The brightness and temperature sensor is suitable for brightness and
temperature measurement for the KNX building management
system.
1.
Push the bus cable through the
nippel grommet into the terminal
compartment.
2.
Connect the bus terminal to the
inserted cable. Pay attention to
polarity.
3.
Press the bus terminal
completely onto the contact
pins.
Electrical equipment may only be installed and assembled by a qualified
electrician. The national regulations and safety directions must be observed
Please observe the rules and instructions in the ZVEI/ZVEH manual for
building management systems to ensure that the bus cables are laid
correctly and commissioning of the devices is carried out correctly.KNX
Interventions in and modifications to the device will invalidate the warranty.
The ETS assigns the physical address, the group addresses; the setting
of parameters is also done with the ETS.
Loading of the physical address:
2
1.
Press button 1.
LED 2 lights up.
2.
The physical address can be assigned
by the ETS.
Measurement range for brightness measurement
1 to 100 000 lux (tolerance ± 20 % resp. ± 1 Lux)
Measurement range for temperature measurement
–25 °C to + 55 °C (tolerance 5 % resp. ± 1 Grad)
(The larger tolerance applies in each case.)
Please note when selecting the installation location
•
that the brightness and temperature sensor is exposed to no or to
minimal dirt, as a dirty sensor has an adverse effect on the
brightness measurement.
•
that direct sunlight can interfere with the temperature
measurement.
Install the brightness and temperature sensor only in a
vertical position!
Consequence on non-observance
Moisture and/or dirt can get into the housing! This will result in
device malfunctions and will short circuit the bus- cable.
Installing the cover
1.
Place the cover carefully over the installed device.
2.
Screw on the cover
Maintaining the cover
1. Clean the cover from time to time, so that the measured values during
brightness measurement are not corrupted by
dirt deposits.
Use a moist
cloth for this.
Brightness and temperature sensor 7549 20 01
Operating voltage bus voltage
Bus coupling unit integrated
Temperature measuring range – 25 °C to +55 °C
Tolerance ± 5 % resp. ± 1 degree
Brightness measuring range 1 to 100 000 Lux
Tolerance Lux± 20 % min. ± 1
Power consumption
< 150 mW
Degree of protection built- in IP 54
with vertical installation with
attached cover
We reserve the right to realise technical and formal changes to the product
in the interest of technical progress.
Our products are under guarantee within the scope of the statutory provisions.
If you have a warranty claim, please contact the point of sale or ship the
device postage free with a description of the fault to our Service -
Center.
Berker GmbH & Co. KG
Abt. Service-Center
Hubertusstraße 17
D- -57482 Wenden Ottfingen
Phone: 0 23 55 / 90 5-0
Fax: 0 23 55 / 90 5- 111
6. B
us connection
7.
Entry of the physical address
3.
Measurement ranges
4.
Selecting the installation location
5.
Installation of the sensor
8.
Installing and maintaining the cover
9.
Technical data
10.
Warranty
310 965 02
Operating instructions
2.
Safety
1.
Use


Product specificaties

Merk: Hager
Categorie: Niet gecategoriseerd
Model: 75492002

Heb je hulp nodig?

Als je hulp nodig hebt met Hager 75492002 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Hager

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd