Eaton 9SXEBM240 Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Eaton 9SXEBM240 (44 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 37 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/44
ENGLISH
9SX 8000
9SX 11000
9PX 8000
9PX 11000
9SX EBM 240V
9PX EBM 240V
Installation
and user manual
Copyright © 2013 EATON
All rights reserved.
Service and support:
Call your local service representative
8-11kVA EU_EN
Page 2 8-11kVA EU_EN
SAVE THESE INSTRUCTIONS. This manual contains important instructions
that should be followed during installation and maintenance of the UPS and batteries.
The 9SX and 9PX models that are covered in this manual are intended for installation
in an environment within 0 to 40°C, free of conductive contaminant.
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of
this equipment in a residential area is likely to cause harmful interference in which case the user will
be required to correct the interference at his own expense.
Certication standards
• Safety: IEC/EN 62040-1 / Ed.1: 2008.
UL 1778 4th edition
• EMC: IEC/EN 62040-2 / Ed.2: 2006.
FCC part 15 Class A.
• Performance: IEC/EN 62040-3 / Ed.2.0: 2011.
• IEC 61000-4-2 (ESD): level 3.
• IEC 61000-4-3 (Radiated eld): level 3.
• IEC 61000-4-4 (EFT): level 4.
• IEC 61000-4-5 (Fast transients): level 4.
• IEC 61000-4-6 (Electromagnetic eld): level 3.
• IEC 61000-4-8 (Conducted magnetic eld): level 4.
Special symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
Important instructions that must always be followed.
Do not discard the UPS or the UPS batteries in the trash.
This product contains sealed lead acid batteries and must be disposed as it's explain in this manual.
For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE)
in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Information, advice, help.
Refer to the user manual of UPS accessories.
SAFETY INSTRUCTIONS
Page 3
8-11kVA EU_EN
ENGLISH
SAFETY INSTRUCTIONS
Safety of persons
• RISK OF VOLTAGE BACKFEED. The system has its own power source (the battery). Isolate the UPS
and check for hazardous voltage upstream and downstream during lockout-tagout operation. Termi-
nal blocks may be energized even if the system is disconnected from the AC power source.
• Dangerous voltage levels are present within the system. It should be opened exclusively by quali-
ed service personnel.
• The system must be properly grounded.
• The battery supplied with the system contains small amounts of toxic materials.
To avoid accidents, the directives listed below must be observed:
- Servicing of batteries should be performed or supervised by personnel knowledgeable about
batteries and the required precautions.
- When replacing batteries, replace with the same type and number of batteries or battery packs.
- Do not dispose of batteries in a re. The batteries may explode.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
• Precautions must be taken for all handling:
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
- Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if such grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded supply circuit).
Product safety
• The UPS connection instructions and operation described in the manual must be followed in
the indicated order.
• CAUTION - To reduce the risk of re, the unit connects only to a circuit provided with branch circuit
overcurrent protection for :
- 50A rating, for 8kVA models,
- 70A rating, for 11kVA models in accordance with the National Electric Code, ANSI/NFPA 70
(US installations only),
The upstream circuit breaker for Normal AC/Bypass AC must be easily accessible. The unit can be
disconnected from AC power source by opening this circuit breaker. This circuit breaker is used for
backfeed protection and must comply with IEC/EN 62040-1 (the creepage and clearance distances
shall meet the basic insulation requirements for pollution degree 2).
• Disconnection and overcurrent protection devices shall be provided by others for permanently
connected AC input (Normal AC/Bypass AC) and AC output circuits.
• Check that the indications on the rating plate correspond to your AC powered system and
to the actual electrical consumption of all the equipment to be connected to the system.
• For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall
be easily accessible
• Never install the system near liquids or in an excessively damp environment.
• Never let a foreign body penetrate inside the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The admissible storage temperature range is -15ºC to +50ºC.
• The system is not for use in a computer room AS DEFINED IN the standard for the Protection
of Information Technology Equipment, ANSI/NFPA 75 (US installations only).
Contact Eaton resellers to order a special battery kit, if needed to meet the ANSI/NFPA 75
requirement.


Product specificaties

Merk: Eaton
Categorie: Niet gecategoriseerd
Model: 9SXEBM240
Kleur van het product: Zwart
Gewicht: 68000 g
Breedte: 130 mm
Diepte: 440 mm
Hoogte: 645 mm
Vormfactor: Rackmontage/toren
Accu/Batterij voltage: 12 V
Ondersteund aantal accu's/batterijen: 20
Batterij capaciteit: 7 Ah
Rack-montage: Ja
Rackcapaciteit: 3U

Heb je hulp nodig?

Als je hulp nodig hebt met Eaton 9SXEBM240 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Eaton

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd