GENERAL
UPS Topology Line-Interactive
Energy Saving GreenPower UPS™ Bypass
Technology
ENERGY STAR® Qualified Yes
Active PFC Compatible Yes
INPUT
Voltage 100 - 125 Vac
Frequency 47 - 63 Hz
Input Voltage Range 70 - 155 Vac
Plug Type NEMA 5-15P
Plug Style Right Angle, 45° Oset Right
Cord Length 10 ft.
OUPUT
VA 750
Watts 750
Automatic Voltage
Regulation Double Boost, Single Buck
On Battery Voltage 100/110/120/125 Vac ± 5%
On Battery Frequency 50/60 Hz +/- 1%
On Battery Waveform Sine Wave
Outlets - Total 8
Outlet Type NEMA 5-15R
Outlets - Critical Load 4
Outlets - Battery
& Surge Protected 8
SPECIFICATIONS
The PR750RTXL2U is a New Smart App Sinewave rack/tower convertible
UPS with line-interactive topology, surge protection, and battery backup.
CyberPower’s New Smart App Sinewave series has sine wave output to
eliminate power gaps that can be detected by sensitive equipment and cause
unexpected shutdowns.
The New Smart App Sinewave PR750RTXL2U improves battery life through
battery equalization technology and Automatic Voltage Regulation (AVR),
which corrects minor power fluctuations without switching to battery
power. The new chassis design with an easy-to-access toolless front panel,
color-coded rear panel, and captive screws for battery panel access make
installations and battery changes simple and fast. The PR750RTXL2U also has
a new LCD panel that rotates 90°, tilts for a better viewing angle, and provides
information on 47 dierent settings including UPS stats, UPS setup and
control management, and testing options.
TYPICAL APPLICATIONS
Servers
Workstations
Network Devices
Telecom Equipment
FEATURES
750 VA/750 W
Line Interactive Topology
GreenPower UPS
2U Rack Mount/Tower Convertible
PR750RTXL2U
SMART APP
SINEWAVE UPS
PR750RTXL2U
SMART APP SINEWAVE UPS
SPECIFICATIONS CONT.
©2018 Cyber Power Systems (USA), Inc. CyberPower is a registered trademark and brand of Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property
of their respective owners. CyberPower reserves the right to change, without notice, marketing programs, product oerings and specifications. www.cyberpowersystems.com
OUTPUT CONT.
Rated Power Factor 1
Overload Protection Internal Circuitry Limiting
Circuit Breaker
Transfer Time 4ms typical
BATTERY
Extended Battery Module BP48VP2U01
Runtime at Half Load
(min) 28.7
Runtime at Full Load
(min) 11.2
Battery Type Sealed Lead-Acid
Battery Size 12 V/7 AH
Hot-Swappable Yes
Replacement Battery RB1270X4H
Battery Quantity 4
User Replaceable Yes
Typical Recharge Time 3 hrs
External Battery
Pack Option Yes
SURGE PROTECTION & FILTERING
RJ11/RJ45 1-in, 1-out
Surge Suppression 2430
EMI/RFI Filtration Yes
MANAGEMENT & COMMUNICATIONS
Multifunction LCD Panel
47 Settings (27 setup and control
items + 20 status updates and log
menus)
HID Compliant USB Port Yes
Serial Port Yes
EPO Port Yes
Contact Closure Yes
Management Cable USB Cable, Serial Cable,
EPO Cable
MANAGEMENT & COMMUNICATIONS CONT.
LED Indicators
Power On, Line Mode, Battery
Mode, Fault, Night Mode,
Wiring Fault
Audible Alarms Battery Mode, Low Battery,
Overload, Overcharge, Overheat
Software PowerPanel® Business Edition
SNMP/HTTP Remote
Monitoring Yes - with Optional RMCARD205
PHYSICAL
Rack Size 2U
Form Factor Rack/Tower
Dimensions (WxHxD) (in.) 17.1 x 3.4 x 16.2
Weight (lbs.) 53.1
Shipping Dimensions
(WxHxD) (in.) 22.1 x 10.8 x 20.9
Shipping Weight (lbs.) 61.1
ENVIRONMENTAL
Operating Temperature 32°F to 104°F (0°C to 4C)
Operating Relative
Humidity 0 – 95% (non-condensing)
Storage Temperature F to 113°F (-15°C to 45°C)
Maximum Operating
Elevation 10,000 ft (3,000 m)
Maximum Storage Elevation 50,000 ft (15,000 m)
AC Mode Thermal
Dissipation 41.3
CERTIFICATIONS
Safety RoHS Compliant
Environmental UL1778, cUL107.1, FCC Class B
WARRANTY
Product Warranty Three-Years Limited
Connected Equipment
Guarantee Lifetime
CEG Amount $400,000


Product specificaties

Merk: CyberPower
Categorie: Niet gecategoriseerd
Model: PR750RTXL2U
Kleur van het product: Zwart
Gewicht: 21300 g
Breedte: 433 mm
Diepte: 412 mm
Hoogte: 86.6 mm
Snoerlengte: 2.54 m
Gewicht verpakking: 27714.5 g
Breedte verpakking: 561.34 mm
Diepte verpakking: 530.86 mm
Hoogte verpakking: 274.32 mm
Gebruikershandleiding: Ja
LED-indicatoren: Ja
Vormfactor: Rackmontage/toren
USB-poort: Ja
Meegeleverde kabels: RS-232, USB cable
Ingebouwde ventilator: Ja
Accu/Batterij voltage: 12 V
Soort serieële aansluiting: RS-232
Aantal Ethernet LAN (RJ-45)-poorten: 2
Ondersteund aantal accu's/batterijen: 4
RS-232 port: 1
Geluidsalarm(en): Ja
Duurzaamheidscertificaten: RoHS, ENERGY STAR
Uitgangsvermogen: 750 W
Batterij capaciteit: 7 Ah
Temperatuur bij opslag: -15 - 45 °C
Frequentie: 47/63 Hz
Luchtvochtigheid bij opslag: 0 - 95 procent
Veiligheid: UL1778, cUL107.1, FCC Class B
Hoogte, in bedrijf: 0 - 3000 m
Hoogte bij opslag: 0 - 15000 m
Inclusief schroeven: Ja
Type koeling: Actief
Rackcapaciteit: 2U
Bedrijfstemperatuur (T-T): 0 - 40 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 95 procent
Batterijtechnologie: Sealed Lead Acid (VRLA)
Type beeldscherm: LCD
Type batterij: RB1270X4H
Surge energy rating: 2430 J
Aantal AC uitgangen: 8 AC-uitgang(en)
Stopcontacttypes: NEMA 5–15R
Rekbevestigingspakket: Ja
Output power capacity: 0.75 kVA
Ingang operation voltage (min): 100 V
Ingang operation voltage (max): 125 V
Uitgang operation voltage (min): 100 V
Uitgang operation voltage (max): 125 V
UPS-topologie: Line-interactive
Typische backup tijd op halve lading: 28.7 min
Typische backup tijd op volledige lading: 11.2 min
Hot-swap batterij: Ja
Seriële interface: Ja
Hoorbare alarmstanden: Alarm when on battery, Low battery alarm, Overload alarm
EMI/RFI geluidsfiltering: Ja
Golfvorm: Sinus
Automatic Voltage Regulation (AVR): Ja
Oplaadduur batterij: 3 uur
Power Factor Correctie (PFC) type: Actief