Bosch D192G Handleiding


Lees hieronder de đź“– handleiding in het Nederlandse voor Bosch D192G (3 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 104 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/3
Fire Alarm Systems | D192G Notification appliance module
D192G Notification appliance module
www.boschsecurity.com
uSupervises 12 VDC or 24 VDC notification appliance
circuits (NACs)
uSupervised signal silencing switch
uNotification appliance circuit rated at 3.0 A
uMultiple module configurations
uMounts in panel enclosure
This module is used for wiring connections to remote
signaling devices. You can connect up to twelve
D192G modules to the same system on compatible
control panels. Wiring is supervised for open, short, or
grounded circuit faults.
The module powers notification appliances from the
control panel power supply or from an Underwriters
Laboratories, Inc. (UL 1481) Listed auxiliary 12 VDC or
24 VDC regulated/power‑limited power supply for fire
protective signaling units and commercial/residential
burglar units. This feature allows the system to
support more signaling devices on longer wire runs. It
also allows the use of 12 V or 24 V notification
appliances requiring the appropriate power supply.
Functions
Supervises 12 VDC or 24 VDC NACs
The D192G powers the notification devices from either
the control panel's power supply or from a UL Listed
Auxiliary 12 VDC or 24 VDC regulated power-limited
power supply for use with Fire Protective Signaling
Units and Commercial and Residential Burglar Units.
The choice of power supply allows the use of 12 V or
24 V notification devices.
Supervised Signal Silencing Switch
The D192G module has a toggle switch for silencing
the notification devices while testing the alarm panel.
When this toggle switch is in the Silence (Off)
position, the module indicates a supervisory trouble
condition to the control panel.
Multiple Module Configurations
Several modules can be connected to the same zone
or point on the control panel. If individual
annunciation of a notification appliance circuit is
desired, D192G modules can be connected to
separate zones or points on‑board or through the
D8128D OctoPOPIT Eight‑point Expander.
Mounts in Panel Enclosure
The D192G mounts inside the control panel enclosure
using existing mounting holes or with a D137 or D138
Mounting Bracket. Refer to the control panel's
installation guide for more information on mounting.
Certifications and approvals
Region Regulatory compliance/quality marks
USA UL AMCX: Central Station Alarm Units
(UL1610,UL1635), APAW: Police Sta-
tion Alarm Units (UL365, UL464),
APOU: Proprietary Alarm Units
(UL1076), NBSX: Household Burglar
Alarm System Units (IL1023), UOJZ:
Control Units, System (UL864, 9th edi-
tion)
UL UL 864 - Standard for Control Units and
Accessories for Fire Alarm Systems
(10th edition)
UL UL 985 - Household Fire Warning Sys-
tem Units (6th edition)
CSFM California State Fire Marshal
FDNY-
CoA
6286 D7412GV4 D9412GV4 NYC COA
6286 2018-2021
NYC-
MEA
12-92-E, Vol. 12 12-92-E, Vol. 12
NYC-
MEA
12-92-E, Vol. XV
Installation/configuration notes
Compatibility Information
Category Product I
Control Panels G‑series
1
B‑series2
D94123, D74123, D72123*
D91243
Detectors For a list of compatible two wire detectors, refer
to the
Approved Applications Compliance Guide
for the control panel being used.
Modules D8128D OctoPOPIT Eight‑point Expander
Mounting
Brackets
D137 Mounting Bracket
D138 Mounting Bracket, Right Angle
1 G-series = D9412GV4, D7412GV4, D7212GV4*, D9412GV3,
D7412GV3, D7212GV3*, D9412GV2, D7412GV2, D7212GV2*,
D9412G3, D7412G3, D7212G3*
2 B series = B5512 and B4512
3 These products are legacy products and have been investigated for
compatibility only to UL864 8th edition
* The D7212 models are not listed for commercial fire applications
Notification Appliances
Notification appliances used with the D192G Module
must:
• Be polarized (DC) equipment
• Match the voltage rating of the alarm power supply
• Not exceed the current rating of the alarm power
supply
• Not exceed 3.0 A in combined device current for each
D192G Module
Wiring
Use a Class B, Style W, two-wire circuit and wire
according to the instructions supplied with the
module. No more than twelve D192G modules can be
used per system. For UL applications, a listed (UTRZ)
regulated power supply can be used to power
notification devices through the D192G module.
To comply with NFPA Standards:
• The control panel and power supply must be
supervised or installed in the same room not more
than 20 ft (6 m) from the module
• Wiring between the control panel and the power
supply must be in conduit
• Power supply fault conditions must be supervised by
a UL Listed relay
Parts included
Quan
tity
Component
1 NAC module
1 Hardware pack
1 Literature pack
Technical specifications
Electrical
External Power In
External Power In
External Power In
External Power InExternal Power In
Current: 3.0 A maximum
Voltage: 12 VDC or 24 VDC nominal
Aux Power In
Aux Power In
Aux Power In
Aux Power InAux Power In
Current: 100 mA maximum
Voltage: 12 VDC nominal
Supervisory Zone Control
Supervisory Zone Control
Supervisory Zone Control
Supervisory Zone ControlSupervisory Zone Control
Current: 5 mA maximum
Mechanical
Dimensions: 5 in. x 3 in. x 0.75 in. (13 cm x 8 cm x 2 cm)
Ordering information
D192G Notification appliance module
The D192G Notification Appliance Circuit (NAC)
module is used for wiring connections to remote
signaling devices. The wiring is supervised for open,
short, or grounded circuit faults. Either 12 VDC or
24 VDC notification devices can be used depending on
the choice of power supply.
Order number D192G
2 | D192G Notification appliance module
3 | D192G Notification appliance module
Represented by:
Europe, Middle East, Africa: Germany: North America: Asia-Pacific:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
emea.securitysystems@bosch.com
emea.boschsecurity.com
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Ring 5
85630 Grasbrunn
Germany
www.boschsecurity.com
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
onlinehelp@us.bosch.com
www.boschsecurity.us
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
© Bosch Security Systems 2020 | Data subject to change without notice
2537484427 | en, V11, 25. Jun 2020


Product specificaties

Merk: Bosch
Categorie: Niet gecategoriseerd
Model: D192G
Kleur van het product: Black, Green
Breedte: 130 mm
Diepte: 80 mm
Hoogte: 20 mm

Heb je hulp nodig?

Als je hulp nodig hebt met Bosch D192G stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Bosch

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd