Carrier ClimaVision 7C-HS-C2W-X Handleiding
Carrier Thermostaat ClimaVision 7C-HS-C2W-X
Bekijk gratis de handleiding van Carrier ClimaVision 7C-HS-C2W-X (4 pagina’s), behorend tot de categorie Thermostaat. Deze gids werd als nuttig beoordeeld door 80 mensen en kreeg gemiddeld 4.6 sterren uit 7 reviews. Heb je een vraag over Carrier ClimaVision 7C-HS-C2W-X of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/4

For more information, contact your local Carrier Controls Expert
©2023 Carrier. All Rights Reserved. Cat. No. 11-808-959-01
INTRODUCTION
HyperStat is a wall-mount thermostat. Its thoughtful design ensures that it blends into most
commercial spaces while still giving a fresh and contemporary feel compared to dated
building control interfaces.
PACKAGE CONTENTS
•HyperStat device
•Mounting accessories
SPECIFICATIONS
Power
Power Source: 24VAC/DC input (+/- 15%)
Peak consumption: 1.4VAMaximum
Operating range
Temperature 32to 122°F (0°C to 50°C)
Humidity 20-85% non-condensing.
Communication
Sensor bus for daisy chained sensor communication and low power 3V dc.
4-wire interface for RS 485 communication @ 115200 baud and 5V
DC, 100mA power source
900-928 MHz Mesh IEEE 802.15.4-compliant, for communications to CCU
Bluetooth: BLE 4.1for commissioning, and communication to wireless sensors
Onboard Sensors
Temperature range of 32to 122°F with an accuracy of +/-1°F
Humidity 0 to 100% with an accuracy of 2%
CO2 sensor with a range of0 - 40,000 ppm, accuracy of +/-30ppm
VOC sensor; Typical Accuracy: 15% of measured value; TVOC: 0 - 60,000
ppb;
Occupancy sensor based on passive infrared (PIR) witha
detection range of
4m with a 15-degree angle
Light Sensor. Ambient light sensor • <100 LUX resolution • High-accuracy UV
index sensor • Matches erythermal curve
Sound sensor with 40-120dB response for 100Hz to 10KHz
PM2.5, PM10 sensor (optional). Detection range of 0-1000µg/m3 and accuracy
of +/-10µg/m3 (PM2.5, 0-100µg/m3) or +/-25µg/m3 (PM10, 0-
100µg/m3).Maximum long-term mass concentration precision limit drift:
•0 to 100 µg/m3 ±1.25 µg/m3/year
•100 to 1000 µg/m3 ±1.25 % mV/year
Inputs
2 x 10K Type-2 thermistor inputs with 2% accuracy
2 x 0-10V Analog voltage inputs with 2% detection accuracy (2-10V)
Touch slider for temperature control along with 3 mechanical buttons
HYPERSTAT
(7C-HS-C2W-X)
INSTALLATION GUIDE
Scan this QR
code to get a
more detailed
version of the
Installation
Guide
Product specificaties
| Merk: | Carrier |
| Categorie: | Thermostaat |
| Model: | ClimaVision 7C-HS-C2W-X |
Heb je hulp nodig?
Als je hulp nodig hebt met Carrier ClimaVision 7C-HS-C2W-X stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Thermostaat Carrier
26 Augustus 2025
12 Mei 2025
9 Januari 2024
9 Januari 2024
9 Januari 2024
9 Januari 2024
9 Januari 2024
8 Januari 2024
8 Januari 2024
8 Januari 2024
Handleiding Thermostaat
Nieuwste handleidingen voor Thermostaat
6 April 2026
1 April 2026
1 April 2026
30 Maart 2026
13 Maart 2026
12 Maart 2026
12 Maart 2026
16 Januari 2026
23 December 2025
22 December 2025