Fujitsu Airstage AJYA72LALH Handleiding
Bekijk gratis de handleiding van Fujitsu Airstage AJYA72LALH (25 pagina’s), behorend tot de categorie Airco. Deze gids werd als nuttig beoordeeld door 92 mensen en kreeg gemiddeld 4.1 sterren uit 9 reviews. Heb je een vraag over Fujitsu Airstage AJYA72LALH of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/25

English
OUTDOOR UNIT
PART NO. 9378945357
Deutsch
AUßENGERÄT
TM
FrançaisEspañol
UNITÉ EXTÉRIEURE
UNIDAD EXTERIOR
Italiano
UNITÀ ESTERNA
ΕλληνικάPortuguês
ΕΞΩΤΕΡΙΚΉΜΟΝΆΔΑ
UNIDADE EXTERIOR
РусскийTürkçe
中 文
ВНЕШНИЙМОДУЛЬ
DIŞ ÜNİTE
室外机
AJYA72LALH
AJYA90LALH
AJY108LALH
AJY126LALH
AJY144LALH
AJHA72LALH
AJHA90LALH
AJH108LALH
AJH126LALH
AJH144LALH
INSTALLATION MANUAL
For authorized service personnel only.
INSTALLATIONSANLEITUNG
Nur für autorisiertes Fachpersonal.
MANUEL D’INSTALLATION
MANUAL DE INSTALACIÓN
Pour le personnel agréé uniquement.
Únicamente para personal de servicio autorizado.
MANUALE DI INSTALLAZIONE
A uso esclusivo del personale tecnico autorizzato.
ΕΓΧΕΙΡΙΔΙΟΕΓΚΑΤΑΣΤΑΣΗΣ
Μόνογιαεξουσιοδοτημένοτεχνικό.προσωπικό
MANUAL DE INSTALAÇÃO
Apenas para técnicos autorizados.
РУКОВОДСТВОПОУСТАНОВКЕ
Толькодля авторизованного обслуживающего.персонала
Yalnızca yetkili servis personeli için.
仅针对授权的专业维修人员。
MONTAJ KILAVUZU
安装说明书
[Original instructions]
Product specificaties
| Merk: | Fujitsu |
| Categorie: | Airco |
| Model: | Airstage AJYA72LALH |
Foutcodes Fujitsu Airstage AJYA72LALH
Foutcodes uit de officiële handleiding, met betekenis en oplossing.
| Code | Betekenis | Oplossing |
|---|---|---|
| E113.1 | Communication error between outdoor units | Check communication cables and connections between units |
| E114.1 | Outdoor unit network communication 1 error | Check network communication cables and settings |
| E114.2 | Outdoor unit network communication 2 error | Check network communication cables and settings |
| E114.5 | The number of indoor unit shortage | Check indoor unit connections and quantity |
| E128.1 | Auto address setting error | Retry auto address setting procedure |
| E128.4 | Signal amplifier auto address error | Check signal amplifier and retry address setting |
| E15U.1 | Indoor unit miscellaneous error | Check indoor unit for general errors |
| E161.5 | Outdoor unit reverse/missing phase & wiring error | Check electrical phase and wiring connections |
| E162.3 | Outdoor unit EEPROM access error | Check EEPROM and electronic components |
| E162.6 | Outdoor unit inverters communication error | Check inverter communication connections |
| E162.8 | Outdoor unit EEPROM data corruption error | Check and replace EEPROM if necessary |
| E163.1 | Outdoor unit inverter error | Check inverter operation and power supply |
| E167.2 | Outdoor unit inverter PCB power short interruption | Check inverter PCB for shorts and power supply |
| E168.1 | Outdoor unit magnetic relay error | Check magnetic relay operation |
| E168.2 | Outdoor unit rush current limiting resister temp. rise error (protective operation) | Check rush current limiting resistor and cooling |
| E169.1 | Outdoor unit transmission PCB parallel communication error | Check PCB communication connections |
| E171.1 | Outdoor unit discharge temp. thermistor 1 error | Check and replace discharge temperature thermistor 1 |
| E171.2 | Outdoor unit discharge temp. thermistor 2 error | Check and replace discharge temperature thermistor 2 |
| E172.1 | Outdoor unit compressor temp. thermistor 1 error | Check and replace compressor temperature thermistor 1 |
| E172.2 | Outdoor unit compressor temp. thermistor 2 error | Check and replace compressor temperature thermistor 2 |
| E173.3 | Outdoor unit heat ex. liquid temp. thermistor error | Check and replace heat exchanger liquid temperature thermistor |
| E174.1 | Outside air temp. thermistor error | Check and replace outside air temperature thermistor |
| E175.1 | Outdoor unit suction gas temp. thermistor error | Check and replace suction gas temperature thermistor |
| E177.1 | Outdoor unit heat sink temp. thermistor error | Check and replace heat sink temperature thermistor |
| E182.1 | Outdoor unit sub-cool heat ex. gas inlet temp. thermistor error | Check and replace gas inlet temperature thermistor |
| E182.2 | Outdoor unit sub-cool heat ex. gas outlet temp. thermistor error | Check and replace gas outlet temperature thermistor |
| E183.1 | Outdoor unit liquid pipe temp. thermistor 1 error | Check and replace liquid pipe temperature thermistor 1 |
| E183.2 | Outdoor unit liquid pipe temp. thermistor 2 error | Check and replace liquid pipe temperature thermistor 2 |
| E184.1 | Outdoor unit current sensor 1 error (permanent stop) | Check and replace current sensor 1 |
| E186.1 | Outdoor unit discharge pressure sensor error | Check and replace discharge pressure sensor |
| E186.3 | Outdoor unit suction pressure sensor error | Check and replace suction pressure sensor |
| E186.4 | Outdoor unit high pressure switch 1 error | Check and replace high pressure switch 1 |
| E186.5 | Outdoor unit high pressure switch 2 error | Check and replace high pressure switch 2 |
| E913.1 | Outdoor unit compressor 2 error | Check outdoor unit compressor 2 operation |
| E913.2 | Outdoor unit compressor 2 current value error | Check compressor 2 current values |
| E913.3 | Outdoor unit inverter compressor start up error | Check inverter and compressor startup sequence |
| E914.1 | Outdoor unit trip detection | Check outdoor unit for trip conditions |
| E915.5 | Outdoor unit compressor motor loss of synchronization error | Check motor synchronization and electrical connections |
| E917.1 | Outdoor unit fan motor 1 lock error | Check fan motor 1 for obstructions or mechanical damage |
| E917.4 | Outdoor unit fan motor 1 undervoltage error | Check power supply voltage to fan motor 1 |
| E917.5 | Outdoor unit fan motor 1 temperature error (protective action) | Allow unit to cool, check fan motor temperature sensor |
| E91U.2 | Outdoor slave unit error | Check outdoor slave unit communication and operation |
| E9A1.1 | Outdoor unit discharge temperature 1 error (permanent stop) | Check discharge temperature thermistor and refrigerant system |
| E9A2.1 | Outdoor unit discharge temperature 2 error (permanent stop) | Check discharge temperature thermistor and refrigerant system |
| E9A3.1 | Outdoor unit compressor 1 temperature error | Check compressor 1 temperature sensor |
| E9A3.2 | Outdoor unit compressor 2 temperature error | Check compressor 2 temperature sensor |
| E9A4.1 | Outdoor unit high pressure error | Check refrigerant charge and high pressure system |
| E9A4.2 | Outdoor unit high pressure protective action 1 | Check refrigerant charge and system pressure |
| E9A4.3 | Outdoor unit high pressure protective action 2 | Check refrigerant charge and system pressure |
| E9A5.1 | Outdoor unit low pressure error | Check refrigerant charge and low pressure system |
Heb je hulp nodig?
Als je hulp nodig hebt met Fujitsu Airstage AJYA72LALH stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Airco Fujitsu
10 Juli 2026
9 Juli 2026
8 Juli 2026
8 Juli 2026
8 Juli 2026
8 Juli 2026
7 Juli 2026
7 Juli 2026
7 Juli 2026
7 Juli 2026
Handleiding Airco
Nieuwste handleidingen voor Airco
26 Augustus 2026
26 Augustus 2026
25 Augustus 2026
25 Augustus 2026
25 Augustus 2026
24 Augustus 2026
24 Augustus 2026
24 Augustus 2026
24 Augustus 2026
21 Augustus 2026