Installation Instructions
For Small Grounding Kit
99411399
Panel Screws Enclosed
Grounding Label
Keps Nut
10–32 Hex Nut
Ground Wire
(not included)
Panel Screw
Lockwasher
10–32x5/8 Screw
1. Insert the 10-32x5/8 screw through the hole in the panel as shown.
2. Secure screw with keps nut. The keps nuts must penetrate into the
paint to ensure electrical continuity.
3. Attach the ground wire and secure with 10-32 hex nut as shown.
4. Install the lockwasher under one of the screws securing the panel to
ensure grounding between the panel and the enclosure. Recommend-
ed torque for grounding washer not to exceed 30 in-lbs.
5. Attach included grounding label adjacent to the bolt as shown.
© 2011 Pentair Technical Products
PH 763 422 2211 • hoffmanonline.com87568836
Rev. B
P/N 93217001
Product specificaties
| Merk: | Hoffman |
| Categorie: | Niet gecategoriseerd |
| Model: | A161410CHFL |
| Kleur van het product: | Grijs |
| Breedte: | 356 mm |
| Diepte: | 254 mm |
| Hoogte: | 406 mm |
| Certificering: | UL 508A Listed; Type 4, 12; File No. E61997cUL Listed per CSA C22.2 No. 94 Listed; Type 4, 12; File No. E61997NEMA/EEMAC Type 4 and 12IEC 60529, IP 66 |
| Materiaal: | Staal |
| Aantal montagegaten: | 4 |
Heb je hulp nodig?
Als je hulp nodig hebt met Hoffman A161410CHFL stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Hoffman
Hoffman A484812WFLP Handleiding Hoffman PPB1126 Handleiding Hoffman A12106CHNFSS Handleiding Hoffman A1614CHFL Handleiding Hoffman A8064CHNFSS Handleiding Hoffman A1212CHNFSS Handleiding Hoffman A30H2412SS6LP Handleiding Hoffman PJ2F Handleiding