Dormakaba 1856 HT SD Handleiding


Lees hieronder de đź“– handleiding in het Nederlandse voor Dormakaba 1856 HT SD (23 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 18 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/23
1856 HT SD, 1856 SFT SD
Surface applied door closer
HT (stnd track) < 2” frame face with smoke detector
SFT (swing free track) < 2” frame face with smoke detector
Installation instructions
08220880 – 03-2020
| | EN
21800 Closer 03-202008220880
dormakaba 1856 HT SD, 1856 SFT SD Installation Instructions Table of Contents
Table of contents
1  Technical specifications 3
1.1 Overview 3
1.2 Tools recommended 3
2 Installation instructions 4
2.1 Overall 4
2.2 Install track 5
2.3 Install closer (regular mount) 6
2.4 Install closer (<2” frame face mount) 6
2.5 Smoke detector attachment 6
2.6 Secure arm 7
2.7 Swing free track mount (SFT) 8
3 Adjustments 9
3.1 Adjust closing speeds: sweep, latch, backcheck,
delayed actions 9
3.2 Set the hold open 9
4 Wiring 10
4.1 Electrical specifications 10
4.2 Power supply 120 VAC, 50/60 HZ 11
4.3 Power supply 24 V AC/DC 11
4.4 Power supply 24 V AC/DC with
remote detectors 12
4.5 ON/OFF switch (optional) 12
4.6 Wire gauge 13
4.7 SD-2 detector to main solenoid connection 14
4.8 SD-2 detector to auxiliary solenoid connection 14
4.9 Solenoid attachment to UL/ULC listed
alarm control panel 14
4.10 SD-2 detector interconnection 15
4.11 SD-2 detector to remote area detector 16
4.12 SD-2 detector to audible signal appliance 16
4.13 SD-2 detector to remote alarm indicator lamp 17
4.14 Alarm initiation wiring 4 wire
style B (Class B) & 6 style D (Class A)* 17
5 Final set up 19
5.1 Detector sensitivity test (ULC required only) 19
5.2 Check connections 19
5.3 Engage hold open 19
5.4 Reset detector 19
6 Maintenance 20
6.1 Maintaining the detector 20
5.5 Unit testing 20
5.6 Install covers 20
6.2 Measure and record test voltage 21
6.3 Vacuum detector 21
6.4 Testing (continued) 22
dormakaba 1856 HT SD, 1856 SFT SD Installation Instructions
08220880 03-20201800 Closer 3
Technical specifications
1  Technical specifications
1.1 Overview
Each 1856 HT SD & 1856 SFT SD unit contains a
door closer, hold open solenoid and a smoke
detector .
The unit can be used as a single installation or as
a series of devices. When the units are wired
together in a run, up to 5 may be interconnected.
Interconnections are accomplished through
terminals #4 and #15 resulting in all alarming
when any one unit senses smoke. In turn, all
associated hold open solenoids are de-energized.
Within any run smoke detecting units it is
permissible to form as many interconnected
series as the total power supply amperage will
allow; but again no more than 5 can be
interconnected.
Any unit with a smoke detector can be connected
to a non-smoke detector unit, or a remote
detector, or both. It can be a single installation
or part of any of the multiple arrangements
described above. A non-smoke detector solenoid
is a slave to the main unit de-energizing when the
main does. Single or group installations can be
connected to the alarm initiation circuit of a
compatible UL/ULC listed fire alarm control 4 or
6 wire configuration panel.
Additional functions are provided to separately
power the hold open solenoids directly from the
alarm control panel or remotely from an alarm
indicator lamp.
ATTENTION!!! Read the entire instruction sheet
prior to installing and refer to NFPA 72E.
Standards may be obtained from THE NATIONAL
FIRE PROTECTION ASSOCIATION in
Batterymarch Park, Quincy, Massachusetts,
02169.
Please make sure you have the tools listed plus
make sure you have the correct model unit and
hand designation per your application.
CAUTION: Sex nuts are required for attachment
of components to unreinforced, wood or plastic
faced composite type fire doors, unless an
alternative method is identified in the individual
door manufacture’s listings. Make sure door
efficiently operates prior to installing the closer.
When Installing main arm attachment observe
directions closely. Confirm dead stop degree prior
to door and frame preparations.
1.2 Tools recommended
Drill bits: #2 Phillips screwdriver
No. 7 drill bit & drill or 13/64”
drill bit
3/16” slotted head screwdriver
1/4-20 tap & holder M5 hex key
1/2” box wrench #3 cross point screwdriver
10” adjustable wrench
Table 1


Product specificaties

Merk: Dormakaba
Categorie: Niet gecategoriseerd
Model: 1856 HT SD

Heb je hulp nodig?

Als je hulp nodig hebt met Dormakaba 1856 HT SD stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Dormakaba

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd