Air King AKZA200D Handleiding

Air King Afzuigkap AKZA200D

Lees hieronder de 📖 handleiding in het Nederlandse voor Air King AKZA200D (8 pagina's) in de categorie Afzuigkap. Deze handleiding was nuttig voor 19 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/8
IMPORTANT INSTRUCTIONS -
OPERATING MANUAL
SAVE THESE INSTRUCTIONS
www.airkinglimited.com
6727926 Rev. C 6-18 1 of 8
Exhaust Fan
AKZA200D, AKZA200D1
READ AND SAVE THESE INSTRUCTIONS
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN
THE PRODUCT DESCRIBED. PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY
INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL
INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
GENERAL SAFETY INFORMATION
When using electrical appliances, basic precautions should
always be followed to reduce the risk of fire, electric shock and
injury to person, including the following:
WARNING: TO REDUCE THE RISK
OF FIRE, ELECTRIC SHOCK AND INJURY TO
PERSON, OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you have
questions, contact the manufacturer.
b) Before servicing or cleaning the unit, switch power off at service
panel and lock the service disconnecting means to prevent power
from being switched on accidentally. When the service disconnecting
means cannot be locked, securely fasten a prominent warning
device, such as a tag, to the service panel.
WARNING: TO REDUCE THE RISK
OF FIRE, ELECTRIC SHOCK AND INJURY TO
PERSON, OBSERVE THE FOLLOWING:
a) Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-related construction.
b) Sufficient air is needed for proper combustion and exhausting of
gases through the flue (chimney) of fuel burning equipment to prevent
back drafting. Follow the heating equipment manufacturer’s guideline
and safety standards such as those published by the National Fire
Protection Association (NFPA) and the American Society for Heating,
Refrigeration, and Air Conditioning Engineers (ASHRAE), and the local
code authorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
CAUTION: FOR GENERAL VENTILATING USE ONLY.
DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE
MATERIALS AND VAPORS.
d) Ducted fans must always be vented to the outdoors.
e) This unit must be grounded.
f) To avoid motor bearing damage and noisy and/or unbalanced impellers,
keep drywall spray, construction dust, etc. off power unit.
g) Read all instructions before installing or using exhaust fan.
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK, DO NOT USE THIS FAN WITH
ANY SOLID-STATE SPEED CONTROL DEVICE.
WARNING: DO NOT USE IN KITCHENS.
WARNING: THE DUCTING FROM THIS FAN TO THE
OUTSIDE OF THE BUILDING HAS A STRONG EFFECT
ON THE AIR FLOW, NOISE AND ENERGY USE OF THE FAN. USE
THE SHORTEST, STRAIGHTEST DUCT ROUTING POSSIBLE FOR
BEST PERFORMANCE, AND AVOID INSTALLING THE FAN WITH
SMALLER DUCTS THAN RECOMMENDED. INSULATION AROUND
THE DUCTS CAN REDUCE ENERGY LOSS AND INHIBIT MOLD
GROWTH. FANS INSTALLED WITH EXISTING DUCTS MAY NOT
ACHIEVE THEIR RATED AIRFLOW.
INSTALLATION INSTRUCTIONS
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE STARTING INSTALLATION.
SECTION 1
Preparing the Exhaust Fan
1. Unpack fan from the carton and confirm that all pieces are present. In addition to the
exhaust fan you should have:
1 - Duct Adapter Panel
1 - Side Panel (attached)
1 - Damper Assembly (attached)
2 - Mounting Brackets
1 - Hardware bag
7 - Screws
4 - Nuts
1 - Instruction/Safety Sheet
2. Choose the location for your fan. To ensure the best air and sound performance, it is
recommended that the length of ducting and the number of elbows be kept to a minimum,
the radius of each elbow be as large as possible for the installation, and that insulated
hard ducting be used. This fan will require at least 12" of clearance in the ceiling or wall,
and will mount through drywall up to ½" thick. The fan mounts between 24" on center
joists using the provided mounting brackets.
3. No additional vibration deadening materials are needed for this fan.
SECTION 2
Determine Discharge
1. Determine if you will require the unit to exhaust vertically/horizontally or at a right angle
and install the included duct adapter panel accordingly, using the included screws
(Figure 1).
NOTE: In the right angle configuration the air will enter the unit and flow out the side at a 90°
angle. In the horizontal/vertical discharge configuration, the air will enter the unit and flow
directly out the other side.
2. Once the duct adapter panel is installed, using the same procedure as in Step 1, install
the side panel onto the open end of the housing (this will be dependent on how you
have chosen to exhaust the unit).
SECTION 3
Mounting to a Joist
1. If the mounting brackets are not already in place, install both brackets through the top
set of slots on the fan housing and secure in place with the four included nuts as shown.
Center the fan housing between the joists and secure the mounting brackets with screws
(not included) to the joist. Adjust the height of the housing so that it will be flush with the
finished ceiling by loosening the mounting bracket nuts and sliding the housing up or
down on the bracket. Full tighten all four nuts to secure the housing in place (Figure 2).
www.airkinglimited.com
6727926 Rev. C 6-18 2 of 8
SECTION 4
Hanging Installation
1. If the mounting brackets are not already in place, install both brackets through the top
set of slots on the fan housing and secure in place with the four included nuts as shown.
Lift unit up onto the threaded rods and secure in place using appropriate hardware (not
included) (Figure 3).
SECTION 5
Ducting
CAUTION: ALL DUCTING MUST COMPLY WITH LOCAL AND
NATIONAL BUILDING CODES.
NOTE: To ensure quiet operation, at least 8 feet of insulated flexible duct or insulated duct board
needs to be installed between the exhaust or supply grille(s) and the fan.
1. Before installing the ducting, make sure the fan’s 2 pin and 3 pin quick connect motor
cords are plugged into the corresponding receptacle located on the interior wire
compartment cover. These cords will only fit one way into the receptacles .(Figure 4)
2. Connect the ducting to the fan’s duct collar Seal ducting to housing with (Figure 5).
appropriately rated tape. Use screws (rectangular duct) or suitable clamps (round duct)
to secure in place. Do not allow screws to interfere with operation of damper. Always
duct the fan to the outside through a wall or roof cap. It is recommended that low
restriction termination fittings be used.
SECTION 6
Wiring
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE STARTING INSTALLATION.
CAUTION: ALL ELECTRICAL CONNECTIONS MUST BE
MADE IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR
NATIONAL ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF INSTALLING
ELECTRICAL WIRING, SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN.
NOTE: This unit includes a side access panel for wiring that does not require the removal of the
fan’s blower assembly.
1. Remove the wire compartment cover screw and place cover in a secure place (Figure 6).
Figure 2 Bracket
Housing
Nut
Joist
Figure 3 Bracket
Housing
Nut
Threaded Rod
Figure 5 Housing
Ducting
Duct Collar
Right Angle
Discharge
Horizontal/
Vertical
Discharge
Figure 1
Duct
Adapter
Screws
Figure 4
2. Continuous Ventilation: For two speed fans wired for continuous ventilation, connect
the White wire of the fan to the White (Neutral) wire from the power source. Connect the
ground wire from the house to the green wire from the fan housing. Run 2 wires from a
properly grounded wall switch (not included) to the fan. Connect the Black wire of the fan
to the Black wire (Hot) from the power source. Connect the Hot Yellow wire from the fan
to the input of the switch. Connect the second Yellow wire from the fan to the output side
of the switch. Closing the switch will change from normal to high speed. Use (Figure 7).
approved methods for all connections.
2b. Intermittent Ventilation: For two speed fans wired for intermittent ventilation with a
standard duplex toggle switch (such as Leviton 5224-2W not included). Connect the White
wire of the fan to the White (Neutral) wire from the power source. Connect the ground wire
from the fan to the ground wire from the power source. Properly ground the switches.
Connect the black wire from the supply to one side of the top switch. Connect the black wire
from the fan to the other side of the top switch, Connect 1 yellow wire from the fan to each
side of the bottom switch. The top switch turns the fan On & Off, the bottom switch changes
speed between high and low Use approved methods for all connections. (Figure 8).
NOTE: Unit must be grounded according to all local and national codes.
3. Carefully tuck wire back inside wire compartment and replace wire compartment cover
securing with the screw that was removed earlier.
www.airkinglimited.com
6727926 Rev. C 6-18 3 of 8
SECTION 7
Completing the Installation
NOTE: When fan is mounted inline and no penetration is made into unconditioned spaces, there
is no need to use a sealant appropriate for contact with the building materials present and for
the temperature requirements of the installation to prevent air leakage from unconditioned
spaces. Additional material (backing rod, ceiling material) are also not required.
NOTE: This fan is rated for direct insulation contact (Type IC) and it is recommended that this fan
be completely covered by insulation in order to reduce heat loss or gain to unconditioned space.
1. Restore power and test your installation.
SECTION 8
Access Panel
1. This unit includes a hinged access panel. This allows access to the interior of the fan
once installed. To access the interior, unscrew the screws holding the panel in place
(Figure 9).
2. Reinstall the access panel by making sure the tabs are inserted into the slots on the
housing and pivoting the panel back towards the housing. Using the screws removed in
step 1, reattach the panel.
SECTION 9
Activating the Boost Speed
If your unit is equipped with a boost speed, and it is determined that additional flow is necessary
due to excessive duct resistance or other field conditions activate the boost speed by:
1. Find the 2 wire harness from the fan motor to the capacitor.
2. Disconnect the harness from the capacitor at the quick connect fitting and remove the
“Boost Label” from the quick connecttting on the boost capacitor.
3. Plug the motor harness into the boost capacitor.
SECTION 10
Use and Care
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE SERVICING THE UNIT.
1. Cleaning the Fan Assembly: Wipe all parts with a dry cloth or gently vacuum the fan.
NEVER IMMERSE ELECTRICAL PARTS IN WATER.
CALIFORNIA RESIDENTS ONLY:
WARNING: THIS PRODUCT CAN EXPOSE YOU TO A CHEMICAL [OR
CHEMICALS] KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER.
WARNING: THIS PRODUCT CAN EXPOSE YOU TO A CHEMICAL
[OR CHEMICALS] KNOWN TO THE STATE OF CALIFORNIA TO CAUSE
REPRODUCTIVE TOXICITY.
Troubleshooting Guide
Trouble Probable Cause Suggested Remedy
1. Fan does not operate when the switch is on. 1a. A fuse may be blown or a circuit tripped. 1a. Replace fuse or reset circuit breaker.
1b. Connector plug from motor is not plugged in. 1b. Turn off power to unit. Remove Grill and plug motor into receptacle
in housing. Restore power to unit.
1c. Wiring is not connected properly. 1c. Turn off power to unit. Check that all wires are connected.
1d Motor has stopped operating. 1d. Replace motor.
2. Fan is operating, but air moves slower than normal. 2. Obstruction in the exhaust ducting. 2. Check for any obstructions in the ducting. The most common are bird
nests in the roof cap or wall cap where the fan exhausts to the outside.
3. Fan is operating louder than normal 3a. Motor is loose. 3a. Turn off power to unit. Remove grill and check that all screws are fully
tightened. Restore power to unit.
3b. Fan blade is hitting housing of unit. 3b. Call your dealer for service.
Figure 6
Screw
Wire
Compartment
Cover
Figure 9
Hinge
Tab
Figure 7
Supply from house
Black
Neutral (White)
Ground (Green or Bare)
Fan
Switch
Neutral (White)
Green
Yellow
Black
Yellow
Figure 8
Supply from house
Neutral (White)
Ground (Green or Bare)
Fan
Switch
Neutral (White)
Green
Black
Yellow
Yellow
Black


Product specificaties

Merk: Air King
Categorie: Afzuigkap
Model: AKZA200D

Heb je hulp nodig?

Als je hulp nodig hebt met Air King AKZA200D stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Afzuigkap Air King

Handleiding Afzuigkap

Nieuwste handleidingen voor Afzuigkap