FSP/Fortron AS-400 Handleiding


Lees hieronder de đź“– handleiding in het Nederlandse voor FSP/Fortron AS-400 (2 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 17 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
1. Product Outlook
DB-9 port 9-pin port
Top View Side View Top View Side View
2. Product Introduction
The AS400 communication card provides contact closures for remote monitoring your UPS. To
meet different application requirement, the AS400 card is capable of selection the status of the
dry-contact signal (active close or active open) by setting jumper. The suitable applications are
listed below:
z IBM Server, Personal PC & Workstations equipments
z Auto-controlled industrial equipment & communication applications
3. Installation
Step 1: Remove cover of Intelligent Slot
on the rear panel of the UPS.
Step 2: Insert AS400 card into Intelligent
Slot.
Step 3: The cover of AS400 should
attach close to the rear panel. Using
screwdriver, secure the AS400 to the
UPS chassis with 2 screws.
Step 4: Use the 9-pin communication cable
to connect UPS and equipment to implement
the remote monitoring and control.
4 Specifications .
Internal circuit of DB-9 port
RS-232 port 9-pin port
Electric Parameter of DB-9 port
Symbol
Max.
Min.
Unit
Resistor*
DC Current
IR
6
1
mA
Diode
Reverse Voltage
V R
6
-
V
Forward Current
I F
50
-
mA
Peak Forward Current
I F (Peak)
1
-
A
Relay
DC Voltage
V DC
24
-
V
DC Current
I DC
1.0
-
A
Note: It’s required to retain the DC current lower than 6mA. Otherwise, it’s necessary to add one resistor
within DC current limitation in the serial loop of Remote Shutdown. (e.g. 2K resistor with at least 0.1W
rating power). Refer to diagrams in .Application
Pin Assignment
Pin Assignment
Function
I/O
Pin 1
UPS Failure
O/P
Pin 2
UPS Audible Alarm
O/P
Pin 3
GND (Common for Pin 4)
Power Ground
Pin 4
On/Off
I/P
Pin 5
Common for Relays
Power Supply
Pin 6
Bypass Active
O/P
Pin 7
Low Battery
O/P
Pin 8
UPS On
O/P
Pin 9
Utility Failure
O/P
P.S. The ON/OFF function pin (pin4 & pin3) accepts more than 2s high level signal to perform UPS on and
off actions.
Function Description
AC Status
AO Status
Reason
Pin 1 & Pin 5 connected
Pin 1 & Pin 5 disconnected
UPS failure
Pin 2 & Pin 5 connected
Pin 2 & Pin 5 disconnected
UPS failure, utility failure, low
battery, bypass active
Pin 6 & Pin 5 connected
Pin 6 & Pin 5 disconnected
Bypass active
Pin 7 & Pin 5 connected
Pin 7 & Pin 5 disconnected
Battery voltage is low
Pin 8 & Pin 5 connected
Pin 8 & Pin 5 disconnected
UPS is in inverter mode
Pin 9 & Pin 5 connected
Pin 9 & Pin 5 disconnected
Utility failure
AS-400 Card Remote On/Off Quick Guide V. 3.0
9 pin com. cable
Application:
Below shows the circuit of basic application to implement monitoring and control.
User Interface for 12 V User Interface for 24 V
5. Internal Logical Connection
IC controller of the card controls actions of 5 relays depending on the UPS status.
Active-Close(A.C) terminal and Active-Open(A.O) terminal of each relay connect to pin 3 and pin
1 of a 3-pin connector respectively. The pin 2 of the 3-pin connector connects to the signal pin of
the DB9 interface connector. The 2-pin jumper can be plugged to the 3-pin connector to either
short-circuit Pin1 & Pin2( or short-circuit Pin3 & Pin2( A.C) A.O).
Fig 1 Pin definition and internal logical connection
Accordingly, if pin1 short-circuits with pin2 via the jumper, the status of dry contact signal will be
ACTIVE CLOSE, refer to Fig 2. When the signal is active, the signal pin on the DB9 connector will
connect with the common pin (pin5) via the relay.
Fig 2 Connection for ACTIVE CLOSE
If Pin3 short-circuit with Pin2(A.O) via the jumper, the status of dry contact sign will be al
ACTIVE OPEN, refer to Fig 3. When the signal is active, the signal pin on the DB9 connector will
disconnect with the common pin (pin5) via the relay.
Fig. 3 Connection for ACTIVE OPEN
6 Jumper Set- up
The 3-pin connectors can be easily found
just near to the relay. Refer to Fig. 4.
There are AC O white silk printings of and A
the connector as shown in Fig. 5 to indicate
pin1&2 in pin2&3 in . A.C and A.O
Fig.4 AS400 card
Fig. 5 AO and AC silk printings
indicates each 3-pin connector status
To achieve ACTIVE CLOSE dry- tact con
signal, the jumper should connect the 2
pins(Pin1&2) as shown in Fig. 6.
To achieve ACTIVE OPEN dry-contact signal,
the jumper should connect the middle pin
and the pin3 as shown in Fig. 7
Fig. 6 Jumper setting for ACTIVE
CLOSE
Fig. 7 Jumper setting for ACTIVE
OPEN
Jumper function description
JP
Description
JP
Description
1
UPS alarm (DB9.P2)
4
Low battery(DB9.P7)
2
UPS on(DB9.P8)
5
Utility failure(DB9.P9)
3
Bypass(DB9.P6)
6
UPS failure(DB9.P1)


Product specificaties

Merk: FSP/Fortron
Categorie: Niet gecategoriseerd
Model: AS-400
Kleur van het product: Black, Green
Stroom: 1 A
Ingangsspanning: 24 V
Hostinterface: 9-pin
Soort aansluiting: RS-232
Type product: Relaiskaart

Heb je hulp nodig?

Als je hulp nodig hebt met FSP/Fortron AS-400 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd FSP/Fortron

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd