Bekijk gratis de handleiding van Bosch MB-PWR (12 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 43 mensen en kreeg gemiddeld 4.7 sterren uit 2 reviews. Heb je een vraag over Bosch MB-PWR of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/12

BOSCH HMB
Installation Instructions
OVERVIEW - Engineer’s Specification
The BOSCH HMB system shall include one Master Panel and one or more Distributed
Panels. The system shall be microprocessor based, and shall be compatible for use with
contact closures from the Fire Alarm Control Panel, (FACP). The system shall have a high-
speed communication bus and have the capacity for 6 channels of combined audio and data
on a single pair of wires. The field wiring for the communication bus may be configured for
either Style 4 or Style 7 supervision. The system shall have the capacity for Fire Fighters
Phone communication. The system shall have a minimum capacity of 2048 monitor and
control points.
The Master Panel shall contain an integral microphone, dual channel digital message
repeater, (DMR) and digital tone generator, 120 VAC power supply, and battery charger. The
system shall be modular in design, and shall be expandable such that additional system
control points may be configured. The system shall include integral self-diagnostic routines
that shall continually monitor system status, and shall indicate the precise type of trouble
conditions should they occur in the system. A trouble condition within the system shall cause
a trouble indication to be transmitted to the FACP.
Distributed panels shall provide a minimum of 4 Class "B" (Style Y) speaker circuits,
expandable to eight total. Alternately, panel may be configured for 4 Class "A" (Style Z)
speaker circuits. Panel will provide up to 6 simultaneous audio channels, up to 16 Fire
Phone circuits. Amplifiers will contain their own power supplies, battery chargers and provide
auxiliary power for other components. Speaker circuits shall be supervised for short and open
circuit conditions, and shall be able to withstand transient or continuous short-circuit
conditions without damage to the system.
System may be configured for General Alarm All Call operation, Alarm by Zone or
Floor Above / Floor Below as required. Contact closures shall allow immediate broadcast of
an alarm signal and evacuation message to the appropriate area. Non-Alarm areas may
receive alert tones and messages as required or activated by the FACP.
The alarm signal/evacuation message shall be broadcast until the FACP is reset, or until
emergency personnel interrupt the broadcast with a manual page.
To prevent unauthorized tampering, the voice evacuation system shall disable the
microphone if the microphone is keyed continuously for 3 minutes or more. Systems that do
not have this feature shall not be acceptable.
P/N B-5010 REV. C
130 Perinton Parkway, Fairport, NY 11450
Customer Service: (800) 289-0096
Technical Support: (888) 886-6189
Product specificaties
| Merk: | Bosch |
| Categorie: | Niet gecategoriseerd |
| Model: | MB-PWR |
| Producttype: | Voeding |
| Stroom: | 1 A |
| Aantal per verpakking: | 1 stuk(s) |
| Ingangsspanning: | 120 V |
| Merkcompatibiliteit: | Bosch |
| Frequentie: | 60 Hz |
| Type product: | Voeding |
Heb je hulp nodig?
Als je hulp nodig hebt met Bosch MB-PWR stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Bosch
13 Augustus 2026
11 Augustus 2026
11 Augustus 2026
10 Augustus 2026
21 Juli 2026
8 Juli 2026
1 Juni 2026
27 Mei 2026
26 Mei 2026
Handleiding Niet gecategoriseerd
Nieuwste handleidingen voor Niet gecategoriseerd
25 Augustus 2026
25 Augustus 2026
25 Augustus 2026
25 Augustus 2026
25 Augustus 2026
25 Augustus 2026
25 Augustus 2026
25 Augustus 2026
25 Augustus 2026
25 Augustus 2026