Apc SURT1000XLI-BNDL Handleiding

Apc UPS SURT1000XLI-BNDL

Lees hieronder de 📖 handleiding in het Nederlandse voor Apc SURT1000XLI-BNDL (21 pagina's) in de categorie UPS. Deze handleiding was nuttig voor 36 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/21
990-1060B 12/2005
APC Smart-UPS® RT
1000/2000 VA
220/230/240 VAC
Tower/Rack Mount 2U
Uninterruptible Power Supply
User Manual
English
1 990-1060B 12/2005
1: SAFETY INFORMATION
American Power Conversion Corporation (APC) is the leading national and international manufac-
turer of state-of-the-art uninterruptible power supplies, redundant switches, power management soft-
ware, and related equipment. APC products protect hardware, software, and data from the threat of
power disturbances in business and government offices throughout the world.
The APC Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags,
and surges from reaching your computer and other valuable electronic equipment. The UPS filters
out small utility line fluctuations and isolates your equipment from large disturbances by internally
disconnecting from the utility line. The UPS provides continuous power from its internal battery until
the utility line returns to safe levels.
Changes or modifications to this unit not expressly approved by the party
responsible for compliance could void the warranty.
H S ANDLING AFETY
Be careful. Do not lift heavy loads without assistance.
<18 kg (<40 lb) 32–55 kg (70–120 lb)
18–32 kg (40–70 lb) >55 kg (>120 lb)
This equipment is intended for installation in a temperature-controlled indoor area free of conductive
contaminants. Refer to Specifications at the APC web site for the actual temperature range.
E S LECTRICAL AFETY
• To reduce the risk of fire, connect only to a circuit provided with a 30 Amp maximum branch
circuit overcurrent protection in accordance with the National Electrical Code ANSI/NFPA or
country specific electrical code.
• Do not work alone under hazardous conditions.
• Check that the power cord(s), plug(s), and sockets are in good condition.
• To reduce the risk of electric shock when grounding, disconnect the equipment from the AC
power outlet before installing or connecting to other equipment. Reconnect the power cord only
after all connections are made.
• Use one hand, whenever possible, to connect or disconnect signal cables to avoid a possible
shock from touching two surfaces with different electrical grounds.
• Connect the equipment to a three wire AC outlet (two poles plus ground). The receptacle must
be connected to appropriate branch circuit/mains protection (fuse or circuit breaker). Connection
to any other type of receptacle may result in a shock hazard.


Product specificaties

Merk: Apc
Categorie: UPS
Model: SURT1000XLI-BNDL
Kleur van het product: Zwart
Gewicht: 23000 g
Breedte: 85 mm
Diepte: 483 mm
Hoogte: 432 mm
Geluidsniveau: 50 dB
Gewicht verpakking: 27800 g
Breedte verpakking: 630 mm
Diepte verpakking: 594 mm
Hoogte verpakking: 286 mm
Internationale veiligheidscode (IP): IP20
LED-indicatoren: Ja
Vormfactor: Rackmontage
Certificering: C-tick, CE, EN 50091-1, EN 50091-2, EN 55022 Class A, EN 60950, EN 61000-3-2, GOST, VDE\r\nREACH
RS-232 port: 1
Geluidsalarm(en): Ja
Duurzaamheidscertificaten: RoHS
Uitgangsvermogen: 700 W
Accu/Batterij oplaadtijd: 3 uur
Temperatuur bij opslag: -20 - 50 °C
Frequentie: 45/65 Hz
Luchtvochtigheid bij opslag: 0 - 95 procent
Hoogte, in bedrijf: 0 - 3000 m
Hoogte bij opslag: 0 - 15000 m
Stekker: C14 stekker
Auto-herstart: Ja
Efficientie: 89.1 procent
Rackcapaciteit: 2U
Bedrijfstemperatuur (T-T): 0 - 40 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 95 procent
Batterijtechnologie: Sealed Lead Acid (VRLA)
Type beeldscherm: LED
Type batterij: RBC31
Aantal batterijcellen: 1
Surge energy rating: 420 J
Aantal AC uitgangen: 6 AC-uitgang(en)
Nominale input voltage: 230 V
Stopcontacttypes: C13 stekker
Output power capacity: 1 kVA
Ingang operation voltage (min): 100 V
Ingang operation voltage (max): 280 V
Uitgang operation voltage (min): 220 V
Uitgang operation voltage (max): 240 V
Crest factor: 3:1
UPS-topologie: Dubbele conversie (online)
Typische backup tijd op halve lading: - min
Typische backup tijd op volledige lading: - min
Hot-swap batterij: Ja
Netspanning, in bedrijf: 230 V
Emergency Power Off (EPO): O
Spanningsbeveiliging: Ja
Golfvorm: Sinus
Koude start: Ja
Number of output IEC jumpers: 2
Automatische batterij test: Ja