Bekijk gratis de handleiding van Festo VZXA (6 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 59 mensen en kreeg gemiddeld 4.7 sterren uit 4 reviews. Heb je een vraag over Festo VZXA of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/6

Translation of the original instructions
© 2020 all rights reserved to Festo SE & Co. KG
1About this document
This document describes the use of the above-mentioned product. It contains
additional information for use of the product in safety-related systems (safety
handbook in accordance with IEC61508).
1.1Applicable Documents
All available documents for the product www.festo.com/sp.è
1.2Specified standards
Version
IEC61508:2010 Part 1,2,4…7IEC61511:2016
Tab. 1 Standards specified in the document
2Safety
2.1General safety instructions
–Only use the product in original status without unauthorised modifications.
–Only use the product if it is in perfect technical condition.
–Use the valve only in the flow direction indicated.
–Take into consideration the ambient conditions at the location of use.
Media
–Only use media in accordance with the specifications 16 Technical data.è
–Use only media that will not cause dangerous reactions if mixed.
–Do not operate the product with chemically unstable gases, abrasive mediaor
solid materials.
–If water is used: up to approx.1000 ppm of chloride content is permitted.
Avoid tensile stresses.
–If aggressive media are used: limit temperature of medium to 65°C.
Actuator
–Do not open the actuator (pressure in the actuator or loaded spring).
–Avoid mechanical stresses on the valve. Do not use the actuator as a lever.
Return to Festo
Hazardous substances can endanger the health and safety of personnel and
cause damage to the environment. To prevent hazards, the product should only
be returned upon explicit request by Festo.
–Consult your regional Festo contact.
–Complete the declaration of contamination and attach it to the outside of the
packaging.
–Comply with all legal requirements for the handling of hazardous substances
and the transport of dangerous goods.
2.2Intended use
The angle seat valve VZXA-...-K is intended to shut-off gaseous or liquid media in
piping systems.
–To control liquid media, use only the product variant VZXA-B-... Use (media
flow under valve seat).
2.3Training of qualified personnel
Work on the product should only be conducted by qualified personnel. The quali-
fied personnel must be familiar with installation of process automation systems.
3Information on functional safety
3.1Operating conditions
–General information on safe operation 2 Safety.è
–Periodic tests (performance test) 11 Maintenance.è
–Ambient conditions and additional technical specifications
è 16 Technical data.
3.2Achievable safety rating
The product is suitable for use as an element in a safety-related system in accord-
ance with IEC 61511.
–In low-demand mode up to SIL 2
–In high-demand mode up to SIL 2.
Taking into account the necessary minimum hardware fault tolerance of HFT = 1,
the product can also be used up to SIL 3 with a redundant execution of the entire
system.
NOTICE!
It is only possible to determine whether the product is suitable for specific applic-
ations by also assessing further components of the subsystem.
3.3Safety function
Single-acting valves
The safety function comprises acceptance of the initial position on request. The
request is implemented by removal of the operating pressure.
–Valves with NO control function: the valve opens completely and remains
open until operating pressure is applied.
–Valves with NC control function: the valve closes completely and remains
closed until operating pressure is applied.
Double-acting valves
The safety function comprises acceptance of the required position on request.
This requires an external power supply.
3.4Characteristic values
Safety standards (in accordance with IEC 61508)Value
Assessment path (Route of assessment)2
H
/1
S
Type of subsystem (Type of Sub System)Type A
Mode of operation (Mode of Operation)Low Demand and
High Demand
Test interval (Assumed Test Interval)T
i
1 a
Confidence level (Confidence Level)1- 95%á
Hardware fault tolerance (Hardware Fault Tolerance)HFT0
Failure rate for dangerous errors (Lambda Dangerous)ë
D
1.36 * 10
-7
/h
Failure rate for dangerous errors not detected (Lambda Dan-
gerous Undetected)
ë
DU
1.36 * 10
-7
/h
Mean time to dangerous failure (Mean Time To Dangerous Fail-
ure)
MTTF
D
7.37 * 10
6
h
Degree of detection of dangerous errors by the proof test
(Proof Test Coverage)
PTC95%
Low Demand Mode
Assumed demands per year (Assumed Demands per Year)n
op
1/a
Mean probability of dangerous failure on demand (Average
Probability of Failure on Demand)
PFD
avg
5.95 * 10
-4
High Demand Mode
Assumed demands per year (Assumed Demands per Year)n
op
1/h
(8760/a)
Mean frequency of a dangerous failure per hour (Probability of
dangerous Failure per Hour)
PFH1.36 * 10
-7
/h
Tab. 2 Safety standards (in accordance with IEC 61508)
4Further information
–Accessories www.festo.com/catalogue.è
–Spare parts www.festo.com/spareparts.è
5Service
Contact your regional Festo contact person if you have technical questions
èwww.festo.com.
8130883
VZXA-...-V13/V14-...-K-...-V4
Angle seat valve with piston actuator
8130883
2020-07c
[8130885]
Operating instructions
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
Product specificaties
| Merk: | Festo |
| Categorie: | Niet gecategoriseerd |
| Model: | VZXA |
Heb je hulp nodig?
Als je hulp nodig hebt met Festo VZXA stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Festo
2 Augustus 2025
2 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
Handleiding Niet gecategoriseerd
Nieuwste handleidingen voor Niet gecategoriseerd
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026