniger Ametista
- Luchtreiniger Dri Eaz
- Luchtreiniger NEO Tools
- Luchtreiniger Jarden
- Luchtreiniger JIMMY
- Luchtreiniger Ravanson
- Luchtreiniger Zedar
- Luchtreiniger Nevoox
- Luchtreiniger AlorAir
- Luchtreiniger Camfil
- Luchtreiniger Kleva
- Luchtreiniger House & Luft
- Luchtreiniger AeraMax
- Luchtreiniger Guardian
- Luchtreiniger Envion
- Luchtreiniger RainbowAir
- Luchtreiniger ASIGO
- Luchtreiniger P3 International
- Luchtreiniger Luma Comfort
- Luchtreiniger Ionmax
- Luchtreiniger Greentec
- Luchtreiniger Airo
- Luchtreiniger Meross
- Luchtreiniger MANN+HUMMEL
- Luchtreiniger Airocide
- Luchtreiniger PRIMAVERA
- Luchtreiniger OZONOS
- Luchtreiniger Welcare
- Luchtreiniger DH Lifelabs
- Luchtreiniger Hacienda
Nieuwste handleidingen voor Luchtreiniger
25 April 2024
18 April 2024
18 April 2024
18 April 2024
16 April 2024
16 April 2024
16 April 2024
16 April 2024
16 April 2024
16 April 2024