Fujitsu Airstage AJYA72LALH Handleiding

Fujitsu Airco Airstage AJYA72LALH

Bekijk gratis de handleiding van Fujitsu Airstage AJYA72LALH (25 pagina’s), behorend tot de categorie Airco. Deze gids werd als nuttig beoordeeld door 92 mensen en kreeg gemiddeld 4.1 sterren uit 9 reviews. Heb je een vraag over Fujitsu Airstage AJYA72LALH of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/25
English
OUTDOOR UNIT
PART NO. 9378945357
Deutsch
AUßENGERÄT
TM
FrançaisEspañol
UNITÉ EXRIEURE
UNIDAD EXTERIOR
Italiano
UNITÀ ESTERNA
ΕλληνικάPortuguês
ΕΞΩΤΕΡΙΚΉΜΟΝΆΔΑ
UNIDADE EXTERIOR
РусскийTürkçe
中 文
ВНЕШНИЙМОДУЛЬ
DIŞ ÜNİTE
AJYA72LALH
AJYA90LALH
AJY108LALH
AJY126LALH
AJY144LALH
AJHA72LALH
AJHA90LALH
AJH108LALH
AJH126LALH
AJH144LALH
INSTALLATION MANUAL
For authorized service personnel only.
INSTALLATIONSANLEITUNG
Nur für autorisiertes Fachpersonal.
MANUEL D’INSTALLATION
MANUAL DE INSTALACIÓN
Pour le personnel agréé uniquement.
Únicamente para personal de servicio autorizado.
MANUALE DI INSTALLAZIONE
A uso esclusivo del personale tecnico autorizzato.
ΕΓΧΕΙΡΙΔΙΟΕΓΚΑΤΑΣΤΑΣΗΣ
Μόνογιαεξουσιοδοτημένοτεχνικό.προσωπικό
MANUAL DE INSTALAÇÃO
Apenas para técnicos autorizados.
РУКОВОДСТВОПОУСТАНОВКЕ
Толькодля авторизованного обслуживающего.персонала
Yalnızca yetkili servis personeli için.
权的维修
MONTAJ KILAVUZU
[Original instructions]

Beoordeel deze handleiding

4.1/5 (9 Beoordelingen)

Product specificaties

Merk: Fujitsu
Categorie: Airco
Model: Airstage AJYA72LALH

Foutcodes Fujitsu Airstage AJYA72LALH

Foutcodes uit de officiële handleiding, met betekenis en oplossing.

Code Betekenis Oplossing
E113.1 Communication error between outdoor units Check communication cables and connections between units
E114.1 Outdoor unit network communication 1 error Check network communication cables and settings
E114.2 Outdoor unit network communication 2 error Check network communication cables and settings
E114.5 The number of indoor unit shortage Check indoor unit connections and quantity
E128.1 Auto address setting error Retry auto address setting procedure
E128.4 Signal amplifier auto address error Check signal amplifier and retry address setting
E15U.1 Indoor unit miscellaneous error Check indoor unit for general errors
E161.5 Outdoor unit reverse/missing phase & wiring error Check electrical phase and wiring connections
E162.3 Outdoor unit EEPROM access error Check EEPROM and electronic components
E162.6 Outdoor unit inverters communication error Check inverter communication connections
E162.8 Outdoor unit EEPROM data corruption error Check and replace EEPROM if necessary
E163.1 Outdoor unit inverter error Check inverter operation and power supply
E167.2 Outdoor unit inverter PCB power short interruption Check inverter PCB for shorts and power supply
E168.1 Outdoor unit magnetic relay error Check magnetic relay operation
E168.2 Outdoor unit rush current limiting resister temp. rise error (protective operation) Check rush current limiting resistor and cooling
E169.1 Outdoor unit transmission PCB parallel communication error Check PCB communication connections
E171.1 Outdoor unit discharge temp. thermistor 1 error Check and replace discharge temperature thermistor 1
E171.2 Outdoor unit discharge temp. thermistor 2 error Check and replace discharge temperature thermistor 2
E172.1 Outdoor unit compressor temp. thermistor 1 error Check and replace compressor temperature thermistor 1
E172.2 Outdoor unit compressor temp. thermistor 2 error Check and replace compressor temperature thermistor 2
E173.3 Outdoor unit heat ex. liquid temp. thermistor error Check and replace heat exchanger liquid temperature thermistor
E174.1 Outside air temp. thermistor error Check and replace outside air temperature thermistor
E175.1 Outdoor unit suction gas temp. thermistor error Check and replace suction gas temperature thermistor
E177.1 Outdoor unit heat sink temp. thermistor error Check and replace heat sink temperature thermistor
E182.1 Outdoor unit sub-cool heat ex. gas inlet temp. thermistor error Check and replace gas inlet temperature thermistor
E182.2 Outdoor unit sub-cool heat ex. gas outlet temp. thermistor error Check and replace gas outlet temperature thermistor
E183.1 Outdoor unit liquid pipe temp. thermistor 1 error Check and replace liquid pipe temperature thermistor 1
E183.2 Outdoor unit liquid pipe temp. thermistor 2 error Check and replace liquid pipe temperature thermistor 2
E184.1 Outdoor unit current sensor 1 error (permanent stop) Check and replace current sensor 1
E186.1 Outdoor unit discharge pressure sensor error Check and replace discharge pressure sensor
E186.3 Outdoor unit suction pressure sensor error Check and replace suction pressure sensor
E186.4 Outdoor unit high pressure switch 1 error Check and replace high pressure switch 1
E186.5 Outdoor unit high pressure switch 2 error Check and replace high pressure switch 2
E913.1 Outdoor unit compressor 2 error Check outdoor unit compressor 2 operation
E913.2 Outdoor unit compressor 2 current value error Check compressor 2 current values
E913.3 Outdoor unit inverter compressor start up error Check inverter and compressor startup sequence
E914.1 Outdoor unit trip detection Check outdoor unit for trip conditions
E915.5 Outdoor unit compressor motor loss of synchronization error Check motor synchronization and electrical connections
E917.1 Outdoor unit fan motor 1 lock error Check fan motor 1 for obstructions or mechanical damage
E917.4 Outdoor unit fan motor 1 undervoltage error Check power supply voltage to fan motor 1
E917.5 Outdoor unit fan motor 1 temperature error (protective action) Allow unit to cool, check fan motor temperature sensor
E91U.2 Outdoor slave unit error Check outdoor slave unit communication and operation
E9A1.1 Outdoor unit discharge temperature 1 error (permanent stop) Check discharge temperature thermistor and refrigerant system
E9A2.1 Outdoor unit discharge temperature 2 error (permanent stop) Check discharge temperature thermistor and refrigerant system
E9A3.1 Outdoor unit compressor 1 temperature error Check compressor 1 temperature sensor
E9A3.2 Outdoor unit compressor 2 temperature error Check compressor 2 temperature sensor
E9A4.1 Outdoor unit high pressure error Check refrigerant charge and high pressure system
E9A4.2 Outdoor unit high pressure protective action 1 Check refrigerant charge and system pressure
E9A4.3 Outdoor unit high pressure protective action 2 Check refrigerant charge and system pressure
E9A5.1 Outdoor unit low pressure error Check refrigerant charge and low pressure system