Eltako WSZ15DE-32A Handleiding

Eltako Meetapparatuur WSZ15DE-32A

Lees hieronder de 📖 handleiding in het Nederlandse voor Eltako WSZ15DE-32A (1 pagina's) in de categorie Meetapparatuur. Deze handleiding was nuttig voor 48 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/1
Single-phase energy meter
WSZ15DE-32A without MID
GB
Temperature at mounting location:
-20°C up to +55°C.
Storage temperature: -25°C up to +70°C.
Relative humidity:
annual average value <75%.
28 032 615 - 1
Only skilled electricians may install this
electrical equipment otherwise there is
the risk of re or electric shock!
Maximum current 32 A. Standby loss 0.4 watt
only.
Modular device for DIN-EN 60715 TH35 rail
mounting. 1 module = 18mm wide and 58mm
deep.
Accuracy class B (1%). With S0 interface.
This single-phase energy meter measures
active energy by means of the current between
input and output. The internal power con-
sumption of 0.4 watt active power is neither
metered nor indicated. Like all meters without
declaration of conformity (e.g. MID), this meter
is not permitted for billing.
Every 30 seconds, the display switches for
5 seconds from the accumulated active energy
in kWh to the momentary consumption in
watts.
1 phase conductor with a max. current up to
32 A can be connected.
If the anticipated load exceeds 50%, main-
tain an air gap of ½ pitch unit to the devices
mounted adjacently.
If necessary, use spacer DS12.
The inrush current is 20 mA.
The display can only be read when the power
supply is on. However, the consumption is
saved to a non-volatile memory and is dis-
played immediately after power restoration.
Two N terminals for secure cross wiring of
several counters.
The digital display has 7 digits. Two decimal
places are indicated up to 99999.99 kWh.
Above 100000.0 kWh there is only one decimal
place.
Power consumption is shown by a bar ashing
at a rate of 1000 times per kWh.
Error message
In case of a wrong connection, a LED is blinking
on the display.
Typical connection
Technical data
Rated voltage 230 V, 50 Hz,
Extended range -2O%/+15%
Reference current
I
ref 5 (32) A
(Limiting current
I
max)
Internal consumption 0.4 W
Active power
Display active power LC display
7 digits,therefrom
1 or 2 digits after
the decimal point
Accuracy class ±1% B
Inrush current according 2O mA
to accuracy class B
Operating temperature -25/+55°C
Interface potential free by opto-coupler,
max. 30 V DC/2O mA
and min. 5 V DC,
pulse interface S0 according
to DIN EN 62053-31,
impedance 100 ohms,
pulse length 30 ms,
2000 Imp./kWh
Must be kept for later use!
We recommend the housing for
operating instructions GBA14.
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025
technical-support@eltako.de
eltako.com
50/2020 Subject to change without notice.
Protection degree lP50 for mounting
in distribution
cabines with
protection class IP51
Maximum L terminals 16 mm2
conductor N and SO terminals
cross section
1) 6 mm2
Recommended torque 2)
L terminals 1,5 Nm
(max. 2,0 Nm)
N and S0 terminals 0,8 Nm
(max. 1,2 Nm)
Mechanical class M1
environmental conditions
Electromagnetic class E2
environmental conditions
1) The carrying capacity of cables and wires is dened in
DIN VDE 0298-4.
2)
The torques for screw terminals are mentioned in DIN
EN 60999-1.
To avoid damages at the energy meter, the recom-
mended torque values for each terminal must not be
exceeded!


Product specificaties

Merk: Eltako
Categorie: Meetapparatuur
Model: WSZ15DE-32A

Heb je hulp nodig?

Als je hulp nodig hebt met Eltako WSZ15DE-32A stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Meetapparatuur Eltako

Handleiding Meetapparatuur

Nieuwste handleidingen voor Meetapparatuur