Bekijk gratis de handleiding van Dormakaba RCI 0162 (2 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 220 mensen en kreeg gemiddeld 4.3 sterren uit 110.5 reviews. Heb je een vraag over Dormakaba RCI 0162 of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/2

Fail Secure = Fail Locked = FL AC = Alternating Current DC = Direct Current
Intermittent Duty = Energized less than 1 minute with 1:5 duty ratio Continuous Duty = Energized 1 minute or more
I N S T A L L A T I O N F0162 / 0162
F0162LM / 0162LM
IS0162 PCN18003
R02-18TG-1
Important: The F0162 or the 0162 Electric Strikes should never be used as a door stop. Please install stops on frame in
appropriate locations. Ensure the exit device functions as intended for life safety concerns by verifying electric strike and
exit device compatibility. Maximum latch projection is essential to obtain full holding force.
When installed in a fail secure manner, the local Authority Having Jurisdiction shall be consulted with regard to the use
of selected panic hardware to ensure emergency exit from the secured area.
Installations of this RIM strike qualify as “Indoor Use Only” when not continuously exposed to an outdoor environment.
Catalog Specifications
MODE VOLTAGE CURRENT DUTY AMPS OHMS
Fail Secure 12V AC Intermittent 0.33 22
Fail Secure 12V DC Continuous 0.50 22
Fail Secure 24V AC Intermittent 0.64 22
Fail Secure 24V DC Continuous 0.24 89
Fail Secure 11-16V AC Intermittent 0.32-0.50 22
1-3/4”
(44.5mm)
3/4”
(19.0mm)
9”
(228.6mm)
5-1/2”
(139.7mm)
1-5/8”
(42.0mm)
8-1/4”
(209.6mm)
HORIZONTAL
ADJUSTMENT
MOUNTING
HOLES
MODEL WITH
LATCH MONIT
OR
LOCK DOWN
HOLES
SURFACE MOUNTED RIM STRIKE
(FIRE RATED AND NON-FIRE RATED)
Electrical Latch Monitor
Specification:
• 12VDC, 1A, resistive load
Note: Contacts identified on the
harness sleeve are indicated with the
keeper in a closed and locked condition,
with no latch present
Dimensional Details
UL 294 Performance Ratings:
Access Control Line Security : Level I
Destructive Attack : Level I
Endurance : Level IV
Standby Power : Level I
© 2018 dormakaba Canada Inc.
www.rutherfordcontrols.com hone ax • P : 1.800.265.6630 • F : 1.800.482.9795 • Email: sales_RCI@dormakaba.com

LOCKING SCREW
(2 PLACES)
3/4" (19.0 mm)
WIRE ACCE
SS HOLE
1/4-20 UNC
(2 PLACES)
DOOR FRAME
DOOR FRAME STOP
MOUNTING SCREW
(2 PLACES)
MOUNTING SCREW
(2 PLACES)
1/4-20 UNC
(2 PLACES)
3/4" (19.0 mm)
WIRE ACCE HOLESS
DOOR FRAME STOP
5/8" (16.0mm)*
WIRE ACCE
SS HOLE
LM MODEL ONLY 5/8" (16.0mm)*
LM MODEL ONLY
NOTE: NOTE: * Wire access hole locations are relative to the exit device orientation. Second wire access hole required for 0162LM only
NOTE: Not to scale. Specifications are subject to change without notice.
Instructions
1. Determine the horizontal centerline of the exit device latch and transfer centerline to the frame stop.
2. Position the template onto the frame aligning with centerline and against the closed door. Center-punch the two
mounting holes and the wire access hole as shown.
3. Drill and tap the two mounting holes and drill the wire access hole(s).
4. Test fit electric strike to ensure full latch engagement. Add provided spacer if required.
5. Make wire connections from the power source to the appropriate wire harness supplied. Use 12VDC wire harness for
12VDC, 12-24VAC or 11-16VAC input power. Use 24VDC wire harness for 24VDC input power only.
NOTE: Overheated or burnt coils caused by incorrect input voltage / wire harness combinations will not be
covered under warranty
6. Connect monitor wires of LM model.
7. Mount the electric strike with 1/4-20 UNC screws provided in the horizontal mounting holes (the outer slots).
Adjust electric strike horizontally until exit device latch fully engages with the door closed.
NOTE: Ensure a 1/16” [1.5mm] clearance between
exit device latch and the electric strike keeper is
maintained. Failing to do so will preload the strike
and in turn will not allow the strike to release the
door upon energizing.
WARNING: For proper operation, a 3/16” gap
(minimum) is required.
8. Tighten the two mounting screws and check operation.
Adjust the horizontal position of electric strike as required.
9. Use the electric strike as a template to mark the two locking holes. Remove strike. Drill & tap for 1/4-20 UNC locking
screws. Using the 1/4-20 UNC screws provided secure the electric strike through the locking holes.
RIM ELECTRIC STRIKE
EXIT DEVICE LATCH
DOOR FRAME
STRIKE KEEPER
3/16”
MINIMUM
1/16” minimum
© 2018 dormakaba Canada Inc.
www.rutherfordcontrols.com hone ax • P : 1.800.265.6630 • F : 1.800.482.9795 • Email: sales_RCI@dormakaba.com
Product specificaties
Merk: | Dormakaba |
Categorie: | Niet gecategoriseerd |
Model: | RCI 0162 |
Heb je hulp nodig?
Als je hulp nodig hebt met Dormakaba RCI 0162 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Dormakaba
9 Juli 2023
9 Juli 2023
9 Juli 2023
9 Juli 2023
9 Juli 2023
9 Juli 2023
9 Juli 2023
9 Juli 2023
9 Juli 2023
9 Juli 2023
Handleiding Niet gecategoriseerd
- Sekonic
- Avital
- Bearware
- Bionaire
- Medeli
- SVAT
- Esdec
- AREXX
- Husky
- T.akustik
- Cascade Audio Engineering
- Lasita Maja
- NovaStar
- Dutchbone