Apc NetBotz NBES0301 Handleiding

Apc Niet gecategoriseerd NetBotz NBES0301

Lees hieronder de 📖 handleiding in het Nederlandse voor Apc NetBotz NBES0301 (2 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 32 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
NetBotz® Spot Fluid Sensor (NBES0301)
Installation Instructions
The NetBotz Spot Fluid Sensor enables you to monitor a remote location for the presence of any
liquid with a resistivity of less than 2 MOhms per cm (including distilled water).
Note: You can extend the length of the cable up to 30.5 m (100 ft) using the RJ-45
coupling and standard CAT-5 cabling.
Installation
1. Place the fluid-sensing portion of the NetBotz Spot Fluid Sensor at the location that you want
to monitor. The four fluid sensor contacts should be in direct contact with the surface.
2. Plug the cable into an available Sensor Port on your NetBotz appliance
Spot Fluid Sensor
Plastic insulation sheet
203-mm (8-in) tie wraps (10) Adhesive cable tie holders (5)
RJ-45 coupling (1)
Customer support and warranty is available at the APC Web site information , www.apc.com.
© 2013 Schneider Electric. APC, the APC logo, InfraStruxure, and NetBotz are owned by Schneider Electric
Industries S.A.S.or their affiliated companies. All other trademarks are property of their respective owners.
990-3294A
0 /203 13
Using the Insulator Sheet on a Conductive
Surface
The NetBotz Spot Fluid Sensor uses electronic
circuits to detect the presence of fluid. If the sensor
contacts are shorted, the uid detection circuits
will not work. Shorting can occur when the sensor
is placed on a metal surface, or on some materials,
such as cement ooring (particularly cement that is
wet), that may be conductive and grounded.
Place the Spot Fluid Sensor on the provided insulator sheet to avoid shorting the contacts.
Configuring the Spot Fluid Sensor
Once the Spot Fluid Sensor is conected to the NetBotz Appliance, it will be detected automatically,
and will appear in the Sensor Readings pane.
The Spot Fluid Sensor is a normally open (NO) dry contact sensor. Use the Dry Contact task to
configure the settings for the NetBotz Spot Fluid Sensor. See the NetBotz Appliance User’s Guide
for more information about the Advanced View.
Caring For and Cleaning Your Sensor
While your Spot Fluid Sensor is fluid-resistant, it is intended for leak detection only and is not
designed to be immersed for extended periods of time. Use only plain tap water to clean your Spot
Fluid Sensor. Do not use soap or detergents of any kind. In addition, the RJ-45 coupling should not
be an area where water will collect or condensation may form, as this may corrode the coupling.


Product specificaties

Merk: Apc
Categorie: Niet gecategoriseerd
Model: NetBotz NBES0301

Heb je hulp nodig?

Als je hulp nodig hebt met Apc NetBotz NBES0301 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Apc

Apc

Apc SP3OPT008 Handleiding

26 Februari 2024
Apc

Apc P4V Handleiding

27 November 2023
Apc

Apc ACRC100 Handleiding

31 Augustus 2023
Apc

Apc UTS10BI Handleiding

3 Augustus 2023
Apc

Apc AP7768 Handleiding

3 Augustus 2023
Apc

Apc UTS6H Handleiding

3 Augustus 2023
Apc

Apc PDPM144F Handleiding

3 Augustus 2023

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd