Bekijk gratis de handleiding van FSP/Fortron AS-400 (2 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 324 mensen en kreeg gemiddeld 4.6 sterren uit 5 reviews. Heb je een vraag over FSP/Fortron AS-400 of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/2

1.Product Outlook
DB-9 port 9-pin port
Top View Side View Top View Side View
2. Product Introduction
The AS400 communication card provides contact closures for remote monitoring your UPS. To
meet different application requirement, the AS400 card is capable of selection the status of the
dry-contact signal (active close or active open) by setting jumper. The suitable applications are
listed below:
zIBM Server, Personal PC & Workstations equipments
zAuto-controlled industrial equipment & communication applications
3. Installation
Step 1: Remove cover of Intelligent Slot
on the rear panel of the UPS.
Step 2: Insert AS400 card into Intelligent
Slot.
Step 3: The cover of AS400 should
attach close to the rear panel. Using
screwdriver, secure the AS400 to the
UPS chassis with 2 screws.
Step 4: Use the 9-pin communication cable
to connect UPS and equipment to implement
the remote monitoring and control.
4Specifications .
Internal circuit of DB-9 port
RS-232 port 9-pin port
Electric Parameter of DB-9 port
Parameter
Symbol
Max.
Min.
Unit
Resistor*
DC Current
IR
6
1
mA
Diode
Reverse Voltage
V R
6
-
V
Forward Current
I F
50
-
mA
Peak Forward Current
I F (Peak)
1
-
A
Relay
DC Voltage
V DC
24
-
V
DC Current
I DC
1.0
-
A
Note: It’s required to retain the DC current lower than 6mA. Otherwise, it’s necessary to add one resistor
within DC current limitation in the serial loop of Remote Shutdown. (e.g. 2K resistor with at least 0.1W
rating power). Refer to diagrams in .Application
Pin Assignment
Pin Assignment
Function
I/O
Pin 1
UPS Failure
O/P
Pin 2
UPS Audible Alarm
O/P
Pin 3
GND (Common for Pin 4)
Power Ground
Pin 4
On/Off
I/P
Pin 5
Common for Relays
Power Supply
Pin 6
Bypass Active
O/P
Pin 7
Low Battery
O/P
Pin 8
UPS On
O/P
Pin 9
Utility Failure
O/P
P.S. The ON/OFF function pin (pin4 & pin3) accepts more than 2s high level signal to perform UPS on and
off actions.
Function Description
AC Status
AO Status
Reason
Pin 1 & Pin 5 connected
Pin 1 & Pin 5 disconnected
UPS failure
Pin 2 & Pin 5 connected
Pin 2 & Pin 5 disconnected
UPS failure, utility failure, low
battery, bypass active
Pin 6 & Pin 5 connected
Pin 6 & Pin 5 disconnected
Bypass active
Pin 7 & Pin 5 connected
Pin 7 & Pin 5 disconnected
Battery voltage is low
Pin 8 & Pin 5 connected
Pin 8 & Pin 5 disconnected
UPS is in inverter mode
Pin 9 & Pin 5 connected
Pin 9 & Pin 5 disconnected
Utility failure
AS-400 Card Remote On/Off Quick Guide V. 3.0
9 pin com. cable
Product specificaties
| Merk: | FSP/Fortron |
| Categorie: | Niet gecategoriseerd |
| Model: | AS-400 |
| Kleur van het product: | Black, Green |
| Stroom: | 1 A |
| Ingangsspanning: | 24 V |
| Hostinterface: | 9-pin |
| Soort aansluiting: | RS-232 |
| Type product: | Relaiskaart |
Heb je hulp nodig?
Als je hulp nodig hebt met FSP/Fortron AS-400 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd FSP/Fortron
25 Augustus 2025
21 Maart 2024
Handleiding Niet gecategoriseerd
Nieuwste handleidingen voor Niet gecategoriseerd
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026