Bekijk gratis de handleiding van CyberPower RELAYIO500 (2 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 9 mensen en kreeg gemiddeld 4.3 sterren uit 3 reviews. Heb je een vraag over CyberPower RELAYIO500 of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/2

Rela
R
ay Control Card
RELAYIO500
User’s Manual
K01-0000416-01
Internal Circuit
RELAYIO500 Card Pinout
Pin
Assignment Function I/O
Pin1 UPS FAULT O/P
Pin2 SUMMARY ALARM O/P
Pin3 GND (Common for Pin4) Power GND
Pin4 REMOTE SHUTDOWN Power + Vcc
Pin5 COMMON (For Relays) O/P
Pin6 BYPASS
1
/ UPS OFF O/P
Pin7 BATTERY LOW O/P
Pin8 UPS ON O/P
Pin9 UTILITY LINE FAIL O/P
Note: All relay contacts are normally open (N.O.) except for Pin6.
Acceptable Power + Vcc for Pin4 is 7.5 – 12V, 0.0672W Max.
1
For OL series UPS models only
1
6
2
7
3
4
5
8
9
UPS FAULT
SUMMARY ALARM
GND (Common for Pin4)
REMOTE SHUTDOWN
COMMON (For Relays)
BYPASS1 / UPS OFF
BATTERY LOW
UPS ON
UTILITY LINE FAIL
GND
Overview
The CyberPower Relay Control Card (RELAYIO500) offers users the
solution for UPS status monitoring via 5 output relays. In addition, the
RELAYIO500 card provides 1 input contact to perform UPS shutdown in
battery mode. This card is compatible with most CyberPower UPS devices
with expansion slot.
Installation Guide
The RELAYIO500 card is hot-swappable and can be installed while the
UPS is on.
1. Remove the two retaining screws on the expansion slot cover, and then
remove the cover.
2. Install the CyberPower RELAYIO500 card into the expansion slot.
3. Re-install and tighten the retaining screws.
Technical Specifications
RELAYIO500
Electrical
External S/D Voltage 7.5V – 12V
Power Dissipation 1.35W Max
(Default 12V input)
Physical
Dimensions (WxHxD) 41.8 x 14.2 x 81mm
(1.65 x 0.6 x 3.2 in)
Weight 52g (1.92oz)
Environmental
Operating Temperature 0°C – 40°C (32°F - 104°F)
Operating Humidity 0% – 95% (Non-condensing)
Output Relay Rating
Maximum
Voltage Current
30VDC / 125VAC 3A (per relay)
Function Description
Status Condition
Pin1 short to Pin5
UPS fault (Inverter Fault / DC Bus Fault / Over
Temperature / Output Short / Battery Over Charge /
Battery Test Fail
1
/ Fan Error
1
)
Pin2 short to Pin5
Summary alarm (Inverter Fault / DC Bus Fault /
Output Short / Over Temperature / Over Load /
Battery Missing / Battery Over Charge / Battery Low /
Wiring Fault / Runtime Low
2
/ Battery Test Fail
1
/
Load Over Setting Level
1
/ Fan Error
1
)
Pin6 short to Pin5 UPS is OFF. / UPS is in Bypass Mode.
1
Pin7 short to Pin5 Battery Low
Pin8 short to Pin5 UPS is on.
Pin9 short to Pin5 Utility Line Fail
1
For OL series UPS models only
2
For PR/OR series UPS models only
Example Application
Supply 12VDC to the COMMON contact and connect LEDs to the DB-9
port pins 1, 2 and 6 to 9. Connect a push button to COMMON (Pin5) and
REMOTE SHUTDOWN (Pin4). Pressing the button for at least 5 seconds
will shutdown the UPS when it is on battery.
Note: When the UPS is on battery, the REMOTE SHUTDOWN input (Pin4
& Pin3) accepts at least 5 seconds of high level signal (+12VDC) to perform
the UPS shutdown. UPS output power will turn off after 120 seconds.
1
6
2
7
3
4
5
8
9
UPS FAULT
SUMMARY ALARM
GND (Common for Pin4)
REMOTE SHUTDOWN
COMMON (For Relays)
BYPASS1 / UPS OFF
BATTERY LOW
UPS ON
UTILITY LINE FAIL
12V
Product specificaties
| Merk: | CyberPower |
| Categorie: | Niet gecategoriseerd |
| Model: | RELAYIO500 |
| Gewicht: | 52 g |
| Breedte: | 41.8 mm |
| Diepte: | 81 mm |
| Hoogte: | 14.2 mm |
| Gewicht verpakking: | 160 g |
| Breedte verpakking: | 168 mm |
| Diepte verpakking: | 162 mm |
| Hoogte verpakking: | 58 mm |
| Certificering: | RoHS |
| Interface: | UPS |
| Duurzaamheidscertificaten: | RoHS |
| Plug and play: | Ja |
| Temperatuur bij opslag: | -10 - 50 °C |
| Intern: | Ja |
| Luchtvochtigheid bij opslag: | 0 - 95 procent |
| Compatibiliteit: | OR Series UPS systems, PR Series UPS systems, OL1000RTXL2U, OL1500RTXL2U, OL1500RTXL2UN, OL3000RTXL2UHV |
| Bedrijfstemperatuur (T-T): | 0 - 40 °C |
| Relatieve vochtigheid in bedrijf (V-V): | 0 - 90 procent |
| Code geharmoniseerd systeem (HS): | 84733020 |
| Aansluiting type: | D9 |
Heb je hulp nodig?
Als je hulp nodig hebt met CyberPower RELAYIO500 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd CyberPower
10 December 2025
10 December 2025
8 December 2025
29 November 2025
28 November 2025
28 November 2025
27 November 2025
30 September 2025
29 Juli 2025
29 Juli 2025
Handleiding Niet gecategoriseerd
Nieuwste handleidingen voor Niet gecategoriseerd
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
22 Januari 2026
22 Januari 2026
22 Januari 2026
22 Januari 2026