Bekijk gratis de handleiding van Festo SDBT-BSW-1L-ZU-W-5-N-LE (1 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 25 mensen en kreeg gemiddeld 4.6 sterren uit 4 reviews. Heb je een vraag over Festo SDBT-BSW-1L-ZU-W-5-N-LE of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/1

Translation of the original instructions
© 2020 all rights reserved to Festo SE & Co. KG
1Applicable Documents
All available documents for the product www.festo.com/sp.è
2Safety
2.1Safety
–Before working on the electrics: switch off the voltage supply.
WARNING!
Risk of injury due to electric shock.
•For the electric power supply, use only PELV circuits that ensure a reliable
electric disconnection from the mains network.
•Observe IEC60204-1/EN60204-1.
2.2Intended use
This product is intended for sensing the position of magnets (e.g. the piston posi-
tion) in Festo products. The device is intended for use in an industrial environ-
ment.
2.2.1Area of application and approval
In combination with the UL inspection mark on the product, the information in this
section must also be observed in order to comply with the certification conditions
of Underwriters Laboratories Inc. (UL) for USA and Canada.
UL approval information
Product category codeNRKH, NRKH7
File numberE232949
Considered standardsUL 60947-1, CAN/CSA C22.2 No. 60947-1
UL 60947-5-2, CAN/CSA C22.2 No. 60947-5-2
UL mark
Industrial Control Equipment
2MD1
Tab. 1
Only for connection to a NEC/CEC Class 2 supply.
3Electrical connection
Circuit diagrams
SDBT-BSW-…-PU-…-M12SDBT-BSW-…-PU-…-LE
SDBT-BSW-…-NU-…-M12SDBT-BSW-…-NU-…-LE
SDBT-BSW-…-ZU-…-LE
Tab. 2
4Mechanical installation
Fig. 1 Mechanical installation
5Operating conditions
If the SDBT-BSW-...-PU or SDBT-BSW-...-NU is aligned at a right angle to the weld-
ing electrode or cable, it can result in maloperations in a limited range (applica-
tion-dependent).
Fig. 2 Operating conditions
Possible remedy:
–Adjust the distance between the proximity sensor and the source of malfunc-
tion (±20mm).
–Adjust the angle between the proximity sensor and the source of malfunction
(±20°).
–Adjust the strength of the welding current.
–On DW/DWA/DWB cylinders: mount sensor in a different position.
6Technical data
6.1Technical data UL
SDBT-BSW-…
Operating voltage range[VDC]10…30
Ambient temperature[°C]–25…+80
NEMA enclosure type number
(Enclosure Type Rating)
Type 1
Tab. 3
6.2Technical data, general
SDBT-BSW--PU/NUZU…
Operating voltage range[VDC]10…30
Max. output current[mA]10080
Max. switching capacity[W]2.81.9
Frequency of welding process
MFDC
[Hz]1000–
Frequency of welding process
AC
[Hz]50…60
Ambient temperature[°C]–25…+85
Ambient temperature with flex-
ible cable installation
[°C]–5…+80
Degree of protectionIP65, IP68
Tab. 4
8140618
SDBT-BSW-...
Proximity sensor
8140618
2020-07c
[8140620]
Operating instructions
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
Product specificaties
| Merk: | Festo |
| Categorie: | Niet gecategoriseerd |
| Model: | SDBT-BSW-1L-ZU-W-5-N-LE |
Heb je hulp nodig?
Als je hulp nodig hebt met Festo SDBT-BSW-1L-ZU-W-5-N-LE stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Festo
2 Augustus 2025
2 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
1 Augustus 2025
Handleiding Niet gecategoriseerd
Nieuwste handleidingen voor Niet gecategoriseerd
24 Januari 2026
24 Januari 2026
24 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026
23 Januari 2026