Bekijk gratis de handleiding van Eastron Smart X96-1A-MT (27 pagina’s), behorend tot de categorie Meetapparatuur. Deze gids werd als nuttig beoordeeld door 4 mensen en kreeg gemiddeld 4.7 sterren uit 2.5 reviews. Heb je een vraag over Eastron Smart X96-1A-MT of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/27
EASTRON SMART X96-1A-MT User Manual V1.0
SMART X96-1A-MT
Smart Energy Analyzer for Single and Three Phase Electrical Systems
Measures kWh, kVarh, kW, kVar, kVA, P,
F, PF, Hz, dmd, V, A, etc.
Bi-directional Measurement IMP & EXP
Energy Information of Each Phase
Two Pulse Outputs
RS485 Modbus RTU
Total Harmonic Distortion of Voltage and Current
2nd~63rd Individual Harmonic Distortion
Backlit LCD Display for Full Viewing Angles
Class 1 , Class 0.5S
Bar Graph for Power Indication
Dimension 96x96mm
MultI-tariff
RJ-12 333mV or 100mA CT input
EASTRON SMART X96-1A-MT User Manual V1.0
Introduction
The multifunction energy analyzer SMART X96 series is a top new-generation intelligent panel meter, used not only in the
electricity transmission and power distribution system, but also in the power consumption measurement and analysis in
high voltage intelligent power grid.
This document provides operating, maintenance and installation instructions for the Eastron SMART X96 series. The unit
measures and displays the characteristics of single phase two wire, three phase three wire and three phase four wire supplies,
including voltage, frequency, current, power and active and reactive energy, imported or exported, Harmonic, Power factor,
Max. Demand etc. Energy is measured in terms of kWh, kVArh. Maximum demand current can be measured over preset
periods of up to 60 minutes. In order to measure energy, the unit requires voltage and current inputs for the supply required
to power the product. The requisite current input(s) are obtained via current transformers The SMART X96 can be configured
to work with a wide range of CTs, giving the unit a wide range of operation. Built-in interfaces provide pulse and RS485
Modbus RTU outputs. Configuration is password protected.
1. Unit Characteristics
1. 1 The Unit can measure and display:
Line voltage and THD% (total harmonic distortion) of all phases
2~63rd voltage IHD% (Individual Harmonic distortion) of all phases
Line Frequency
Phase Sequence
Currents, Current demands and current THD% of all phases
2~63rd current IHD% of all phases
Active power, reactive power, apparent power, maximum power demand and power factor
Active energy imported and exported
Reactive energy imported and exported
Energy of each phase
Multi Tariff active energy
1.2 The unit has password-protected set-up screens for:
Communication setting: Modbus address, Baud rate, Parity, Stop bit
CT setting: CT 1 ( Primary)
PT setting: PT1 (Primary)
Pulse setting: Pulse output 1, Pulse rate, Pulse time
Demand setting: Demand interval time, demand method
Time setting: Backlit time, display scroll time
System configuration: System type, System connect, Change password, Auto display scroll
Reset
1.3 CT and PT
CT1 (primary current)5~9999A
CT2 (secondary current): 100mA
PT1 (primary voltage): 100V ~ 500,000V
PT2 (secondary voltage): 100 to 480 V AC (L-L)